09-730-017EXISTING 6" STANDP SPRINKLER CONECTI( EXISTING WITH 2y2" GENERAL NOTES: 1. All Pipe Locations are to be Field Measured NPrior to Fabrication and Installation by Sprinkler Contractor. 2. All Dimensions Shown are Center to Center. 3. High Temperature Heads are to be Field Located Where Required. 4. All Pipes and Hangers are to be Installed per NFPA #13. 5. Hangers are to be U.L. Listed and F.M. Approved. Symbol Description O Hydraulic Reference Points Elev. Below Top of Steel LOCATION 1­61 Elev. Above Finished Floor TY —QR —FRB K:5.6 165° CHROME REC. PENDANT SPRINKLER Elev. of Top of Steel Ceiling Height = Denotes Hanger Location__- - NEW RECESED SPRINKLER HEAD s Rise up or down Number of Sprinklers Total This Sheet: 56 Total This Job: 367 (Phase:3) Symbol No. Description. (� 19 TY QR -RFII K:5.6 165° PEND. CONC. SPRINKLER W/WHITE COVER PATE 34 TY -QR -FRB K:5.6 165° CHROME REC. PEND. SPRINKLER C) 3 TY -QR K:5.6 155° BRASS UPRIGHT Drawn By: J LDT Scale: AS NOTED Date: 07 -23 -2009 - -- Approval By: J.T. Symbol I Revisions: Al I FIRE DEPT COMMENTS Date: 08/05/09 1,18 P LAN 1/2" MAIN SPRINKLER HEAD, LEGEND TYPE LOCATION TY —QR —RFII K:5.6 165° PENDANT CONCEALED SPRINKLER W /WHITE C. P. ALL LOBBYS, NURSES STATIONS, PUBLIC AREAS, & CORRIDORS TY —QR —FRB K:5.6 165° CHROME REC. PENDANT SPRINKLER ALL SPACES UNLESS NOTED OTHERWISE ABOVE SCOPE OF WORK EXISTING SPRINKLER SYSTEM, FIRE PUMP,& STANDPIPE WORK FOR PHASE 3 ONLY: HEAD RELOCATION FOR NEW FLOOR LAYOUT NO WORK ON OTHER PHASES UNDER THIS PERMIT Exsitinq 6th Connection Detail LEGEND EXISTING PIPING TO REMAIN South Miami Hospital NEW PIPING TO BE INSTALLED - EXISTING SPRINKLER HEAD TO BE REMOVED NEW CONECTION 7400 S.W. 62nd Ave. South Miami Florida 33143 NEW CONCEALED SPRINKLER HEAD NEW RECESED SPRINKLER HEAD s 0 NEW BRASS UPRIGHT SPRIN " ERAF � Y� EXISTING HEAD TO BE REPLACED (`SAME LOC TI.N) 6th Floor Fire Protectio SCALE: 3/6 " =1 ' -0" If, C.A. No.2435 7290 NW 44th STREET Miami, FL. 33166 Tel. (305) 994 9220 Fax. (305) 994 9210 SEAL: Jorge de la Torriente P.E. Reg.No.: 18690 g� r 0. e -3 JOB NAME: M w South Miami Hospital NO a. 7400 S.W. 62nd Ave. South Miami Florida 33143 Ll. W M z 6W Drawing Title: 6th Floor Fire Protection Phase:3 Permit Plan X