09-730-015EXISTING 6'
SPRINKLER
EXISTING
WITH 21 "
GENERAL NOTES:
1. All Pipe Locations are to be Field Measured
N Prior to Fabrication and Installation by
Sprinkler Contractor.
2. All Dimensions Shown are Center to Center.
3. High Temperature Heads are to be Field
Located Where Required.
4. All Pipes and Hangers are to be Installed
per NFPA #13.
5. Hangers are to be U.L. Listed and F.M.
Approved.
Symbol Description
0
Hydraulic Reference Points
LOCATION
Elev. Below Top of Steel
L 8 -61
Elev. Above Finished Floor
ALL SPACES UNLESS NOTED OTHERWISE ABOVE
Elev. of Top of Steel
>
_ ..._
.. .._.._ _ - --
Ceiling Height
. _
NEW CONCEALED SPRINKLER HEAD
Denotes Hanger Location_
NEW RECESED SPRINKLER HEAD
Rise up or down
Number of Sprinklers
Total This Sheet: 56 Total This Job: 367 (Phase:3)
Symbol No. Description: Drawn By
[J 16 TY- QR -RFII K:5.6 165° PEND. CONC. SPRINKLER W/WHITE COVER PLATE
37 TY -QR -FRB K:5.6 165° CHROME REC. PEND. SPRINKLER
__... _. .— tale:
3 TY -QR K:5.6 155° BRASS UPRIGHT
Date:
JLDT
AS NOTED
07 -24 -2009
. -- - ----I Approval By: J.T.
Symbol I Revisions:
SPRINKLER HEAD LEGEND
TYPE
LOCATION
TY— QR —RFII K:5.6 165° PENDANT CONCEALED
SPRINKLER W /WHITE C.P.
ALL LOBBYS, NURSES STATIONS,PUBLIC AREAS,AND
CORRIDORS
TY —QR —FRB K:5.6 165° CHROME REC. PENDANT
SPRINKLER
ALL SPACES UNLESS NOTED OTHERWISE ABOVE
SCOPE OF WORK
EXISTING SPRINKLER SYSTEM, FIRE PUMP,&
STANDPIPE
WORK FOR PHASE 3 ONLY: HEAD RELOC
FOR NEW FLOOR LAYOUT
NO WORK ON OTHER PHASES UNDER TI-
PERMIT
IRE HOSE CABINET
HOSE VALVE
ANDPIPE &
JECTION
Date:
Area of
This Pe
Key Plan: Phase:3
SCALE: N.T.S.
LEGEND
....
EXISTING PIPING TO REMAIN
South Miami Hospital
NEW PIPING TO BE INSTALLED
C)
EXISTING SPRINKLER HEAD TO BE REMOVED
Y
NEW CONECTION
Q
NEW CONCEALED SPRINKLER HEAD
II
NEW RECESED SPRINKLER HEAD
0
NEW BRASS UPRIGHT SPRINKLER HEAD
_l
EXISTING HEAD TO BE REPLACED (SAME LOCATION)
�r
DISAPPROVED Ely"
I DWAR10111
IUM
Fifth Floor Fire Protection Plan Phase 3
SCALE: 3/32"_I"
C.A. No.2435
7290 NW 44th STREET
Miami, FL. 33166
Tel. (305) 994 9220
Fax. (305) 994 9210
SE Li
a r e
Jorge de la Torriente
P.E. Reg.No.: 18690
JOB NAME:
�
co
L0
South Miami Hospital
a r e
Jorge de la Torriente
P.E. Reg.No.: 18690
JOB NAME:
�
co
L0
South Miami Hospital
0
N
CL
C)
Y
7400 S.W. 62nd Ave.
South Miami,Florida 33143
LL
W
II
m
Drawing Tale: 5th Floor Fire Protection
Phase:3 Permit Plan
a
co