09-730-001so1fJ
i
6
/6'
GENERAL NOTES:
1. All Pipe Locations are to be Field Measured
N Prior to Fabrication and Installation by
Sprinkler Contractor.
2, All Dimensions Shown are Center to Center.
3. High Temperature Heads are to be Field
Located Where Required.
4. All Pipes and Hangers are to be Installed
per NFPA #13.
5. Hangers are to be U.L. Listed and F.M.
Approved.
Symbol Description
Hydraulic Reference Points
Elev. Below Top of Steel
L Elev. Above Finished Floor
Elev. of Top of Steel
0_ .) Ceiling Height
Denotes Hanaer Location
«> I Rise up or down
Number of Sprinklers
Total This Sheet: 80 Total This Job: 367 (PHASE-.3)
Symbol No. Description:
47 TY- QR -RFII K:5.6 155° PEND. CONC. SPRINKLER W/WHITE COVER PLATE
20 TY -QR -FRB K:5.6 155° CHROME REC. PEND. SPRINKLER
(� 13 TY- QR'K:5.6 1550 BRASS UPRIGHT
6"
EXISTING UNDERGROUND TO
6 "X2Y2"X2J " SIAMESE
6"
Drawn By: JLDT
Scale: AS NOTED
Date: 07 -24 -2009
Approval By: J.T.
Symbol I Revisions: Date:
10 FIRE DEPT COMMENTS 08/05/09
1
i °n —.i1Li a'Y+a4^994PNIiflilffni � p� ` r`. d,
SPRINKLER HEAD LLEGEND
TYPE I i nrorinNi
TY— QR —RFII K:5.6 165° PENDANT CONCEALED
SPRINKLER W /WHITE C.P.
TY -QR -FRB K:5.6 165° CHROME REC. PENDANT
SPRINKLER
SCOPE OF WORK
SPRINKLER HEADS RELOCATION FOR NEW
FLOOR LAYOUT
PHASE 3 ONLY
NOTE:
"FIRE PUMP, STANDPIPE SYSTEM AI\
SPRINKLER SYSTEM ARE EXISTING"
$I*
Area of '
This Per
ALL LOBBYS, NURSES STATIONS,PUBLIC AREAS,AND
CORRIDORS
ALL SPACES UNLESS NOTED OTHERWISE ABOVE
i
kC.A. No.2435
7290 NW 44th STREET
Miami, FL. 33166
Tel. (305) 994 9220
Fax. (305) 994 9210
Key Plan: P ha_s_e_: 3
SCALE: N.T.S.
LEGEND
EXISTING PIPING TO REMAIN
NEW PIPING TO BE INSTALLED
EXISTING SPRINKLER HEAD TO BE REMOVED
NEW CONECTION
a
NEW CONCEALED SPRINKLER HEAD
NEW RECESED SPRINKLER HEAD
0
NEW BRASS UPRIGHT SPRINKLER HEAD
0
EXISTING HEAD TO BE REPLACED (SAME LOCATION)
o,
First Floor Over Ii,TF-
Fire Protection Plan n Phase :3
SCALE: 3/32 " =1 "
SEAL:
Jorge de la Torriente
P.E. Reg.No.: 18690
JOB NAME:
za ��
I (D
ao
South Miami Hospital { Y Q
IL '
7400 S.W. 62nd Ave.
South Miami,Florida 33143 w n
z
Drawing Title: First Floor Overall LIL
W F:
Fire Protection Plan Phase:'