09-73-0054100 -8201 Fire Alarm Control Panel - Node 4 - South Miami Hospital - 2nd Floor Main Tower PBX
Standby Total Norm Total
Module Qly Description Current Standby Current Nam
Panel Equipment
4100 -8201
1
COMM PANEL W AUDIO
0.000000
0.000000
0.000000
0.060000
4100 -7003
1
MASTER CONTROLLER
0.292000
0.292000
0.292000
0.292000
4100 -6051
1
NON -POWER LIMITED OPTION
0.000000
0.000000
0.000OOD
0.000000
4100 -4321
9
6 CIRCUIT CLASS B STYLE
0.025000
0.225000
0.070000
0.630000
4100 -3003
1
8 FT AUX RELAY MOD 3 AMP
0.025000
0.025000
0.280000
0.280000
4100-0108
2
EXPANSION 120V RAMP POWER SUPP
0.000000
0.000000
0.000000
0.000000
4100 -0110
2
MAPNET 0 ADDRESSABLE MALE
0.270000
0.540000
0.290000
0.580000
4100 -0210
1
SINGLE CHANNEL AUDID CONTROL
0.185000
0.105000
0.185000
0.185000
4100-0203
1
100 WATT AMPLIFIER
0.068000
0.068000
8.750000
8.750000
4100-0215
1
PHONE RISER TERMINATION BOARD
0.000000
0.000000
0.000000
0.000000
4100 -0301
1
64/64 LED/SWITCH CONTROLLER
0.015000
0.015000
0.260000
0.260000
4100 -0412
1
1 CHANNEL AUDIO CONTROL SWITCH
0.000000
0.000000
0.000000
0.000000
4100 -200.3
2
PKG SIZE, 6 UNIT, GLASS DR
1 0.000000
0.000000
1 0.000000
0.000000
4100 -0142
2
WIRED MEDIA MODULE
0.040000
0.0800011
0.040000
0.080000
4100 -6014
1
NETWORK IF CARD, WIRED
0.046000
0.046000
0.046000
0.046000
3.2 Ohms
Total Panel
1.476000
Total Pond Alarm
11.103000
Peripheral Devices
4099 -9001
23
IDNET SINGLE ACTION PULL STATION •
0.000000
0.000000
0.000000
0.000000
4098 -9733
0
TRUEALARM HEAT SENSOR
0.000000
0.000000
0.000000
0.000000
4098 -9714
123
TRUDI M PHOTO SMOKE SENSOR
0.000000
0.000000
0.000000
0.000000
4098 -9792
123
TRUEALARM SENSOR BASE •
0.000000
O.OD0000
0.000000
0.000000
4098 -9756
5
TRUFAL M DUCT SMOKE SENSOR ?Z RELAY OUTPUT •2
0.002400
0.012000
0.015000
0.075000
2098 -9797
5
SAMPLING TUBE 49°
0.000000
0.000000
0.000000
0.000000
2098 -9806
5
REMOTE TEST STATION W LED AND KEY SWITCH
0.000000
0.000000
0.000000
0.000000
4098 -9843
4
ENCAPSULATED RELAY PAM -SD
0.002400
0.009600
0.015000
0.060000
4090 -9001
19
IDNET SUPERVISED IAM •
0.000000
0.000000
0.000000
0.000000
2190 -9161
1
MAPNET CLASS B SIGNAL ZAM *
0.015000
0.015000
0.040000
0.040000
2190 -9163
0
MAPNET UNSUPERVISED CONTROL. ZAM •
0.010000
0.000000
0.040000
0.000000
2088 -9032
5
RELAY SPOT Wjtp MR -801
0.000000
0.000000
0.022000
0.110000
2190 -9162
1
MAPNET CLASS B SIGNAL ZAM •
0.015000
0.01500D
0.040000
0.040000
4903 - 9150
40
15CD SPNP6PU RED HDRIZONTAL MOUNT 25 OR 71NVRMS
0.000000
0.000000
0.082000
3.280000
4903 -9148
4
30CD SPEAKER RED HORIZONTAL MOUNT 25 OR 70VRMS
0.000000
0.0000110
0.123000
0.492000
4903 -9149
1
11OCD SPEAKER BLE RED HORIZONTAL MOUNT 25 OR 70VRUS
0.000000
0.000000
0.275000
0.275000
4904 -9176
13
15CD VISIBLE ONLY F S RED VERTICAL MOUNT
0.000000
0.000000
0.082000
1.066000
4903 -9357
7
TRUEALERT 75CD SPEAKER VISIBLE 25V OVRMS RED
0.000000
0.000000
0.199000
1.393000
4904 -9332
8
TRUEALERT 75CD VISIBLE ONLY RED SYNC
0.000000
0.000000
0.199000
1.592000
ET70WP- 2475W -FR
1
WHEELOCK WALL MOUNT SPEAKER STROBE 75CD WP
0.000000
0.0110000
0.102000
0.102000
4905 -9938
19
ITRUEALERT SYNC CONTROL MODULE
0.000000
0.1100000
0.030000
0.570000
4906 -9101
10
ITRUE ALERT MULTIGANDELA STROBE, 75CD, WALL
0.000000
0.000000
0.186000
1.860000
4906 -9151
13
ITRUE AM MULTICANDEIA SPEAKER 75CD, WALL
0.000000
0.000000
0.186000
2.418000
0
Total Pariph Stby
0.052
Total Pedph Alarm
13.373
Total Standby Ampal 1.528 Total Alarm Amps 24.476
* Currant Draw Included With Device Addresses used (See additional current draws) Quantity Of Flock -up Amplifiers L:
1. 2 -wire detector alarm current is included in the alarm Current of the Initiating Device Circuit,
2. 50% of these devices in alarm, am used in the calculations below
Standby Alarm
Batted, Set 1 (Cabinet /(longer Current Current
Control Panel Power Master Power Supphy 0.868 1.773
Mapnet /IDNet Card Current Draw 2 0.540 0.580
Current Draw For 90 Watt Or 100 Watt Amplifiers 1 0.068 8.750
Current Draw For Dual 25 Watt Ampfirnrs 0 0.000 0.000
Power For External Peripheral Devices 0.05160 13.34900
1.528 < -- sub Totals - -> 24.452
Addt*W Current Draws
LUPNET /IDNet Device Addresses ordered / used 172 172.0 0.139 0.173
Spare addressable point capacity included for battery calc 20% 34 0.028 0.035
1.695 < - -Grand Totals - -> 24.660
Additional Battery Capacity Required 20% 0.339 4.932
Standby Time = 4 _ Hill; 8.135 Standby M
Alarm Turn = 15 Mills. 7.398 Alarm Ah
Battery Supplied 2081 -9296 50M 36.047 Total Ah
4100 -8201 Fire Alarm Control Panel - Node 4 - South Miami Hospital - 2nd Floor Main Tower PBX
SPEAKER CIRCUIT LOAD CALCULATION
MAXIMUM -3 dB DROP PER CIRCUIT
PHONE /SPEAKER CIRCUIT DESCRIPTION
PANEL
CIRCUIT
NUMBER
WIRE
GAUGE
(18, 16, 14
12 )
CIRCUTT
VOLTAGE
(25 OR
70 MW
APPLIANCES QUANTITIES TAP VALUES
4906 -9151 4903 -9150 4903 -9148 4903 -9149 ET7OWP- 2475W -FR 4903 -9357 2084 -9001
TAPPED AT TAPPED AT TAPPED AT TAPPED AT TAPPED AT TAPPED AT PHONE JIUIC
0.5 Watts 0.5 Wafts 0.5 Watts 0.5 Watts 1 Watts 0.5 Watts 0 Watt
TOTAL
CIRCUIT
LOAD
(WATTS)
ESTIMATED
CIRCUIT
LENGTH
ACTUAL
MIRE /LASS
dB
MAXIMUM
ALLOWABLE
CKT. LENGTH
TOTAL
CIRCUIT
RESISTANCE
OHMS
1st Floor Main Building Speakers
4. -21
18 awg
25 wire;
0
5
1
0
1
0
0
4.00 Watts
200 ft.
-0.14 dB
5,059 ft
2.6 Ohms
1st Floor Main Bum
4 -22
18 awg
25 wms
0
6
1
0
0
0
0
3.50 Watts
200 ft.
-0.12 d8
5,782 ft
2.6 Ohms
1st Floor Main Bun ers
4 -23
18 awg
25 vrms
0
4
2
0
0
0
0
3.00 Watts
200 ft
-0.11 dB
6,745 ft
2.6 Ohms
2M Floor Main Building Speakers
4 -24
16 owg
25 vrms
0
10
0
1
0
0
0
5.50 Watts
225 ft.
-0.22 dB
3 679 ft
2.9 Ohms
2nd Floor Wain Building
4:5g-25
16 awg
25 vrms
0
14
0
0
0
0
0
7.00 Watts
225 ft.
-0.28 dB
2,891 ft.
2.9 Ohms
2nd Floor Main Builds
4' -26
18 awg
25 vrms
0
1
0
0
0
0
0
0.50 Watts
250 ft.
-0.02 dB
40,471 ft
3.2 Ohms
3rd Floor Main Build keys
4 -27
18 awg
25 vrms
0
9
0
0
0
0
0
4.50 Watts
250 ft.
-0.20 dB
4,497 ft.
3.2 Ohms
3rd Floor Main Building Speakers
4 -28
18 Gag
25 vans
8
0
0
0
0
0
0
4.00 Watts
275 ft.
-0.19 dB
5 059 ft.
3.5 Ohms
Stairwell 16 Speaker Riser
4: 29
18 awg
25 vrms
0
3
0
0
0
0
0
1.50 Watts
275 tt.
-0.07 dB
13,490 ft.
3.5 Ohms
Stairwell f7 Speaker Tiler
4 -3D
18 owg
25 vrms
0
4
0
0
0
0
0
2.00 Watts
275 ft
-0.10 dB
10,118 ft.
3.5 Ohms
3rd Floc to East Tower Speakers
4 -31
18 owg
25 vrms
0
7
0
0
0
0
0
3.50 Watts
300 ft
-0.18 dB
5,782 IL
3.8 Ohms
1st Floor North Tower Speakers
4: -32
18 awg
25 vrms
2
0
0
0
0
2
0
2.00 Watts
0 ft
0.00 dB
10,118 ft.
0.0 Ohms
1st Floor Man Building Phones
4:9g-33
18 aw
N A vrms
0
0
0
0
0
0
4
0.00 Watts
300 ft.
0.00 dB
0 fL
3.8 Ohms
2nd Floor Man Building Phones
4: -34
18 aw
N A vans
0
0
0
0
0
0
5
0.00 Wafts
300 ft
0.00 dB
0 ft.
3.8 Ohms
3rd Floor Man Ekrld Phones
4 -35
18 awo
NIA wms
0
0
0
0
0
0
1
0.00 Watts
200 ft
0.00 dB
0 ft.
2.6 Ohms
let Floor Star 6 Phone
4 -36
18 awg
N A vrms
0
0
_ 0
0
0
0
0
0
0
1
1
0.00 Watts
0.00 Watts
200 ft
200 ft
O.00 dB
0.00 dB
0 ft.
0 fL
2.6 Ohms
2.6 Ohms
let Floor Stoir 7 Phone
4 -37
16 aw
N A vrms
0
0
0
2nd Floor Star 6 Phone
4. -36
18 aw
NIA vrms
0
0
0
0
0
0
1
0.00 Watts
200 ft
0.00 dB
0 ft
2.6 Ohms
2nd Floor Stair 7 Phan
4:&g-39
18 aw
N/A vrms
0
0
0
0
0
0
1
0.00 Watts
200 tL
0.00 dB
0 ft.
2.6 Ohms
3rd Floor Stair 6 Phone
4. -40
18 air
N/A vrms
0
0
0
0
0
0
1
0.00 Watts
225 R
0.00 dB
0 ft.
2.9 Ohms
3rd Floor Star 7 Phone
4 -41
18 awg
wms
0
0
0
0
0
0
1
0.00 Watts
250 ft.
0.00 dB
0 ft.
3.2 OMs
Spare Plane
4 -42
16 aw
N/A wms
0
0
0
0
0
0
0
0.00 Watts
0 f.
0.00 dB
0 f.
0.0 Ohms
Spm Phone
4 -43
16
N A vrms
0
0
- 0
0
0
0
0
0.00 Watts
0 ft.
0.00 dB
O f.
0.0 Ohms
Spam Phone
4 -44
1 16 aw
N/A vrms
0
0
0
1 0
1 0
1 0
1 0
0.00 Watts
0 ft
0.00 dB
1 0 ft.
0.0 Ohms
Summary Total Load Watt Max Load Watts Per Amp
10 63 4 1 1 1 1 1 2 1 16 41.00 100.00
Max Load alts Per Circuit
45.00
NOTE:
LUMP SUM METHOD WAS USED TO CALCULATE MAXIMUM ALLOWABLE CIRCUIT LENGTH. THIS METHOD ALLOWS FOR A SMALL
MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS
SHOWN ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH S GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
LENGTH, CONTACT YOU LOCAL SIMPLEX BRANCH
4009 Notification Appliance Extender Panel Battery Calculation - NAC #1
RMS
20.4
13 FLOOR STROBES
CKT 2
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
LENGTH
3 FLOOR STROBES
CKT 3
STROBE
Standby
Total
Alarm
Total
Module
Q1Y
Description
110CD
Current
Standby
Current
Alarm
Panel Equipment
0.1860
0.2520
AWG
OHM FT
FT
FT
1.9
4009 -9201
1
14009 IDNET NAC EXTENDER, 120 VAC
0.930
0.085000
0.085000
0.185000
0.185000
1 483
5
0
5
Total Panel Stby
0.085000
Total Panel Alarm
0.185000
Peripheral Devices
250
966
1
0
4
0
1 0.90
4906- 9101*75
10
TRUEMIRT MULTI - CANDELA STROBE RED, WALL 0 75 CANDELA
250
0.000000
0.000000
0.186000
1.860000
4906 - 9101 *110
0
TRUEALERT MULTI - CANDELA STROBE RED, WALL 0 110 CANDELA
12
0.000000
0.000000
0.252000
0.000000
4906 - 9151 *75
13
TRUEALERT MULTI - CANDELA SPEAKER STROBE RED, WALL 0 75 CANDELA
0.000000
0.000000
0.186000
2.418000
4906 -9151 *110
0
TRUEALERT MULTI - CANDELA SPEAKER STROBE RED, WALL Oi 110 CANDELA
0.000000
O.000OOO
0.252000
0.000000
m
J
Total Peri h Stby
0.000
Total Peri h Alarm
4.278
z
z w
Total Standby Amps
0.085
1 Total Alarm Ampsl
4.463
�
Standby
Alarm
z
Battery Calculations
Current
Current
u)iY
Control Panel Card Power
0.085
0.185
U
Q
z
O
Power For External Peripheral Devices
0.00000
4.27800
0.085
< -- Totals - ->
4.463
W
U
Additional Battery Capacity Required 20%
0.017
0.893
W
O
U
W
1
Standby Time = 4 Hrs
0.408
Standby Ah
z_
0
�_
in
Alarm Time = 15 Mins.
1.339
Alarm Ah
1.747
Total Ah
W
Q
4
�
Battery Required 2081 -9272 6.2
4.917
Ah
O
.-
\ \S=W\WW111A00- 200A9G M MM ►OMIX (AIM s11E)\SW 11101 ref( MIT-IRMUM WO 940420911 \sW HM p9( ANUMin INM 1�1011111w.nb.r 5. 2008 DATZ PLOSrJM: tbwwbw 6, 2005 DATZ sAVW. N".60 e, 2005
4009 Notification Appliance Extender Panel
NAC SCHEDULE / VOLTAGE DROP CALCULATION
17% MAXIMUM VOLTAGE DROP
CIRCUIT OUTPUT VOLTAGE (FOR CALCULATIONS) _
CIRCUIT I DESCRIPTION
cKT 11
RMS
20.4
13 FLOOR STROBES
CKT 2
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
LENGTH
3 FLOOR STROBES
CKT 3
STROBE
113
FLOOR STROBES
CKT#4
4906- 9101 *110
4906-9151 *75
13 FLOOR STROBES
METHOD USED TO CALCULATE VOLTAGE DROP:
[(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS / FT)]
Wire Resistance At
75 Degrees Celsius
Ohms / ft
10 GA = 0.001210
12 GA = 0.001930
14 GA = 0.003070
16 GA = 0.004890
18 GA = 0.007770
LAI
SCALE: NTS
Calculation - NAC #1 APPLIANCE / QUANTITIES / CURRENT DFM @ MAXIMUM
RMS
20.4
CIRCUIT
TYPE
WIRE
GAUGE
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
LENGTH
MAXIMUM
ALLOWABLE
CIRCUIT
LENGTH
STROBE
STROBE
SPKR STRB
SPKR STRB
4906- 9101 *75
4906- 9101 *110
4906-9151 *75
4906- 9151 *110
75CD
110CD
75CD
110CD
VOLTS
0.1860
0.2520
0.1860
0.2520
AWG
OHM FT
FT
FT
1.9
3.5
17.0%
16.9
0.930
V/0
1 12
0.00193
1 250
1 483
5
0
5
0
1.0
V 0
12
0.00193
250
966
1
0
4
0
1 0.90
V 0
12
0.00193
250
1,610
3
0
0
0
V 0
12
0.00193
250
966
1
0
4
0
CL
10 1 0 1 13 1 0
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE)
NOTE:
LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN
OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN
ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
LENGTH, CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE.
4.278
Total NAC Load:
VOLTAGE DROP TOTALS
TOTAL
CIRCUIT
LOAD
MAX
CIRCUIT
CAP.
AS DESIGNED
AT MAX ALLOW. CIRC. LENGTH
Total NAC Capacity:
TOTAL
CIRCUIT
RES.
ACTUAL
VOLTAGE
DROP
_
LAST
DEVICE
VOLT
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
LAST
DEVICE
VOLT
AMPS
AMPS
OHMS
VOLTS
%
VOLTS
OHMS
VOLTS
%
VOLTS
1.860
2.000
2.000
2.000
2.000
1.0
1.79
8.8%
18.6
1.9
3.5
17.0%
16.9
0.930
1.0
0.90
4.4%
19.5
3.7
3.5
17.0%
16.9
0.558
1.0
1 0.54
2.6%
19.9
6.2
1 3.5
17.0%
16.9
0,930
1.0
1 0.90
4.4%
19.5
3.7
1 3.5
17.0%
16.9
4.278
Total NAC Load:
4.28 A 53%
Largest Single Circuit Load:
1.86 A 93%
Lowest Voltage at any Device:
16.9 V 106%
Total NAC Capacity:
8 A
Single Circuit Capacity:
2.0 A
Minimum Device Voltage:
16 V
Note:
'Regulated 24 VDC' refers to the voltage range of 16 to 33 VDC
per UL standard 1971. This voltage is the absolute operating range.
Please note that 16VDC is the lowest operating voltage that is allowed
at the last appliance on the NAC under worst case conditions.
The maximum RMS current listed is the nameplate rating.
Strobe designs are constant wattage and the maximum RMS current
rating occurs at the lowest allowable operating voltage.
7 -- Z
a
.mss :.,P d ,.. ....,.... a..... .�..✓.0 ... a 6
m�
L. TRIANA &ASSOCIATES, INC.
CONS111t. .ENGINEERS
CERTIFIgAj,'f' 3t!A bRIZATiOf4' 26644
5151 S *1,' Oth
MIAMI FL 3316
LID
as
®sw
Ll 5 f R ®TR\ W4A, P. E.
Florida Registration No. PE65707
W
I-
CO
z
Q
5w
m u.
4
a- o
"2
�R
�®
WMM(D
ry M
O E in
U_
f- S
�Q�
p z
tn
2COM
C)
W a
CL
CL
z
w
W
m
J
J im
Ww
z
z w
®
Uj
0W
�
z
u)iY
°o Q
U
Q
z
O
z
O.
a ,
h-
W
U
z.
O
W
O
U
W
1
1
z_
0
�_
in
W
LLI
rn
W
Q
4
�
O
.-
O
z
}-i
F-4
�
U
W
r
" t
to
Q
W co
tL
=
tom. i
+s
S�
F-
C rn
O
z
63
�A
z
0
w
o
U
U
p�
W
w
U�
0
ow
dD
00
W4
D¢
a
_0
F-
5
z
z
00
U0
z
r-1
•+
w
z
J
a td
U
Z
z
O
0
►�i
U)
�i
:!9
0
(d r�
d0
�_
0
F.
m
-0
(1)
Z
0
o
w
L3
m0
z
z
o Q -'--1
0
Q
a�W t-m°
J
0QQ
Q.
3
DRAWN BY:
DATE:
RC
11-4 -08
DESIGNED BY:
DATE:
APPROVED BY:
DATE:
PROJECT NUMBER:
263 - 404043/940420911
SHEET TITLE/ PATH:
S MH\SMHHIGHRI SKANTEPARTUM\
SHEET NUMBER:
FA03
SIZE m (241n