09-725-0025. INSTALLATION SHALL COMPLY WITH NFPA 101, 2003, APPLICABLE CHAPTERS, 6, INSTALLATION SHALL COMPLY WITH NEC 2005, 7. CONDUIT, AS APPLICABLE SHALL BE 1/2 MINIMUM WITH A MAXIMUM FILL OF 40 %. COMPLY WITH NEC. 8, SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS, 9, ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE, 10, ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11, SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS, 12, CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' + /-- ON SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED. 13. SIGNALLING LINE CIRCUITS SHALL HAVE A MAXIMUM OF 250 POINTS PER CHANNEL, SEE I FLOOR PLANS FOR QUANTITIES & TYRES OF DEVICES. N YASCA ASSOCIATED 14. FIRE ALAR M PANEL >� ANY S O I TE ALARM TRANSPONDERS SHAL L BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER, 15, ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER NFPA 72, 16. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17, THE DESIGN INSTALLATION COMPLIES WITH F.R.C. 11- 4,28.3 SCOPE UF , I 1 1. RELOCATE 1 GULL STATION AND 1 PHONE JACK ON THE SECOND FLOOR IN THE PBX AREA. 2, THIS SYSTEM SHALL BE A EXISTING REMOTE STATION SIGNALING SYSTEM. i D Aron Plpr mom 3• b► (792 mm) diem (or smaller) Cass •r ductile Iran pipe. C. Conduit- Nom 6 In. (152 mm) dram (or smaller) rigid start conduit. SYMBOL LEGEND .... •.. . • ••i•• ... EXISTING FRCP FJ 2084 -9001 EXISTING FIREMAN'S PHONE JACK Q 4099 -9001 EXISTING PULL STATION 4-1/2(114) 1/2 -6 (13 -152) Packing material t• be recessed from t surface of floor •r from bath th surfaces of wall n! • as required to accommodate the required thickness of caulk fill material (Item 4). with cement coated nails s specified h v W I r ` i a in the Individual Wall o part�t on Design. When steel channel stud ! framing Is . 4-1/2(114) 4. FKt Vold •r m - Cavity Matt as Caulk q Se1�aud to fill the annular In space flush with tap surface of floor. n wall assemblies, required caulk thickness t• be Installed symmetrically on employed, gypsum wallboard attached to studs with Type S self - drilling, self - tapping w bugle -head steel screws as specified In the Individual Wail or partition Design. . 13 ifJ �j f a � 2� \V/ � L ..e.r i I The hourly F Rating of the flrestop system Is equal to the hourly fire rating of the wall M Ir M' -D,,R assembly In Which it Is Installed. f � r�T ! :1 -1�. Y r 7�^ r 1 (25) applied at 4q surface of flrrr and at bath surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown In the itt 0 ;;i +LA.�i1 �V NOT following table, 2. Cables - Individual cable or max 1 In. dlam cable bundle Installed in through opening with an FipE al�la ?)r' iDf1.�- y �, : 'i 'AIN E,XT:� 1/2 -12 (13 -305) 3-1/4(83) or _T 1. FIR. E ALARM SYSTEM SHALL BE POWER LIMITED. • 2 (51) • • • • t, • • 1 -3 /i (35) 2, WIRING SHALL BE #12 THHN, #14 THHN OR 18/2 TWISTED SHIELDED PAIR FPL TYPE CABLE, •Y` ••` •�• `a` ••• i•• ' 3. INSTALLATION SHALL COMPLY WITH NFPA 1, 2003, APPLICABLE CHAPTERS, � U� �u p Z 4 INSTALLATI ❑N SHALL COMPLY WITH NFPA 72 2002 APPLICABLE CHAPTERS L ova O W a .i 5. INSTALLATION SHALL COMPLY WITH NFPA 101, 2003, APPLICABLE CHAPTERS, 6, INSTALLATION SHALL COMPLY WITH NEC 2005, 7. CONDUIT, AS APPLICABLE SHALL BE 1/2 MINIMUM WITH A MAXIMUM FILL OF 40 %. COMPLY WITH NEC. 8, SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS, 9, ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE, 10, ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11, SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS, 12, CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' + /-- ON SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED. 13. SIGNALLING LINE CIRCUITS SHALL HAVE A MAXIMUM OF 250 POINTS PER CHANNEL, SEE I FLOOR PLANS FOR QUANTITIES & TYRES OF DEVICES. N YASCA ASSOCIATED 14. FIRE ALAR M PANEL >� ANY S O I TE ALARM TRANSPONDERS SHAL L BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER, 15, ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER NFPA 72, 16. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17, THE DESIGN INSTALLATION COMPLIES WITH F.R.C. 11- 4,28.3 SCOPE UF , I 1 1. RELOCATE 1 GULL STATION AND 1 PHONE JACK ON THE SECOND FLOOR IN THE PBX AREA. 2, THIS SYSTEM SHALL BE A EXISTING REMOTE STATION SIGNALING SYSTEM. i V%AI V R: ALL AUDIOVISUAL APPLIANCES, SPEAKERS AND STROBES WITHIN THE FLOOR WHERE THE ALARM INITIATED SHALL BE ACTIVATED. IN ADDITION, ALL AUDIOVISUAL APPLIANCES, SPEAKERS AND STROBES LOCATED ON THE FLOOR IMMEDIATELY ABOVE AND ON THE FLOOR IMMEDIATELY BELOW, SHALL ALSO BE ACTIVATED. ALL STROBES ACTIVATED UPON ALARM, WITHIN EACH SMOKE COMPARTMENT, SHALL BE SYNCHRONIZED. ALL MAGNETIC DOOR HOLDERS ASSOCIATED WITH THE DOORS LEADING INTO AND OUT OF THE SMOKE COMPARTMENT IN ALARM SHALL BE ACTIVATED TO f RELEASE DOORS TO ISOLATE THE SMOKE COMPARTMENT WHERE THE ALARM INITIATED FROM. ALL AIR HANDLING UNITS AND FANS SERVING THE SMOKE COMPARTMENT, FROM WHICH THE ALARM ORIGINATED FROM, SHALL BE SHUT DOWN. I ALL SMOKE DAMPERS ASSOCIATED WITH THE AIR CONDITIONING DUCTS PENETRATING THE RATED PARTITIONS ASSOCIATED WITH THE SMOKE COMPARTMENT WHERE THE ALARM IS ORIGINATED FROM, SHALL BE CLOSED. System No.W -L -3001 *SSIfij . SSIF September 07, 2004 UPON ACTIVATI ❑N OF THE ELEVATOR LOBBY SMOKE DETECTORS (WITH THE EXCEPTI ❑N G�' fid System No, C -AJ -1044 Formed System No. 149 OF THE ELEVATOR LOBBY DETECTOR AT THE PRIMARY LEVEL OF EGRESS), June 15, 2005 (Formerly y ) THE FOLLOWING SHALL OCCUR IN ADDITION TO ABOVEI F Ratings - 1 and 2 Hr (See Item 1) F Ratings 2 3 and 4 Hr See Items 2 A and 4 9 I ) 1, ELEVATORS SHALL RECALL T❑ THE PRIMARY LEVEL OF EGRESS, US T Patin - 0 Hr U` U T Ratings 3/4, 1, 1-1/2 and 2 Hr (See Item 2) Rating 2. WARNING SIGN SHALL ILLUMINATE, L Rating At Ambient - 2 CFM /sq 1t L Rating At Ambient - 15 CFM /sq ft (See Item 3) FILL VOID OR CAVITY MATERIALS L Rating At 400 F - less than 1 CFM /s ft FILL VOID OR CAVITY MATERIALS L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) UPON ACTIVATION ❑F THE ELEVATOR LOBBY SMOKE DETECTOR AT THE PRIMARY LEVEL CLASSIFIED BY UNDERWRITERS q OF EGRESS, THE FOLLOWING SHALL OCCUR, IN ADDITION TO AB❑VEI LABORATORIES, INC4 FOR USE IN W Rating - Class I (See Item 4) CLASSIFIED By UNDERWRITERS LABORATORIES, INC,(& FOR USE IN 1. ELEVATORS SHALL RECALL TO THE ALTERNATE LEVEL OF EGRESS, THROUGH- PENETRATION THROUGH- PENETRATION 2. WARNING SIGN SHALL ILLUMINATE, FIRESTOP SYSTEMS (XHEZ). q FIRESTOP SYSTEMS (XHEZ). 1 SEE CURRENT UL FIRE 4 SEE CURRENT UL FIRE UPON ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR, THE FOLLOWING RESISTANCE DIRECTORY A RESISTANCE DIRECTORY SHALL OCCUR, IN ADDITION TO ABOVE, 501-6, 9OG9 q 501-6, 9DC 1, ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL. OF EGRESS, 2, WARNING SIGN SHALL BLINK, A 1 �, .. UPON ACTIVATION OF THE ELEVATOR TOP OF SHAFT SMOKE DETECTOR, THE FOLLOWING SHALL OCCURI 1, ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS, w 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF A TAMPER SWITCH, THE FOLLOWING SHALL OCCUR. k ; 1, A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR, 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT, r `� i 2 3 , ~oaf• �• y.K . r y UPON ACTIVATI ❑N OF A DUCT SMOKE DETECTOR, THE FOLL ❑WING SHALL OCCUR. A 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. r 3. THE AIR HANDLER UNIT ASSOCIATED WITH THAT DUCT DETECTOR SHALL SHUT DOWN. SECTION A -A UPON ACTIVATION OF A ELEVATOR HEAT DETECTOR LOCATED IN THE SHAFT OR MACHINE ROOM THE FOLLOWING SHALL OCCUR. L Floor or Walt Assembly ht rr, normal weight (109 -154 pcf or 1600 -2400 k9/m3) concrete. Except as note In in tale under Item 4, min thickness of s•lkl concrete floor •r 1 wall assembly Is 4 -1/2 h (114 mm). Floor may also be constructed of any min 6 In. (152 mm) 1 1, A SUPERVISORY SIGNAL. SMALL BE SE NT TO THE FRCP >IR REMOTE ANNUNCIATOR, _ thick UL Class! l Classified hallow core precast Concrete UnlidMen floor Is constructed of hollow 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT, core precast concrete units, packing materll (Item 3) and caulk fill material (Item 4) to be 3. THE SIGNAL WILL BE SENT TO THE SHUNT SWITCH FOR POWER SHUTDOWN. Installed symmetrically on Moth sides of floor, flush with floor surface. Wall assembly may else be constructed of any UL Classified Concrete ilacksMax dam of opening is In solid lightweight or normal weight concrete. Floor Is 32 In. (913 mm). Max dlam of opening In floor A constructed of hollow -core precast concrete units Is 7 h (178 mm). {-� See Concrete ilecklCAZT) and precast Concrete Urmm categories In the Fire Resistance 111 111 Directory for names of manufacturers. IA, Steel Sleevdaptlrnal, not shown) - Max 15 hl. (391 mm) ID (•r smatter) Schedule 10 (or SECTION A —A heavier) stoat strove cast or grouted Into floor or wall assembly. Sleeve may extend a Max of 2 In. (51 mm) above ter of floor or beyond either surface of watt. Max Kin. (406 mm) ID (or smaller) min 0.029 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or outed Into floor wait •r a l assembl .Sleeve may t tp'• Y Y ex end a max of 1/2 In. (13 mm) beyond eltlxrr surface of floor or wall 2. Through PenetranisOne metallic pipe, conduit or tubing o be Installed either c•ncrntrlcall - , 9 y 1. Wall Assembly The 1 or 2 hr fire-rated gypsum wallboard /stl d wall assembly shag be constructed or eccentrically within the firest•p system. Max anrader space between pipe, conduit or of the materials and In the manner described In the Individual U300 or U400 Series Wall or partition tubing and edge of through opening or sleeve Is dependent an the parameters shown In Item 4. Min annular space between pipe or conduit and edge of through opening Is 9 bu (4 MM) Designs In the UL Fire Resistance Directory and shall Include the following construction features: (point contact). Plot conduit or tubing to be Y supported rted •n both sides • f floor or • all I dk l assembly. The following types and sizes of neta�l PI P es , conduits or -tubing used . A. studs _ Wall framing may consist of either wood studs or steel channel studs. Wood studs to A Steel pipe Non 31 In. (762 mm) dam ter smaller) Schedule 10 (or heavier) steel PIP e. consist of nom 2 by 4 In. lumber spaced 16 In. OC with nom 2 by 4 In. lumber end plates and cross D Aron Plpr mom 3• b► (792 mm) diem (or smaller) Cass •r ductile Iran pipe. C. Conduit- Nom 6 In. (152 mm) dram (or smaller) rigid start conduit. SYMBOL LEGEND SYMBOL SIMPLEX MODEL #k DESCRIPTI ❑N ODE 4100 -8201 EXISTING FRCP FJ 2084 -9001 EXISTING FIREMAN'S PHONE JACK Q 4099 -9001 EXISTING PULL STATION V%AI V R: ALL AUDIOVISUAL APPLIANCES, SPEAKERS AND STROBES WITHIN THE FLOOR WHERE THE ALARM INITIATED SHALL BE ACTIVATED. IN ADDITION, ALL AUDIOVISUAL APPLIANCES, SPEAKERS AND STROBES LOCATED ON THE FLOOR IMMEDIATELY ABOVE AND ON THE FLOOR IMMEDIATELY BELOW, SHALL ALSO BE ACTIVATED. ALL STROBES ACTIVATED UPON ALARM, WITHIN EACH SMOKE COMPARTMENT, SHALL BE SYNCHRONIZED. ALL MAGNETIC DOOR HOLDERS ASSOCIATED WITH THE DOORS LEADING INTO AND OUT OF THE SMOKE COMPARTMENT IN ALARM SHALL BE ACTIVATED TO f RELEASE DOORS TO ISOLATE THE SMOKE COMPARTMENT WHERE THE ALARM INITIATED FROM. ALL AIR HANDLING UNITS AND FANS SERVING THE SMOKE COMPARTMENT, FROM WHICH THE ALARM ORIGINATED FROM, SHALL BE SHUT DOWN. I ALL SMOKE DAMPERS ASSOCIATED WITH THE AIR CONDITIONING DUCTS PENETRATING THE RATED PARTITIONS ASSOCIATED WITH THE SMOKE COMPARTMENT WHERE THE ALARM IS ORIGINATED FROM, SHALL BE CLOSED. System No.W -L -3001 *SSIfij . SSIF September 07, 2004 UPON ACTIVATI ❑N OF THE ELEVATOR LOBBY SMOKE DETECTORS (WITH THE EXCEPTI ❑N G�' fid System No, C -AJ -1044 Formed System No. 149 OF THE ELEVATOR LOBBY DETECTOR AT THE PRIMARY LEVEL OF EGRESS), June 15, 2005 (Formerly y ) THE FOLLOWING SHALL OCCUR IN ADDITION TO ABOVEI F Ratings - 1 and 2 Hr (See Item 1) F Ratings 2 3 and 4 Hr See Items 2 A and 4 9 I ) 1, ELEVATORS SHALL RECALL T❑ THE PRIMARY LEVEL OF EGRESS, US T Patin - 0 Hr U` U T Ratings 3/4, 1, 1-1/2 and 2 Hr (See Item 2) Rating 2. WARNING SIGN SHALL ILLUMINATE, L Rating At Ambient - 2 CFM /sq 1t L Rating At Ambient - 15 CFM /sq ft (See Item 3) FILL VOID OR CAVITY MATERIALS L Rating At 400 F - less than 1 CFM /s ft FILL VOID OR CAVITY MATERIALS L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) UPON ACTIVATION ❑F THE ELEVATOR LOBBY SMOKE DETECTOR AT THE PRIMARY LEVEL CLASSIFIED BY UNDERWRITERS q OF EGRESS, THE FOLLOWING SHALL OCCUR, IN ADDITION TO AB❑VEI LABORATORIES, INC4 FOR USE IN W Rating - Class I (See Item 4) CLASSIFIED By UNDERWRITERS LABORATORIES, INC,(& FOR USE IN 1. ELEVATORS SHALL RECALL TO THE ALTERNATE LEVEL OF EGRESS, THROUGH- PENETRATION THROUGH- PENETRATION 2. WARNING SIGN SHALL ILLUMINATE, FIRESTOP SYSTEMS (XHEZ). q FIRESTOP SYSTEMS (XHEZ). 1 SEE CURRENT UL FIRE 4 SEE CURRENT UL FIRE UPON ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR, THE FOLLOWING RESISTANCE DIRECTORY A RESISTANCE DIRECTORY SHALL OCCUR, IN ADDITION TO ABOVE, 501-6, 9OG9 q 501-6, 9DC 1, ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL. OF EGRESS, 2, WARNING SIGN SHALL BLINK, A 1 �, .. UPON ACTIVATION OF THE ELEVATOR TOP OF SHAFT SMOKE DETECTOR, THE FOLLOWING SHALL OCCURI 1, ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS, w 2. WARNING SIGN SHALL BLINK. UPON ACTIVATION OF A TAMPER SWITCH, THE FOLLOWING SHALL OCCUR. k ; 1, A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR, 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT, r `� i 2 3 , ~oaf• �• y.K . r y UPON ACTIVATI ❑N OF A DUCT SMOKE DETECTOR, THE FOLL ❑WING SHALL OCCUR. A 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT. r 3. THE AIR HANDLER UNIT ASSOCIATED WITH THAT DUCT DETECTOR SHALL SHUT DOWN. SECTION A -A UPON ACTIVATION OF A ELEVATOR HEAT DETECTOR LOCATED IN THE SHAFT OR MACHINE ROOM THE FOLLOWING SHALL OCCUR. L Floor or Walt Assembly ht rr, normal weight (109 -154 pcf or 1600 -2400 k9/m3) concrete. Except as note In in tale under Item 4, min thickness of s•lkl concrete floor •r 1 wall assembly Is 4 -1/2 h (114 mm). Floor may also be constructed of any min 6 In. (152 mm) 1 1, A SUPERVISORY SIGNAL. SMALL BE SE NT TO THE FRCP >IR REMOTE ANNUNCIATOR, _ thick UL Class! l Classified hallow core precast Concrete UnlidMen floor Is constructed of hollow 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS REMOTE STATION VIA DACT, core precast concrete units, packing materll (Item 3) and caulk fill material (Item 4) to be 3. THE SIGNAL WILL BE SENT TO THE SHUNT SWITCH FOR POWER SHUTDOWN. Installed symmetrically on Moth sides of floor, flush with floor surface. Wall assembly may else be constructed of any UL Classified Concrete ilacksMax dam of opening is In solid lightweight or normal weight concrete. Floor Is 32 In. (913 mm). Max dlam of opening In floor A constructed of hollow -core precast concrete units Is 7 h (178 mm). {-� See Concrete ilecklCAZT) and precast Concrete Urmm categories In the Fire Resistance 111 111 Directory for names of manufacturers. IA, Steel Sleevdaptlrnal, not shown) - Max 15 hl. (391 mm) ID (•r smatter) Schedule 10 (or SECTION A —A heavier) stoat strove cast or grouted Into floor or wall assembly. Sleeve may extend a Max of 2 In. (51 mm) above ter of floor or beyond either surface of watt. Max Kin. (406 mm) ID (or smaller) min 0.029 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or outed Into floor wait •r a l assembl .Sleeve may t tp'• Y Y ex end a max of 1/2 In. (13 mm) beyond eltlxrr surface of floor or wall 2. Through PenetranisOne metallic pipe, conduit or tubing o be Installed either c•ncrntrlcall - , 9 y 1. Wall Assembly The 1 or 2 hr fire-rated gypsum wallboard /stl d wall assembly shag be constructed or eccentrically within the firest•p system. Max anrader space between pipe, conduit or of the materials and In the manner described In the Individual U300 or U400 Series Wall or partition tubing and edge of through opening or sleeve Is dependent an the parameters shown In Item 4. Min annular space between pipe or conduit and edge of through opening Is 9 bu (4 MM) Designs In the UL Fire Resistance Directory and shall Include the following construction features: (point contact). Plot conduit or tubing to be Y supported rted •n both sides • f floor or • all I dk l assembly. The following types and sizes of neta�l PI P es , conduits or -tubing used . A. studs _ Wall framing may consist of either wood studs or steel channel studs. Wood studs to A Steel pipe Non 31 In. (762 mm) dam ter smaller) Schedule 10 (or heavier) steel PIP e. consist of nom 2 by 4 In. lumber spaced 16 In. OC with nom 2 by 4 In. lumber end plates and cross Min Floor or Wall Thkns In. (mm) D Aron Plpr mom 3• b► (792 mm) diem (or smaller) Cass •r ductile Iran pipe. C. Conduit- Nom 6 In. (152 mm) dram (or smaller) rigid start conduit. - braces. Steel studs t• be min 3 5/i In. wide by 1 -3 /8 in. deep channels spaced max 24 In OC. S. Gypsum Board* - Nom 1/2 or 5/9 in, thick, 4 ft wide with square or tapered edges. The gypsum Min Caulk rhkns In. (mm F Rating Hr D. Crndult - Nom 4 In. (102 mm) dlam (or smaller) sleet electrical Metallic tubing, - E. Capper- Tubing Nom 6 k% (152 mm) dam (•r smaller) Type L (•r heavier) copper tuba wallboard type, thickness, number of layers and sheet orientation shall be as specified In the Individual FIRE ALkRM SYSTEM fO BE y F. Copper pipe- Non 6 In. (152 mm) dam (•r smaller) Regular (•r heavier) copper pipe. Wall or partition Design. Dlam of circular through opening to be 3/8 in. to 5/8 In. larger than outside diam of cable or cable bundle. WSTAU ED IN ACCORDAI ICE WITH 3-1/4(93) 3. packing Materlalr Polyethylene backer rod or nom 1 In. (25 mm) thickness of tlghtty- packed mineral wool Matt or lass fiber Insulation firmly eked Into • n as a permanent • Y M opening p ont forts. . _ C. Fasteners When wood stud framing is employed gypsum wallboard layers attached to studs NFPA 72, 70,1Q1 4-1/2(114) 1/2 -6 (13 -152) Packing material t• be recessed from t surface of floor •r from bath th surfaces of wall n! • as required to accommodate the required thickness of caulk fill material (Item 4). with cement coated nails s specified h v W I r ` i a in the Individual Wall o part�t on Design. When steel channel stud ! framing Is 4-1/2(114) 4. FKt Vold •r m - Cavity Matt as Caulk q Se1�aud to fill the annular In space flush with tap surface of floor. n wall assemblies, required caulk thickness t• be Installed symmetrically on employed, gypsum wallboard attached to studs with Type S self - drilling, self - tapping w bugle -head steel screws as specified In the Individual Wail or partition Design. . 13 ifJ �j f a � 2� \V/ � L �..... .,.r..r...`.,w cr;.. ;y L BOF NORD 3 both sides of wall, flush with Malt surface. At pint contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 In. (6 mm) dkm bead of caulk shall bei�rCiiil�iTY"iE� The hourly F Rating of the flrestop system Is equal to the hourly fire rating of the wall M Ir M' -D,,R assembly In Which it Is Installed. f � r�T ! :1 -1�. Y r 7�^ r 1 (25) applied at 4q surface of flrrr and at bath surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown In the Tti.(.�I)u.PCRII #IT Ei! ,- .....r. ;;i +LA.�i1 �V 2 (51) following table, 2. Cables - Individual cable or max 1 In. dlam cable bundle Installed in through opening with an FipE al�la ?)r' iDf1.�- y �, : 'i 'AIN E,XT:� 1/2 -12 (13 -305) 3-1/4(83) annular space of min 0 in. (point contact) to max 3/4 in. Cable to be rigidly supported on both sides of _T 4 -1/2 (114) 22 -30 (558 -762) wall assembly. The following types and sizes of cables may be used: 2 (51) 3 5 -1/2 (140) 1 A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC insulation _ 1 and jacket materials. When max 25 pair telephone cable Is used,© 1 -3 /i (35) Min Floor or Wall Thkns In. (mm) N•m Pipe Tube or Conduit Dlam In. (mm ) Max Annular Space In. (mm) Min Caulk rhkns In. (mm F Rating Hr 2-1/2(64) 1/2 -12 (13 -305) 1 -3/9 (35) 1/2 (13) 2 2-1/2(64) 1/2 -12 (13 -305) 3-1/4(93) 1 (25) 2 4-1/2(114) 1/2 -6 (13 -152) 1-3/2(35) 1/4 (6) (a) 2 4-1/2(114) 1/2 -12 (13 -365) 1-1/4(32) 1/2(13) 3 4-1/2(114) 1/2 -20 (13 -506) 2 (51) 1 (25) 3 4 -1/2 (114) 1/2 -26 (13 -yes) 2 (51) 1 (25) 3 4 -1/2 (114) 1/2 -12 (13 -305) 3-1/4(83) 1 (25) 3 4 -1/2 (114) 22 -30 (558 -762) 2 (51) 2 (51) 3 5 -1/2 (140) 1 1/2 -6 (13 -152) 1 -3 /i (35) 1 (25)(b) 4 T Rating Is 2 hr.Whan 50 to 150 pair telephone cable Is used in 1 hr fire rated wall, T Rating Is 3/4 hr.When 50 to 150 palr telephone cable Is used in 2 hr fire rated wall, T Cr) 0% -�' (i ii" N"W �J Rating is 1 hr. �k,�ll B. Max No. 10 AWG multiple copper conductor Type NM ( "Romex" ) nonmetallic sheathed cable with PVC insulation and jacket materials. When Type NM cable Is used, max T Rating is 1 -1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside dlam of 5/8 In, When Tibor optic cable Is used, max T Rating Is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross - linked polyethylene (XLPE) Insulation and XLPE or PVC jacket materials. When multi conductor power /control cable is used, max T Rating Is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl chloride Insulation and jacket materials. I (a)MIn 2 In. (51 non) thickness •f mineral wool Batt Insulation required In annular space. 3. F1111/eld or Cavity Materials* -Caul Sealant or Putty - Caulk or u fill material Installed to (b)Min 1 In. (25 nn) thickness •f mineral wool butt Insulation required N annular space r ty k, ttY putty on both sides of floor or watt assembly, Min 1 In. (25 mm) thickness of caulk to be Installed completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min flush with each surface of floor or wait assembly. 1/4 In. dram bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the 3M COMPANY - CP 25Wg+ caulk or rB -•3000 WT sealant. (Note, W Rating applies only when wall. Fi-3oo0 WT sealant Is used.) 3M COMPANY - MP+ St i x putty, CP 25WB caulk, F - 3000 WT sealant or Cable wrap putty r)earIng the UL Classification Marking * NOTE (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. *Bearing the UL Classification Mark i i NOTES I I I I \ \SGMI..AMI1 \DPAF MIG \N- 2003 \1 - UOM MIAMI HOSPITAL (MASM SRE) \SMH Pg)( KNOVATION REM')- 9451711002 \SMN rPm. mE7.7ltt'Amw. FIW,211&n lQm2.DWG DATR TUMM: July 21, 2000 DATR RAM: July 21. 20" I_ W W 5 z `. uJ MI li WNO Z p t0 U cq In CV m 40 �. L M iu c� � „J b. -V L0 y �tL M CUR � U� �u p Z L ova O W a .i a (n v Z= w J JZ (� In W z Zw O �w C CL Z O Z O L ~ o! � z U W a Z 0 aW rn c a Ci Z i i l�-1 w U It 5 a t < z W W 1C 1l. Y w w x E LL 04 O_ Z NN a t C7 ti � W l:i M J `n z (L O Z �r V Z ` O U ~ O U W 0! V � C WW Z U H � Z OW W C a F- L 7 t L Z) t C{ W U p m� W f1, z 0 J 1.4 0 Z (7 k L J E­1 Z O � oU I--I a w Z C) Z W O W �O Z S Q I-� U)i a a a 0 C� 2 W Z Z J O WIL d 00 W O a zw ��Do Z >o Z` O cy) it IL O �a DRAWN BY: DATE: KW 7/21/09 DESIGNED BY: DATE: KW 7/21/09 APPROVED BY: DATE: PROJECT NUMBER: 945178002 SHEET NUMBER: NOTES VIE: