09-720-011UNISTRUT ACROSS TFE
TOP OF THE EQUIPMENT
AT EACH END.
22.5° MIN.—
WASHER 1-1/2 O.D X IOG
5/8' EYE BOLT
DOUBLE CABLE CLAMPS
TYR AT ALL POINTS
5/16 ' 6X7 GALV. WIRE
ROPE GUY
5/8 EYE BOLT. IF FASTENED
TO STEEL TO BE DONE SAME
AS TOP EYE BOLT. IF
INSERTED IN CONC. USE
'RED HEAD' R -58 SELF
DRILLING CONC. ANCHOR E
EYE BOLT W/ 1 -1/2" MIN.
THREAD DEPTH.
EQUIPMENT HURRICANE ANCHORING DETAIL
N.T.S.
NOTE:
I: EACH OF 4 CORNERS OF ROOF MTD. EQUIP TO BE GUYED IN THIS FASION. ALL
HARDWARE TO BE GALV. OR CADMIUM PLATED FORGET STEEL ASTM-A-325
2- INSTALLATION MUST MEET MINIMUM OF 150 MPH WIND LOANDNNG, MINIMUM REQUIREMENTS
ARE I -EREBY II�ICATED, HOWEVER BASED ON ACTL�2AL EQUIPMENT INSTALLED EPA
(EFFECTIVE PROJECTED AREA) ADDITIONAL SECURING SHALL BE PROVIDE
4
'NUTS
PAD
CONDENSING UNIT MOUNTING DETAIL MITSUBISHI
N.T.S.
NOTE:
I. INSTALLATION MUST MEET MINIMUM OF 150 MPH WIND LOADING, MINIMUM REQUIREMENTS
ARE HEREBY INDICATED, HOWEVER BASED ON ACTURAL EQUIPMENT INSTALLED
EPA ( EFFECTIVE PROJECTED AREA) ADDITIONAL SECURING SHALL BE PROVIDED.
2. CORROSION PROTECTION. BUILDINGS LOCATED WITHIN 3,000 FT. OF THE OCEAN
SHOULD USE NON- FERROUS METAL, STAINLESS STEEL OR STEEL WITH MINIMUM
G -90 HOT -DIP GALVANIZED COATING FOR EQUIPMENT STANDS AND ANCHORS AND
STAINLESS STEEL SCREWS.
3. MECHANICAL SYSTEMS SHALL BE EITFER PLACED ABOVE THE BASE FLOOD ELEVATION
OR PROTECTED SO AS TO PREVENT WATER FROM ENTERING OR ACCUMULATING
WITHIN THE EQUIPMENT, APPLIANCES, DUCTS OR PLENUM SPACE DURING FLOODS UP TO
THE BASE FLOOD ELEVATION.
4. SEAL ENTRANCE OF REFRIGERANT LIDS INTO PVC PIPE W /IMPERMEABLE,
RESILIENT MATERIAL (SEE DETAIL).
5. AN ANCHOR BOLT W/ MINIMUM 500 LBS PULL OUT RESISTANCE SHALL SECURE
THE AC CONDENSER UNITFROM WITHIN THE UNIT THROUGH THE CONC. SLAB ON
WHICH THE UNIT RESTS.(ANTI- TI-EFT BOLT). (MDC CH 8-C SEC. 8G-5)
SURFACE t
CHANNEL L
THROUGH 1
OF THE CH
W
UNISTRUT CHANNEL
ON EACH FLOOR.
16 GA. SHEET METAL
SADDLE FOR INSULATED
PIPES 1/4' THICK
NEOPRENE SLEEVE FOR
UNINSULATED PIPES.
REFRIGERANT PIPE RISER SUPPORT DETAIL
N.T.S.
METAL PIPE
OR CONDUIT
I, 2, 3, OR 4 HOUR FIRE
RATED CONCRETE FLOOR SLAB.
.7•5: 9 �
USE 3M CP -25 WB W SELF - LEVELING CAULK
ON HORIZONTAL SURFACES WHEN FILLING
GAPS FROM ABOVE THE PENETRATION.
USE 3M CP -25 WB W NO SAG CAULK
ON VERTICAL SURFACES AND ON HORIZONTAL
SURFACES WHEN FILLING GAPS FROM BELOW.
DAMPING
MATERIAL
INSULATION (IF REQUIRED
BY SPECIFICATION
1, 2, 3, OR 4 HOUR RATED
CONCRETE BLOCK WALL
FOR SOLID CONCRETE WALL
(SEE NOTE 1)
INSULATION (IF REQUIRED
BY SPECIFICATION
FILL GAP COMPLETELY AROUND
PIPE WITH 3M CP -25 WB W CAULK
(SEE NOTES 3-5)
DAMPING MATERIAL (FIBERGLASS
INSULATION, BACKER ROD OR MINERAL
WOOL) ENOUGH TO SUPPORT WEIGHT OF
3M CP -25 WB W CAULK.
SECTION VIEW (SLAB)
NOTES:
PIPE 1. FOR SOLID CONCRETE WALLS. CENTER 3M CP -25 WB ( *) CAULK
OR CONDUIT WITHIN WALL WITH DAMPING MATERIAL ON ONE SIDE.
2. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
PER ASTM E -814 (UL -1479) FIRE TEST AND UL
CLASSIFICATION FIRE STOP SYSTEM CAJ -1175.
3. WET INSTALLED DEPTH OF 3M CP -25 WB ( *) CAULKS DEPENDS ON
3M CP -25 WB W N/S CAULK TYPE AND SIZE OF PIPE: AND DESIRED RATING.
BOTH SIDES OF WALL WET DEPTH PIPE SIZE FIRE RATING
(SEE NOTE)
1/2" 03MM) MAX. e (203MM) 1 -2 HRS.
I' (25MM) MAX. e (203MM) 3 -4 HRS.
4. UP TO 40% SHRINKAGE OF 3M CP -25 WB ( *) CAULK
IS ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION.
SECTION VIEW (WALL) 5. MAXIMUM ANNULAR SPACE TO BE FILLED IS 13/8" (35MM).
UL APPROVED PIPING SAFING ASSEMBLIES EQUAL
TO UL SYSTEM uCAJ-1175 FOR INSULATED PIPE AND
SYSTEM uWJ-1009 FOR NON INSULATED PIPE
PIPE PENETRATION FIRESTOP DETAIL
N.T.S.
( *) (OR APPROVED EQUIVALENT)
U.L. SYSTEM NO. WL1092
STEEL PIPE THROUGH I -HR. OR 2 -HR. GYPSUM WALL ASSEMBLY
F RATING = I -HR. OR 2 -H2.
T RATING = 0 -HR.
FRONT VIEW SECTION A -A
A'=i ! -
A _j
I. GYPSUM WALL ASSEMBLY (I -HR. OR 2 -HR. FIRE- RATING)(2 -HR. SHOWN).
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING:
A. MAXIMUM 6" DIAMETER STEEL PIPE.
B. MAXIMUM 4" DIAMETER STEEL CONDUIT.
C. MAXIMUM 4' DIAMETER EMT.
3. MAXIMUM 10' DIAMETER STEEL SLEEVE (MINIMUM 28 GAGE SI -;EET METAL OR NO. 8
STEEL WIRE MESH).
4. MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED (SEE NOTE NO. 2 BELOW).
5. MIN. 1 -114' DEPTH HILTI FS -ONE HIGH PERFORMANCE INTUMESCENT FIRESTOP SEALANT.
NOTES: I. MAXIMUM DIAMETER OF OPENING . 10'.
2. THICKNESS OF MINERAL WOOL TO BE ONE OF THE FOLLOWING:
A. MINIMUM 1 -1/4" THICKNESS FOR A 1 -1-12. FIRE -RATED SYSTEM.
B. MINIMUM 2 -1/2' THICKNESS FOR A 2 -HR. FIRE -RATED SYSTEM.
3. ANNULAR SPACE = MINIMUM I% MAXIMUM 2 -3/8 ".
SEE HILTI F12ESTOP INSTALLATION MANUAL FOR ADDITIONAL INSTRUCTIONS
HILTI, INC. TULSA, OK 1- 800-879 -8000
-PRO,,,, No.-18002.5 EB0000924
LOUIS LAGUIRRE & ASSOCIATES P.A.
a" C.OkSJLTING ENGINEERS
950 SOUTH - DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FA-k- - - --(303) 670 -0144
E-MAIL ADnESS:- GRALMAIL@LJAAPA.COM
Revisions:
A
a
A
a:
a
"
LL f
Ts' Q
�6
z
a
z
J,v
u..
Q..
Q
o
ci�`�pV a`Q
x0
0
Q44
w-
w-�z4
Omu
"
0
I
��
Q..
Q
o
w-
�pmmm"
C�
0 pmm a
O Q x
v
ono -0oa�
o a
PERMIT SET
DRAWN. J.H.,J.B.
CHECKED: E.S. E.Z.
DATE: 0- 1 -21 -O B
ISCAL A5 NOTED
Sheet No.
M7.00
JOB # 2 013
w-
Sheet No.
M7.00
JOB # 2 013