09-57-022GATE VALVE
-TAMPER SNITCH
- ELECTRIC WATER FLOW
SWITCH
- PRESSURE GAUGE
k COCK
TO AUTOMATIC SPRINKLER
SYSTEM-
GLASS
SECTIONAL
DRAIN VALVE
UNION W/ CORROSION RESISTANT ORIFICE
GIVING FLOW EQUAL TO SMALLEST
SPRINKLER ORIFICE IN SYSTEM.
�
A/S !RAIN
STANDPIPE OR
SPRINKLER MAIN.
SEE FLOOR PLAN
BOGS. FOR SIZES.
EXISTING A/S ZONE CONNECTION DETAIL
SCiALEa NONE
i
0
I
U1
ELEVATION
A/S ZONE DRAIN LINE
CEILING CEILING
A/S DRAIN VALVE
INSPECTOR TEST
/CONNNECTION
-TEST VALVE V
SITE GLASS 1'
UNION WITH ORIFICE
TERMINATE MAIN A/S
DRAIN LINE TO EXTERIOR
SEE SECTION
.� ESCUTCHEON
i GROUND FLOOR
ASS DRAIN AND TEST
CONNECTION DETAIL
EXTERIOR WALL
SEE ARCH.DWG.
A/S DRAIN LINE
PIPE SLEEVE
ESCUTHEON
THREADED
OUTLET
Is 45 ELBOW
18' A.F.G.
NOTE:
TYPICAL A/S DRAIN
LINE TERMINATION
TO EXTERIOR.
PIPE HANGER RING
I.T.T. GRINNELL FIG.69
PIPE HANGER RING J PIPE
I.T.T. GRINNELL FIG.260
PIPES 3" & SMALLER PIPES 4" & LARGER
U.L. /F.M. APPROVED
CONCRETE INSERT
PIPING HANGER DETAIL
SCALE:
SPRINKLER NOTES
NONE
1. ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPLIANCE WITH THE
LOCAL FIRE CODES AND ORDINANCES AND INSTALLED IN ACCODANCE
WITH THE LATEST CODES AND STANDARDS.
A. NFPA -13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS. (2002).
B. NFPA -101 LIFE SAFETY CODE. (2003)
C. CHAPTER 69A -3.012 STATE OF FLORIDA FIRE PREVENTION CODE. (2004)
D. BUILDING CODES AND LOCAL REQUIREMENTS.
2. MAKE ALL OFFSETS REQUIRED AS PER JOB CONDITIONS.
3. CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (24)
SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEING INSTALLED.
4. ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENT A NEAT AND
BALANCED CEILING PATTERN UNLESS SHOWN OTHERWISE.
5. CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES
BEFORE INSTALLING SPRINKLER WORK.
6. INSTALL PIPING TIGHT TO STRUCTURE WHERE POSSIBLE.
7. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE
PROTECTION CONTRACTOR.
$. ALL PRODUCTS THE MERWR T RS LABORATORIES RI S (UL)LISTEAND FACTORY (FM) APPROVED.
9000 000 • • •0000 000
•10 •0Y • • • 9999 • •
r • • r• • r
• • • • Y ♦ f f • G •
•000 iro9• 000 0090
•000 0 Y • • •
• ♦ • • • r •
0ti• i 919.0 • ••• • GOY• •
NEW CONSTRUCTION LEGEND
SYMBOL
DESCRIPTION
TEMP
EXISTING TO REMAIN
I. RECESSED CROME PENDANT - QRS
5.6
NEW CONSTRUCTION
-�
CONNECT TO EXIST. AT THIS POINT
APPROVED FOR
BUILDING PER�AITTING PURPOSES
BY IVIIA "III -DADIE COUNTY F! 'RE DEFF1PJRT1N,`ZNT
FIE;? Pi�;'177"'if0i a^{ ,a"^Rf (' MPH'S
a .R P `%,r
I-1 :t P. T'" ,L .1�ayr�
TC.;
BEFt R.E A °Y FIR PROT!D"'7I0 "i S ifS T EM
IS INSTALLED OR RE id r"12LED
DATE,64�- f BY.
SPRINKLER HEAD LEGEND
TYPE
K -FACT
TEMP
LOCATION
I. RECESSED CROME PENDANT - QRS
5.6
1650
ALL SPACES UNLESS NOTED OTHERWISE. BELOW
2. CONCEALED - QRS (W /WHITE C.P.)
5.6
1650
ALL LOBBYS, NURSES STATIONS, PUBLIC AREAS AND CORRIDORS
3. UPRIGHT GENERAL - QRS
5.6
165'
ELECTRIC ROOMS, STAIRS AND ROOMS W /NO CEILINGS
T.S.
TAMPER SWITCH
A.F.F.
ABOVE FINISHED FLOOR
I
FLOW SWITCH
BALL VA LVE-
CAP ON LINE
---- ��
CHECK VALVE
SEE SPECIFICATIONS FOR MODEL NUMBERS.
*�c CONTRACTOR SHALL REFER TO ARCHITECTS REFLECTED CEILING PLAN FOR EXACT HEAD LOCATIONS.
IN NO CASE SHALL SPRINKLER HEADS BE LOCATED MORE THAN 14' -0' ON CENTER.
FIRE PROTECTION ABBREVIATIONS
F.H.C.
FIRE HOSE CABINET
O.S. & Y.
OUTSIDE STEM AND YOKE
F.E.
FIRE EXTINGUISHER
S.C.V.
SECTIONAL CONTROL VALVE
A/S
AUTOMATIC SPRINKLER
F.H.
FIRE HYDRANT
F.SP.
FIRE STANDPIPE
R.P.B.P.
REDUCED PRESSURE BACKFLOW PREVENTER
T.S.
TAMPER SWITCH
A.F.F.
ABOVE FINISHED FLOOR
I
FLOW SWITCH
BALL VA LVE-
CAP ON LINE
---- ��
CHECK VALVE
FIRE PROTECTION LEGEND
SYMBOL DESCRIPTION"
SYMBOL DESCRIPTION
F
FIRE LINE OR MAIN
PARTIAL SECOND FLOOR DEMOLITION PLAN - FIRE PROTECTION
FIRE EXTINGUISHER OR FIRE HOSE CABINET
A/S
AUTOMATIC SPRINKLER MAIN
FP -1,ETC
FIXTURE INDENTIFICATION
D
DRAIN LINE
CONNECTION TO EXISTING
PIPE TURNED UP
•
'FIRE EXTINGUISHER - WALL HUNG
-0
PIPE TURNED DOWN
I
FLOW SWITCH
BALL VA LVE-
CAP ON LINE
---- ��
CHECK VALVE
—
FIRE HYDRANT WITH VALVE
—
SECTIONAL CONTROL VALVE
O.S.&Y. GATE VLV W /TAMPER SW
O
EXISTING SPRINKLER HEAD
•
NEW SPRINKLER HEAD
4
NEW SIDEWALL SPRINKLER HEAD
0
NEW SPRINKLER HEAD BELOW DUCTWORK
PLUMBING /EIRE PROTECTION DRAWING INDEX
SHEET DESCRIPTION
NO.
FP -0.1
SCHEDULES, LEGEND, DETAILS - FIRE PROTECTION
FP -1.1
PARTIAL SECOND FLOOR DEMOLITION PLAN - FIRE PROTECTION
FP -2.1
PARTIAL SECOND FLOOR NEW WORK PLAN - FIRE PROTECTION
BERMELLO•AJAMIL
& PARTNERS MC
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 So. Bayshore Drive
Suite 1000
Miami, Florida 33133
(305) 659 -2050 FAX (305) 859 -9638
Smith a
% Seckman
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Belch, FL 33441
(954) 421 -1260
FAX- (954) 421 -1466
www.ssr- inc.com
Firm Certification - EX- 0000957
Alfred Esquivel PE - 452163
Bruce W. Peek PE - 35201
Chris A. Freyer PE - 43222
Dennis Davis PE - 12522
Donald Netinhe PE - 42454
John E. Moulder 2E - 33200
Juan Echavarria PE - 12677
SS2t JOB alt 0432103.0
STRUCTURAL ENGINEERS
DONNELL, DUQUESNE & ALIAISA, P A.
CONSULTING E=NGINEERS
❑RAMON R. DONNELL P.E. 0011690
CIVIL /STRUCTURAL
❑PEDRO J. DUOUESNEP.E. 0022764
CIV1 L /STRUCTURAL
❑AIDA M. ALMAISA P.,E 0045130
I 4'30 S.W. 74th CT. MIAMI, FLORIDAA3315`.
................ ue isle ! 305) 666-0711 FAX G6G -5257
� -t
r'A
Pe!Y
Revisions:
Project Name:
SOUTH MIAMI
HEART CENTER
PBX RENOVATION
6200 S.W. Y3 STREET
MIAMI, FLORIDA 33143
KEY PLAN
LOCATION-
OF
NON- INVASIVF
0
Comm. No. 40002.000
Scale:
Date: 12 -19 -08
Drawn:
Checked:
CADD File:
Draw'g Title;
GEN. NOTES
SCHEDULES
FIRE PROTECTION
Sheet No.
FP -0.1