Loading...
09-314-022410OU Fire Alarm Control Panel - South Miami Hosp Phase 8 - 1st Fl Main Lobby Standby Total Alarm Total Module ri tion Current Standby Current Alarm Panel Equipment 4100 -9111 0 41000 CONFlG. DOMESTIC 120V 0.373000 0.000000 0.470000 0.000000 4100 -0621 1 ANALOG AUDIO RISER MODULE 0.000000 0.000000 0.000000 0.000000 4100 -0632 1 UTILITY BLOC, 16 TERMINALS 0.000000 0.000000 0.000000 0.000000 4100 -0634 1 POWER DISTRIBUTION MODULE 120V 0.000000 0.000000 0.000000 0.000000 4100 -1272 1 11EXPANSION PHONE CONTROLLER 0.075000 0.075000 0.075000 0.075000 4100 -1279 le 2' BLANK DISPLAY MODULE 0.000000 0.000000 0.000000 0.000000 4100 -1314 1 1DOW AMP W/6 B NACS 120VAC 25V 0.060000 0.060000 4.000000 4.000000 4100 -2300 2 EXPANSION BAY PHASE 10 ONLY) 0.000000 0.000000 0.000000 0.000000 4100 -2320 1 AUDIO EXPANSION BAY KIT 0.000000 0.000000 0.000000 0.000000 4100 -6014 1 NETWORK IF CARD, WIRED 0.046000 0.046000 0.046000 0.046000 4100 -6056 2 NETWORK MEDIA CARD WIRED 0.055000 0.110000 0.055000 0.110000 4100 -2153 1 INDICATOR ONLY 3 BAY CLASS 0.000000 0.000000 0.000000 0.000000 4100 -3101 1 IDNET MODULE, UP TO 250 POINTS 0.075000 0.075000 0.115000 0.115000 0.240000 Total Panel Stby 0.388000 Total Panel Alarm 4.348000 Peripheral Devices 4090 -9001 91 JIDNEr SUPERMSED LAM • 0.000000 0.000000 0.000000 0.000000 4090 -9002 81 JIDNEr RELAY NM • 0.000000 0.000000 0.000000 0.000000 4098 -9756 109 ITRUEALARM DUCT SMOKE SENSOR W RELAY OUTPUT • 0.002400 0.261600 0.015000 1.635000 2098 -9806 109 REMOTE TEST STATION W LED AND KEY SWITCH 0.000000 0.000000 0.000000 0.000000 2098 -9797 109 SAMPUNG TUBE 49' 0.000000 0.000000 0.000000 0.000000 4098 -9843 214 ENCAPSULATED RELAY PAM -SD 0.002400 0.513600 0.015000 3.210000 4098 -9714 211 TRUEALARM PHOTO SMOKE SENSOR 0.000000 0.000000 0.000000 0.000000 4098 -9733 1 TRUEALARM HEAT SENSOR 0.000000 0.000000 0.000000 0.000000 4098 -9792 212 TRUEAIARM SENSOR BASE • 0.000000 0.000000 0.000000 0.000000 4099 -9001 48 1 IDNET SINGLE ACTION PULL STATION • 0.000000 0.000000 0.000000 0.000000 4009 -9201 5 4009 IDNET NAC EXTENDER, 120 VAC 0 0.000000 0.000000 0.009000 0.045000 2088 -9608 38 MAGNETIC DOOR HOLDER, SEMI -FLUSH 0.015000 0.540000 0.000000 0.000000 2088 -9032 13 RELAY SPOT W LED MR -801 0.000000 0.000000 0.022000 0.286000 2084 -9001 51 REMOTE PHONE JACK 0.000000 0.000000 0.000000 0.000000 4902 -9703 15 SPEAKER 25VRMS RED 0.000000 0.000000 0.000000 0.000000 4903 -9357 lie TRUER ERT 75CD SPEAKER/VISIBLE 25V OVRMS RED 0.000000 0.000000 0.199000 23.482000 4904 -9332 42 ITRUEALERT 75CD VISIBLE ONLY RED SYNC 0.000000 0.000000 0.199000 8.358000 4904 -9333 1 ITRUEALERT 110CD VISIBLE ONLY RED SYNC 0.000000 1 0.000000 0.253000 0.253000 2081 -9027 1 1 TRANSIENT CUBE 0.000000 0.000000 0.000000 0.000000 Miscellaneous Outside Purchased Items Requiring System Power CC -623 3 IDUAL CONTACT FIXED 135 HEAT DETECTOR 0.000000 0.000000 0.000000 0.000000 EIA -SS 4 ELEVATOR WARNING SIGN 0.000000 0.000000 0.070000 0.280000 ET70WP- 2475W -FR 5 SPEAKER STROBE WEATHERPROOF 180CD 0.000000 0.000000 0.000000 0.000000 SM -12 24 -R 1 SYNC MODULE 0.000000 0.000000 0.000000 0.000000 4906 -9101 4 STROBE ONLY MC 75CD 24VDC, WALL, RED. 0.000000 0.000000 0.186000 0.744000 0 Total Peri h Stbyj 1.3152 1 Total Peri h Alarm 1 38.293 Total Standby Ampa 1.681 Total Alarm Ampa 42.639 • Current Draw Included With Device Addresses Used (See additional current draws) 1. 2 -wire detector alarm current is included in the alarm current of the Initiating Device Circuit. Note: The total Ah required takes into account any physical and chemical properties of battery discharge rates, high alarm current draw of a battery after a long (standby) low current draw, and reflects the manufacturers discharge rates per their recommendations and UL standards. Standby Alarm Battery Set #1 (Cabinet/Charger 1 Qty Current Current Additional Current Draws Cabinet #1 Card Power 0.306 Backup Amplifier 0.346 Current Draw For 100 Watt Or 95 Watt Amplifiers 1 0.060 0 4.000 Current Draw For Flex 35 and 50 Watt Amplifiers 0 0.000 0.000 Power For External Peripheral Devices 1.31520 38.29300 1.681 < -- Sub Totals - -> 42.639 Additional Current Draws Not enough MAPNET/IDNet cards available RUI Connected Peripheral Devices 0 0.000 0.000 MAPNET /IDNet Device Addresses ordered / used 544 544.0 0.435 0.539 Spare addressable point capacity included for battery talc 20% 109 0.087 0.108 2.203 <- -Grand Totals - -> 43.286 Additional Battery Capacity Required 20% 0.441 8.657 Standby Time - 4 Hrs 10.574 Standby Ah Alarm Time - 15 Mine. 12.986 Alarm Ah Battery Required 2081 -9279 110AH 57.127 Total Ah 6th FL STAIR 2 PHONES Phase 8 South Miami Hosp Mini -Panel - 1st Fl Main Lobby PHONE/SPEAKER CIRCUIT LOAD CALCULATION MAXIMUM -3 dB DROP PER CIRCUIT IM M Backup From SO CIRCUIT NUMBER Standby Total Alarm Total Battery Battery Battery Battery Module Qty Description Current Standby Current Alarm Set 1 Set #2 Set #3 Set #4 Panel Equipment ESTIMATED EXISTING 4906 -9101 4906 -9151 t t y Qty Qty 4100 -9600 1 BASIC TRANSPONDER 0.087000 0.087000 0.087000 0.087000 1 GAUGE VOLTAGE VOLTAGE 4100 -0621 1 ANALOG AUDIO RISER MODULE 0.000000 0.000000 0.000000 0.000000 1 18, 16, 14, 12 DROP % DROP (VOLTS) 4100 -0632 1 U IUTY BLOC, 16 TERMINALS 0.000000 0.000000 0.000000 0.000000 1 0 1.592 14 4100 -0634 2 POWER DISTRIBUTION MODULE 120Y 0.000000 0.000000 0.000000 0.000000 2 100 ft 1.592 0 4100 -0636 1 BOX TO BOX HARNESS KIT 0.000000 0.000000 0.000000 0.000000 1 SIG -5 1ST FLOOR SW WING RVISUAL 4100 -1248 2 100 WATT EXPANSION NAC BOARD 0.001200 0.002400 0.120000 0.240000 2 0.6 Ohms 358 ft 4100 -1272 10 EXPANSION PHONE CONTROLLER 0.075000 0.750000 0.075000 0.750000 10 0 0.00% 0.000 4100 -1314 1 10OW AMP W/6 B NAGS 120VAC 25V 0.060000 0.060000 4.000000 4.000000 1 0 0 0.000 4100 -2300 5 EXPANSION BAY PHASE 10 ONLY) 0.000000 0.000000 0.000000 0.000000 5 100 it 0 ft 0.000 4100 -2320 5 AUDIO EXPANSION BAY KIT 0.000000 0.000000 0.000000 0.000000 5 0 ft 5IG -9 1ST FLOOR SW WING 4100 -3206 1 8 RELAYS - 3 AMP 0.015000 0.015000 0.190000 0.190000 1 1.466 0.9 Ohms 4100 -5111 1 SYSTEM PWR SUPPLY (SPS) - 120VAC 60HZ 0.175000 0.175000 0.225000 0.225000 1 1.181 14 5.33% 4100 -5128 2 EXTERNAL BATTERY POWER 0.000000 0.000000 0.000000 0.000000 2 1.393 3 0 4100 -2163 2 INDICATOR ONLY 3 BAY SOLID 0.000000 0.000000 0.000000 0.000000 2 REQUIRES NAC EXPANDER BOARD AMPOi 0 IL 0.000 Total Panel Stby 1.089400 Total Panel Alarm 5.492000 0.00% 0.000 Total Peri h Stby 0.0000 Total Peri h Alarm 0.000 REQUIRES NAC EXPANDER BOARD Total Standby Ampa 1.089 Total Alarm Ampa 5.492 0 •Current Draw Included With Device Addresses Used (See additional current draws) 0 1 0.00% 0.000 0.0 Ohms 1. 2 -wire detector alarm current is included is the alarm current of the Initiating Device Circuit. 5IG -14 REQUIRES NAC EXPANDER BOARD SIG -30 0 ft 0.000 Note: The total Ah required takes into account any physical and chemical properties of battery discharge rates, 0 0.000 0 0.00% high alarm current draw of a battery after a long (standby) low current draw, and reflects the 0.0 Ohms 0 it 2nd FL STAIR 2 PHONES SIG -31 manufacturers discharge rates per their recommendations and UL standards. 25 vrms 0 Total Load (AMPS) 1 0.00 Watts 100 ft Standby 0 ft Alarm AMPOI 8.756 Battery Set #1 Cabinet Char er 1 Qty Current 9.500 Current 0 1 Cabinet it Card Power 1.029 Backup Amplifier 1.492 1.9 Ohms AMPOI Current Draw For 100 Watt Or 95 Watt Amplifiers 1 0.060 0 4.000 0 0 Current Draw For Flex 35 and 50 Watt Amplifiers 0 0.000 150 ft 0.000 0 ft 1.9 Ohms Power For External Peripheral Devices 0.00000 SIG -34 0.00000 25 vans 0 0 1.089 < -- Sub Totals - -> 5.492 0.00 dB 0 ft Additional Current Draws AMPOI 6th FL STAIR 2 PHONES SIG -35 18 crwq 25 vans RUT Connected Peripheral Devices 0 0.000 1 0.000 200 ft 0.00 dB MAPNET /IDNet Device Addresses ordered / used 0 0.0 0.000 AMPOI 0.000 SIG -36 18 owq Spare addressable point capacity included for battery tale Oy 0 0.000 0 0.000 0.00 Watts 225 ft. 0.00 dB 1.089 <- -Grand Totals - -> 5.492 2.9 Ohms AMPOi Additional Battery Capacity Required 0% 0.000 18 owg 0.000 0 10GA = 0.001210 Standby Time = 24 Hrs 26.146 Standby Ah 0.00 dB 0 ft 1.3 Ohms Alarm Time = 5 Mins. 0.458 Alarm Ah 18 awg 25 vrms 12GA - 0.001930 Battery Required 2081 -9276 33AH 32.163 Total Ah 100 ft 0.00 dB 0 it 410OU Fire Alarm Control - South Miami Hosp Phase 8 - 1st Fl Main Lobby PHONE/SPEAKER CIRCUIT LOAD CALCULATION MAXIMUM -3 dB DROP PER CIRCUIT IM M PHONE/SPEAKER CIRCUIT DESCRIPTION SO CIRCUIT NUMBER WIRE GAUGE (18, 16, 14 12 ) CIRCUIT VOLTAGE (25 OR 70 VRMS ) APPLIANCES TAPPED AT 0.5 Watts QUANTITIES TAP VALUES 2084 -9001 TAPPED AT PHONES 0.5 Watts 0 TOTAL CIRCUIT LOAD (WATTS) NAC SCHEDULE / VOLTAGE DROP CALCULATION ACTUAL WIRE/LOSS dB MAXIMUM ALLOWABLE CKT. LENGTH V/0 S/V 1ST FLOOR PHONES VOLTAGE DROP TOTALS 25 vans 0 0 4 17 y MAXIMUM VOLTAGE DROP ESTIMATED EXISTING 4906 -9101 4906 -9151 TOTAL WIRE ACTUAL ACTUAL TOTAL MAXIMUM CIRCUIT OUTPUT VOLTAGE - 20.4 FOR CALCULATIONS CIRCUIT CIRCUIT 0.00 Wotts 75CD 75CD CKT. LOAD GAUGE VOLTAGE VOLTAGE CIRCUIT ALLOWABLE CIRCUIT DESCRIPTION TYPE LENGTH 1.000 0.186 0.188 AMPS 18, 16, 14, 12 DROP % DROP (VOLTS) RESISTANCE CKT. LENGTH SIC -3 1ST FLOOR NW WING RVISUAL 100 ft 1.592 0 0 1.592 14 4.79% 0.977 0.6 Ohms 358 ft. SIG -4 1ST FLOOR WEST WING RVISUAL 100 ft 1.592 0 1 0 1.592 14 4.79% 0.977 0.6 Ohms 358 ft. SIG -5 1ST FLOOR SW WING RVISUAL 100 ft 1.592 0 0 1.592 14 4.79% 0.977 0.6 Ohms 358 ft SIG -6 UNUSABLE SIGNAL CIRCUIT 1 0 ft 0.000 0 0 0.000 0 0.00% 0.000 0.0 Ohms 0 ft. SIG -7 UNUSABLE SIGNAL CIRCUIT 0.00 Watts 0 ft 0.000 0 0 0.000 0 0.00% 0.000 0.0 Ohms 0 ft. SIG -8 UNUSABLE SIGNAL CIRCUIT 100 it 0 ft 0.000 0 0 0.000 0 0.00% 0.000 0.0 Ohms 0 ft 5IG -9 1ST FLOOR SW WING RVISUAL 150 ft 1.592 0 0 1.592 14 7.19% 1.466 0.9 Ohms 358 ft. SIG -10 1ST FLOOR SW WING RVISUAL 150 iL 0.995 1 0 1.181 14 5.33% 1.088 0.9 Ohms 483 ft SIG -11 1ST FLOOR EAST WING RVISUAL 150 ft 1.393 3 0 1.951 14 8.81% 1.797 0.9 Ohms 292 ft SIG -12 REQUIRES NAC EXPANDER BOARD AMPOi 0 IL 0.000 0 0 0.000 0 0.00% 0.000 0.0 Ohms 0 ft. SIG -13 REQUIRES NAC EXPANDER BOARD 7th FL STAIR 1 PHONES 0 ft 0.000 0 0 0.000 0 1 0.00% 0.000 0.0 Ohms 0 ft. 5IG -14 REQUIRES NAC EXPANDER BOARD SIG -30 0 ft 0.000 0 0 0.000 0 0.00% 0.000 0.0 Ohms 0 it 2nd FL STAIR 2 PHONES SIG -31 18 awo 25 vrms 0 Total Load (AMPS) 1 0.00 Watts 100 ft 0.00 dB 0 ft METHOD USED TO CALCULATE VOLTAGE DROP: AMPOI 8.756 4 0 9.500 0 0 1 0.00 Watts 150 ft 0.00 dB [(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS / FT)] 1.9 Ohms AMPOI 4th FL STAIR 2 PHONES SIG -33 18 owq 25 vrms 0 0 1 0.00 Watts 150 ft Wire Resistance At 0 ft 1.9 Ohms AMPOI 5th FL STAIR 2 PHONES SIG -34 18 owq 25 vans 0 0 1 0.00 Watts 75 Degrees Celsius 0.00 dB 0 ft 2.6 Ohms AMPOI 6th FL STAIR 2 PHONES SIG -35 18 crwq 25 vans 0 0 1 187 Degrees Fahrenheit 200 ft 0.00 dB 0 ft 26 Ohms AMPOI 7th FL STAIR 2 PHONES SIG -36 18 owq 25 vans 0 0 Ohms / ft 0.00 Watts 225 ft. 0.00 dB 0 ft 2.9 Ohms AMPOi 1ST FL STAIR 3 PHONES SIG -37 18 owg 25 vans 0 10GA = 0.001210 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMP01 2nd FL STAIR 3 PHONES SIG -38 18 awg 25 vrms 12GA - 0.001930 0 1 0.00 Watts 100 ft 0.00 dB 0 it 1.3 Ohms AMP01 3rd FL STAIR 3 PHONES SIG -39 18 awg 14GA = 0.003070 0 0 1 0.00 Watts 150 ft 0.00 dB 0 it IS Ohms AMP01 4th FL STAIR 3 PHONES SIG -40 16GA = 0.004890 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 f . 1.9 Ohms AMP01 5th FL STAIR 3 PHONES 18GA = 0.007770 18 aw 25 vans 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft. 2.6 Ohms AMPOI HIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE UNCOATED SOLID COPPER WIRE) SIG -42 18 awg 25 vans 0 0 1 0.00 Watts 200 ft 0.00 d8 NOTE: 2.6 Ohms AMPOI 7th FL STAIR 3 PHONES SIG -43 1 18 owg 25 vans 0 0 1 0.00 Watts 225 ft LUMP SUM METHOD WAS USED TO CALCULATE ALL WABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN 2.9 Ohms AMPOI 1ST FL STAIR 4 PHONE SIG -44 18 crwg 25 vrms 0 0 OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN 100 ft. 0.00 dB 1 0 ft 1.3 Ohms AMPOI 2nd FL STAIR 4 PHONE SIG -45 18 awq ON THE SHOP DRAWINGS. iF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT 0 0 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms LENGTH, CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE. 3rd FL STAIR 4 PHONE SIG -46 18 awQ 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 ft 41000 Fire Alarm Control Panel - South Miami Hosp Phase 8 - 1 st Fl Main Lobby PHONE/SPEAKER CIRCUIT LOAD CALCULATION MAXIMUM -3 dB DROP PER CIRCUIT IM M PHONE/SPEAKER CIRCUIT DESCRIPTION SO CIRCUIT NUMBER WIRE GAUGE (18, 16, 14 12 ) CIRCUIT VOLTAGE (25 OR 70 VRMS ) APPLIANCES TAPPED AT 0.5 Watts QUANTITIES TAP VALUES 2084 -9001 TAPPED AT PHONES 0.5 Watts 0 TOTAL CIRCUIT LOAD (WATTS) ESTIMATED CIRCUIT LENGTH ACTUAL WIRE/LOSS dB MAXIMUM ALLOWABLE CKT. LENGTH TOTAL CIRCUIT RESISTANCE OHMS Amplifier Power supply 1ST FLOOR PHONES SIG -15 18 owg 25 vans 0 0 4 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMPOI 2ND FLOOR PHONES SIG -16 18 owg 25 vans 0 0 3 0.00 Wotts 150 ft 0.00 dB 0 fl 1.9 Ohms AMPOI 3rd FLOOR PHONES SIG -17 18 awg 25 vrms 0 0 3 0.00 Watts 150 ft 0.00 dB 0 ft. 1.9 Ohms AMPOI 4th FLOOR PHONES SIG -18 18 awo 25 vrms 0 0 3 0.00 Watts 175 ft 0.00 dB 0 ft. 2.2 Ohms AMPOI 5th FLOOR PHONES SIG -19 18 awg 25 vrms- 0 0 3 0100 Watts 175 ft. 0.00 dB 0 ft 2.2 Ohms AMPOI 6th FLOOR PHONES SIG -20 18 owq 25 vans 0 0 3 0.00 Watts 200 ft 0.00 dB 0 ft 2.6 Ohms AMPOI 7th FLOOR PHONES SIG -21 18 owq 25 vrms 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft 2.6 Ohms AMPOI ELEVATOR MACHINE RM PHONES SIG -22 18 awq 25 vrms 0 0 3 0.00 Watts 200 ft. 0.00 dB 0 ft 2.6 Ohms AMPOI 1ST FL STAIR 1 PHONES SIG -23 18 cwq 25 vans 0 0 1 0.00 Watts 100 it 0.00 dB 0 ft 1.3 Ohms AMPOI 51) FL STAIR 1 PHONES SIG -24 18 awg 25 vrms 0 0 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMPOI 3rd FL STAIR 1 PHONES SIG -25 18 awa 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 it 1.9 Ohms AMPOi 4th FL STAIR 1 PHONES SIG -26 18 awa 25 vmis 0 0 1 0.00 Wafts 150 ft 0.00 dB 0 ft 1.9 Ohms AMPOI 5th FL STAIR 1 PHONES SIG -27 18 awg 25 vrms 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft. 2.6 Ohms AMPOi 6th FL STAIR 1 PHONES SIG -28 18 awq 25 vans 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft 2.6 Ohms AMPOI 7th FL STAIR 1 PHONES SIG-29 18 (rwq 25 vrms 0 0 1 0.00 Watts 225 fL 0.00 dB 0 ft 2.9 Ohms AMPOI 1ST FL STAIR 2 PHONES SIG -30 18 awg 25 vans 0 0 1 0.00 Watts 100 ft 0.00 d8 0 ft 1.3 Ohms AMPOI 2nd FL STAIR 2 PHONES SIG -31 18 awo 25 vrms 0 0 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMPOI 3rd FL STAIR 2 PHONES SIG -32 18 owa 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 ft 1.9 Ohms AMPOI 4th FL STAIR 2 PHONES SIG -33 18 owq 25 vrms 0 0 1 0.00 Watts 150 ft 0.00 dB 0 ft 1.9 Ohms AMPOI 5th FL STAIR 2 PHONES SIG -34 18 owq 25 vans 0 0 1 0.00 Watts 200 ft. 0.00 dB 0 ft 2.6 Ohms AMPOI 6th FL STAIR 2 PHONES SIG -35 18 crwq 25 vans 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft 26 Ohms AMPOI 7th FL STAIR 2 PHONES SIG -36 18 owq 25 vans 0 0 1 0.00 Watts 225 ft. 0.00 dB 0 ft 2.9 Ohms AMPOi 1ST FL STAIR 3 PHONES SIG -37 18 owg 25 vans 0 0 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMP01 2nd FL STAIR 3 PHONES SIG -38 18 awg 25 vrms 0 0 1 0.00 Watts 100 ft 0.00 dB 0 it 1.3 Ohms AMP01 3rd FL STAIR 3 PHONES SIG -39 18 awg 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 it IS Ohms AMP01 4th FL STAIR 3 PHONES SIG -40 18 awil 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 f . 1.9 Ohms AMP01 5th FL STAIR 3 PHONES SIG -41 18 aw 25 vans 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft. 2.6 Ohms AMPOI 6th FL STAIR 3 PHONES SIG -42 18 awg 25 vans 0 0 1 0.00 Watts 200 ft 0.00 d8 0 ft 2.6 Ohms AMPOI 7th FL STAIR 3 PHONES SIG -43 1 18 owg 25 vans 0 0 1 0.00 Watts 225 ft 0.00 dB 0 ft 2.9 Ohms AMPOI 1ST FL STAIR 4 PHONE SIG -44 18 crwg 25 vrms 0 0 1 0.00 Watts 100 ft. 0.00 dB 1 0 ft 1.3 Ohms AMPOI 2nd FL STAIR 4 PHONE SIG -45 18 awq 25 vans 0 0 1 0.00 Watts 100 ft 0.00 dB 0 ft 1.3 Ohms AMPOI 3rd FL STAIR 4 PHONE SIG -46 18 awQ 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 ft 1.9 Ohms AMPOI 4th FL STAIR 4 PHONE SIG -47 18 awg 25 vans 0 0 1 0.00 Watts 150 ft 0.00 dB 0 ft 1.9 Ohms AMPOi 5th FL STAIR 4 PHONE SIG -48 18 owil 25 vrms 0 0 1 0.00 Watts 200 ft 0.00 dB 0 ft 2.6 Ohms AMPOI 6th FL STAIR 4 PHONE SIG -49 18 awa 25 vrm3 0 0 1 0.00 Watts 200 ft. 0.00 dB 0 ft. 2.6 Ohms AMPOI Circuit SIG -50 18 awq 25 vans 0 0 0 0.00 Watts 0 ft 0.00 dB 0 ft, 0.0 Ohms AMPOI 1ST FLOOR SPEAKERS SIG -51 18 owg 25 vrms 26 0 0 13.00 Watts 150 ICI -0.34 dB 1.557 ft. 1.9 Ohms AMPOI 2nd FLOOR SPEAKERS SIG -52 18 awg 25 vans 13 1 0 6.50 Watts 200 ft. -0.23 d8 31113 ft 16 Ohms AMPOI 3rd FLOOR SPEAKERS SIG -53 18 awq 25 vans 10 3 0 5.00 Watts 225 ft -0.20 dB 4,047 ft 2.9 Ohms AMPOI 4th FLOOR SPEAKERS SIG -54 18 awo 25 vans 16 3 0 8.00 Watts 250 ft. -0.35 dB 2,529 ft 3.2 Ohms AMPOI 5th FLOOR SPEAKERS SIG -55 18 owq 25 vans 11 3 0 5.50 Watts 300 ft. -0.29 dB 3,679 ft 3.8 Ohms AMPOI 6th FLOOR SPEAKERS SIG -56 1 8 awo 1 25 vans 15 3 0 7.50 Watts 325 ft -0.42 dB 2,698 ft 4.2 Ohms AMPOI 7th FLOOR SPEAKERS SIG -57 18 awg 25 vans 3 0 0 1.50 Watts 350 ft -0.1jdB 10,118 ft 4.5 Ohms AMP01 EL EVATOR MACHINE RM SPEAKERS SIG -58 18 ow 25 vans 4 2 0 2.00 Watts 375 ft -0.1 10118 ft 4.8 Ohms AMP01 Circuit SIG -59 18 aw 25 vrms 0 0 0 0.00 Watts 0 ft 0.0 0 ft 0.0 Ohms AMPOI Circuit SIG -60 18 aw 25 vrms 0 0 0 0.00 Watts 0 ft 0.0 0 fl 0.0 Ohms AMP01 Circuit SIG -61 18 aw 25 vans 0 0 0 0.00 Watts 0 tL 0.0 0 fL 0.0 Ohms AMP01 Circuit SIG -62 18 aw 25 vrms 0 0 0 0.00 Watts 0 LL 0.0 0 f . 0.0 Ohms AMP01 Applianc Summa Total Load Watts Mox Los Per Map 99 15 50 49.00 100.00 Max Load Watts Per Circuit NOTE 45.00 LUMP SUM METHOD WAS USED TO CALCULATE MAXIMUM ALLOWABLE CIRCUIT LENGTH. THIS METHOD ALLOWS FOR A SMALL MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT LENGTH, CONTACT YOU LOCAL SIMPLEX BRANCH. BATTERY CALLS SCALE ,vas U CONSULTING L. TRIANA &ASSOCIATES, INC. ENGINEERS CERTIFICATE OF AQTHOI�12kYjON: 26644 5151 S.W. 98th MIRD ,) S MIAMI, FLORIDIA�3 165 E $rte �t ..K IraJ�,:i�; . Florida R96 ti 5707d ° y l IM M LIJ cc U G p Q -I W m LL Q ne m Q C u7 w ccjpp m m IL N O (O � ao M F- 0 ZO z rn Lo Rau: GO O n. •'~ ° a U) V = W V z U) ,v � v \ / Nn J J ❑ wj