TEST & BALANCE NOTES
A. CONTRACTOR SHALL BE RESPONSIBLE TO TEST AND BALANCE THE SYSTEM
TO ACHIEVE RATES AS SHOWN ON PLANS AND SCHEDULES.
TEST/BALANCE RESULTS SHALL BE SUBMITTED TO ARCHITECT/ENGINEER
FOR REVIEW PRIOR TO FINAL PAYMENT REQUISITION. THE TEST AND
BALANCE SHALL BE PERFORMED BY AN INDEPENDENT T &B CONTRACTOR
CERTIFIED BY THE A.A.B.C. AND /OR N.E.B.B.
THE SUBMITTED TEST AND BALANCE REPORT SHALL BE ON OFFICIAL
A.A.B.C. OR N.E.B.B. REPORT FORMS.
B. BALANCE AIR SYSTEM TO DELIVER SPECIFIED QUANTITIES AT
EACH OUTLET WITHIN 10% USING A.A.B.C. PROCEDURES AND
TESTS. SUBMIT AIR BALANCE TEST RESULTS FOR REVIEW PRIOR
TO FINAL INSPECTION AND ACCEPTANCE.
C. FINAL CONSTRUCTION
UPON COMPLETION OF THE HVAC RENOVATION WORK, THE SAME
CONTRACTOR SHALL REBALANCE THE NEW AND EXISTING EQUIPMENT
AND DUCTS TO PROVIDE INDICATED AIR QUANTITIES TO THE RENO-
VATED SPACE, ANY ADDITION OF DAMPERS, ADJUSTMENTS, (FAN SPEED,
CHANGE OUT OF PULLEYS, ETC.) REQUIRED FOR THIS SHALL BE INCLUDED
IN THIS CONTRACTOR PROPOSAL
D. FINAL REPORT
SUBMIT FINAL TEST AND BALANCE REPORT TO ENGINEER FOR REVIEW
AND ACEPTANCE ONE WEEK PRIOR TO FINAL AHCA INSPECTION FOR
EACH PHASE.
MECHANICAL SPECIFICATIONS
A. GENERAL REQUIREMENTS
1. SCOPE OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, TOOLS,
EQUIPMENT, TRANSPORTATION, HOISTING, RIGGING, INSURANCE,
ETC., TO PERFORM THE WORK AS INDICATED ON THE DRAWINGS AND
HEREIN SPECIFIED FOR A COMPLETE INSTALLATION.
2. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL STATE AND
LOCAL CODES AND ORDINANCES. AIA 2006 AND NFPA LSC 101 2003 CODES.
FBC 2004 WITH 2006 AMENDMENTS.
3. MANUFACTURES SHALL PROVIDE THEIR STANDARD GUARANTEES
AND WARRANTIES FOR WORK UNDER THIS CONTRACT.
4. LOCATIONS OF PIPING, DUCTWORK, CONDUITS AND EQUIPMENT
SHALL BE ADJUSTED TO ACCOMMODATE THE NEW WORK. LINES
WHICH PITCH SHALL HAVE THE RIGHT -OF -WAY OVER THOSE WHICH
DO NOT PITCH. OFFSETS, TRANSITIONS AND CHANGES OF
DIRECTION IN ALL SYSTEMS SHALL BE MADE AS REQUIRED TO
MAINTAIN PROPER HEADROOM AND PITCH OF SLOPING LINES
WHETHER OR NOT INDICATED ON THE DRAWINGS. ALL WORK SHALL
BE INSTALLED IN A WAY TO PERMIT REMOVAL AND ALLOW PROPER
ACCESS TO ALL EQUIPMENT INCLUDING DUCT ACCESS DOORS.
5. FINAL LOCATION OF ALL AIR DISTRIBUTION DEVICES, T -STATS
CONTROL DEVICES, ETC. SHALL BE COORDINATED WITH THE
ARCHITECTURAL REFLECTED PLAN AND /OR OTHER ARCH. DETAILS.
OFFSETS OF DUCTWORK, ADDED SHEETMETAL, FITTINGS, ELBOWS
ETC. SHALL BE PROVIDED AS REQUIRED TO COMPLY WITH ARCH.
PLANS.
6. ALL EQUIPMENT SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT.
ALL EQUIPMENT SHALL MEET THE AUTHORITIES HAVING
JURISDICTION. WHERE ACCEPTANCE IS CONTINGENT UPON THE
PRODUCTS LISTED OR LABELED, THE PRODUCT SHALL BE LISTED
OR LABELED.
7. ALL EQUIPMENT OF ONE TYPE, SUCH AS VALVES, FANS AIR
HANDLING UNITS, SHALL BE THE PRODUCT ON ONE MANUFACTURER.
8. PROVIDE ALL HANGERS AND SUPPORTS AS REQUIRED TO SUPPORT
ALL NEW DUCTWORK AND EQUIPMENT.
9. PAY FOR ALL PERMITS AND FEES, OBTAIN ALL APPROVALS.
10. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL
CONTRACTOR TO STUDY ALL DRAWINGS AND DETAILS SO THAT THE
INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED.
THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE TO SATISFY
HIMSELF THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS
OF THIS PROJECT. IF DISCREPANCIES EXIST BETWEEN DRAWINGS
AND /OR SITE CONDITIONS, THE MECHANICAL CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO SIGNING OF CONTRACT.
FAILURE TO DO SO WILL NOT BE ALLOWED AS A BASIS FOR
ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OR
DIFFERENCE FROM CONDITIONS INFERRED OR INDICATED ON THE
DRAWINGS THAT WOULD HAVE BEEN APPARENT DURING SAID VISIT.
11. ALL CUTTING, CORE DRILLING, PATCHING, ETC. REQUIRED FOR
THE INSTALLATION OF THE NEW MECHANICAL SYSTEMS SHALL BE BY
THE MECHANICAL CONTRACTOR UNDER SUPERVISION OF THE GENERAL
CONTRACTOR.
12. HVAC WORK IS DIAGRAMMATIC. EXACT LOCATION OF ALL COMPONENTS
ARE TO BE DETERMINED IN THE FIELD AND BY THE ACTUAL BUILDING
CONDITIONS. EQUIPMENT, DUCTS OR PIPES INTERFERING WITH THE
INSTALLATION SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL
COST TO THE OWNER. COORDINATE WITH ALL TRADES TO AVOID
INTERFERENCE OF EQUIPMENT.
13. INSTALLATION METHODS SHALL PERMIT ACCESSIBILITY FOR
SERVICE AND /OR REPLACEMENT OF EQUIPMENT PROVIDED.
14. ALL MECHANICAL EQUIPMENT SHALL BE ISOLATED FROM THE
BUILDING STRUCTURE BY MEANS OF NOISE AND VIBRATION
ISOLATORS. DUCTWORK PENETRATIONS THROUGH WALLS SHALL NOT
BE RIGIDLY CONNECTED TO THE BUILDING STRUCTURE. SLEEVES
SHALL BE PROVIDED WITH CLEARANCES AROUND THE OUTSIDE. ALL
SUCH PENETRATIONS SHALL BE SMOKE AND FIRESTOPPED.
15. ALL DEBRIS TO BE REMOVED DAILY.
B. SCOPE OF WORK
1. INSTALL ALL DUCTWORK, PIPING, EQUIPMENT, ETC. AS INDICATED IN
THE CONSTRUC11ON DOCUMENTS OR SPECIFICATIONS.
2. PROVIDE ALL NEW DISCONNECTS AND CAPPING TO FACILITATE
CONSTRUCTION. ALL REMOVAL AND DISPOSAL SHALL BE
ACCOMPLISHED BY THE GENERAL CONTRACTOR.
3. TEST AND BALANCE AS SHOWN ON PLANS BY MECHANICAL CONTRACTOR.
T &B REPORT WILL BE REQUIRED TO BE SUBMITTED TO ENGINEER FOR
APPROVAL.
4. THE EQUIPMENT INDICATED ON THE DRAWINGS HAS BEEN COORDINATED
WITH THE ELECTRICAL SYSTEMS. IF THE CONTRACTOR ELECTS TO USE
ALTERNATE EQUIPMENT, HE SHALL BE RESPONSIBLE FOR ALL
COORDINATION WITH THE ELECTRICAL ENGINEER AND SHALL BEAR ANY
EXPENSE TO THE ELECTRICAL CONTRACTOR RESULTING FROM SUCH
ALTERNATE SELECTIONS.
5. CONTRACTOR SHALL NOT DEVIATE FROM THESE DESIGN DOCUMENTS
WITHOUT PRIOR APPROVAL FROM ENGINEER. CONTRACTOR IS
RESPONSIBLE FOR ALL AS -BUILT DRAWINGS AND SHALL BEAR ALL
COSTS REQUIRED TO DOCUMENT AS -BUILT DRAWINGS, CONTRACTOR
SHALL MAINTAIN REDLINE MARKUP DRAWINGS OF AS -BUILT CONDITIONS
AT THE JOB SITE.
C. MATERIALS
INSULATION, ADHESIVE, COATING SEALERS, TAPES, SHALL HAVE A FLAME
SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPMENT OF 50 OR LESS
IN ACCORDANCE WITH ASTM E -84 AND UL 723.
1. EXHAUST AIR DUCTWORK
CONSTRUCTION: GALVANIZED SHEET METAL, ASTM A 653P /6/53M,
SHALLZCOMP Y COATING WITH UL 1181vA.RO OMP YNWIT AND SEAM
SMA NA'S "HVAC TAPE/SEALANT
INSTALLATION. PRESSURE CLASS: 1'� W.G. (SMACNA TABLE 1 -1S)CT
CONSTRUCTION STANDARDS, METAL AND FLEXIBLE" FOR FABRICATION AND
INSULATION: NONE UNLESS SPECIFIED OTHERWISE.
FLEXIBLE DUCTS: CORRUGATED ALUMINUM. INSULATION: NONE.
2. SUPPLY AND RETURN DUCTWORK RECTANGLE -
ALL DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED
SHEET METAL (ASTM A527), BASED ON 2" STATIC PRESSURE
WHICH SHALL BE CONSTRUED TO BE THE "OPERATING PRESSURE" AS
INDICATED IN SMACNA TABLE 1 -1 AND ASSOCIATED NOTES.
PROVIDE 2" DUCT WRAP AT R =6.
4. CONDENSATE PIPING
TYPE L COPPER. PROVIDE P -TRAP.
5. HOT WATER REHEAT WATER PIPE AND INSULATION
TYPE L COPPER. PROVIDE WITH 1" FIBERGLASS INSULATION.
PROVIDE KRAFT PAPER JACKET INSIDE AND ALUMINUM JACKET OUTSIDE.
5. CHILLED WATER PIPE AND INSULATION
TYPE L COPPER. PROVIDE WITH 1 1/2" FOAM GLASS
PROVIDE KRAFT PAPER JACKET INSIDE,
6. AIR HANDLING UNIT
AS SPECIFIED IN SCHEDULE OR APPROVED BY OWNER.
7. AIR DISTRIBUTION DEVICES
AS SPECIFIED IN SCHEDULE OR APPROVED BY OWNER. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. PROVIDE MIN R =6
THICK GLASS -FIBER INSULATION BLANKET FOR UNINSULATED SUPPLY
AND RETURN AIR GRILLES.
8. MANUAL VOLUME DAMPERS IN RECTANGULAR DUCTS
GREENHECK MODEL VCD -15 WITH LOCKING QUADRANT OR APPROVED
EQUAL INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
9. HVAC CONTROLS SHALL BE AN EXTENSION OF THE BUILDINGS CONTROL SYSTEM
CONNECT NEW AHU -2 -06 TO CONTROL SYSTEM.
PROVIDE INTERFACE IN NEW EQUIPMENT AND ALL CONTROL WIRING.
D. SUBMITTALS
1. CONTRACTOR SHALL PROVIDE SUBMITTALS TO ENGINEER (VIA ARCHITECT)
FOR ALL NEW EQUIPMENT & MATERIALS FOR FINAL APPROVAL PRIOR TO
ORDERING /PURCHASING.
2. CONTRACTOR SHALL SUBMIT TEST & BALANCE REPORT TO ENGINEER (VIA
ARCHITECT) FOR APPROVAL ONE WEEK PRIOR TO FINAL INSPECTION.
CONTRACTOR SHALL BE AABC OR NEBB CERTIFIED AND ALL REPORTS
SHALL INCLUDE THE AABC OR NEBB CERTIFICATE. ALL AIR FLOWS
SHALL BE WITHIN 10% OF DESIGN. PRESSURE RELATIONSHIPS WILL BE
AS INDICATED DRAWINGS AT A MINIMUM.
4 1 3 1 2
AIR DISTRIBUTION DEVICE SCHEDULE
UNIT
SERVICE
AIR
NECK
SELECTION
NO.
FIRE DAMPER(S)
PA`I`TERN
SIZE
BA 'SED ON
A
CEILING
SUPPLY
ONE WAY
SEE
PLANS
TITUS TDC -AA
B
CEILING
SUPPLY
TWO WAY - 90'
SEE
PLANS
TITUS TDC -AA
C
CEILING
SUPPLY
TWO WAY - 180
SEE
PLANS
TITUS TDC -AA
D
CEILING
SUPPLY
THREE WAY
SEE
PLANS
TITUS TDC -AA
E
CEILING
SUPPLY
FOUR WAY
SEE
PLANS
TITUS TDC -AA
F
RETURN
-
SEE
TITUS 50F
N
m
PLANS
RETURN GRILLE FOR SUPPLY
G
EXHAUST
-
SEE
PLANS
TITUS 50F
NOTES:
1. ALL DEVICES SHALL MATCH CEILING TYPES.
2. FOR TYPES A -E, ALL DIFFUSERS SHALL BE SIZE 18X18 TO KEEP
UNIFORM APPEARANCE WITH NECK SIZE AS SPECIFIED ON DRAWINGS.
3. TYPE F,G - PROVIDE PLENUM BOX FOR DUCT CONNECTION AS REQUIRED
BOX SHALL BE 4" WIDER AND HIGHER THEN DUCT CONNECTION.
-10" ROUND NECK SIZE
4. NOMENCLATURE 10 "� 4 -WAY SUPPLY DIFFUSER
E -200 200 CFM
HVAC DESIGN REQUIRES
M -1
YES
NO
DUCT SMOKE DETECTOR(S)
M -3
NO
FIRE DAMPER(S)
W
0�
NO
SMOKE DAMPER(S)
C�
NO
FIRE RATED ENCLOSURE
r
NO
FIRE RATED ROOF/FLOOR CEILING ASSEMBLY
• M
M
NO
FIRE STOPPING (SEE ARCH.)
Cr
r J
NO
SMOKE CONTROL
CO s..
NO
HVAC
/1 CFM
z CFM
z CFM
0
m
F- FSD
v0
.0
LEGEND
SUPPLY DUCTWORK
RETURN OR EXHAUST
DUCTWORK
SUPPLY DIFFUSER &
AIR QUANTITY
RETURN GRILLE & AIR
QUAN 11 TY
EXHAUST GRILLE & AIR
QUANTITY
THERMOSTAT
DUCT SMOKE DETECTOR
FIRE DAMPER
COMBINATION FIRE &
SMOKE DAMPER
MANUAL VOLUME DAMPER
EXISTING TO REMAIN
NEW
EQUIPMENT TO BE REMOVED
CONNECT OR REMOVE EXISTING
TO THIS POINT
MECHANICAL SHEET INDEX
M -1
HVAC SCHEDULES, NOTES & SPECIFICATIONS- MECHANICAL
M -2
PARTIAL DEMOLITION & RENOVATION PLAN- MECHANICAL
M -3
ICRA DEMOLITION PLAN FOR (INVASIVE PHYSICIAN OFFICE) - MECHANICAL
v
W
0�
ISSUED FOR
PERMIT AND
'ON STRU CT ON
DATE:
02/27/2009
CLIENT CODE /FILE
NUMBER:
PROJECT ID- SUBMISSION
NUMBER:
ROBERT BROWN
ARCHITECT
LICENSE # AR92624
Architecture
Facility Assessments
PI onning
Interior Design
� WA4
ri
L I N E A 5, i n c,
420 LINCOLN ROAD, SUITE 258
MIAMI BEACH, FLORIDA 33139
305 -673 -0004
FAX305- 673 -0080
CIS
0
•0
O
W
(13
=
v
W
0�
I I '
C�
O
r
:
O=
cc; p
•V_
• M
M
W •
CIO
Cr
r J
--+
>O
CO s..
I`
r*-- cc�
Q
-+--�
• (n
Cf) +w��
Q-U>
>
O
C
N
m
�
a
� N
N W
o U H
o w
J
U 5'z 92
W Cf) vi 00
Q n N O
D V
tx Ha`�'•3a�ow
a. aWZzo��.
WdUo EW-wi
rLj
a w 0�:
w Li w
¢Z aZOO
00
Z
�ww
JQ Q J
U Q
Z LJ (/l U Lq
¢_� �
J U W 0
�W Qw
Q� w
❑ ❑
I NO DESCRIPTION DATE
1
JOB NO 40827.00
DRAWN BY CHECKED B
I.Q A.D
DATE SCALE
1 /4" =1' -0"
µ
SHEET No
J t C* !y e
17� �'SR ✓Fj�/) V
L fi M44° 4 ti r ;° N
1 OF 3
(�Ndi ,
5c47 ��
J
E
I