SPRINKLER NOTES
I. ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPLIANCE WITH THE LOCAL FIRE
CODES AND ORDINANCES AND AS PER NFPA 13 2002 EDITION REQUIREMENTS.
2. SPRINKLER SYSTEM SHALL BE INSTALLED BY A STATE CERTIFIED FIRE
PROTECTION CONTRACTOR.
3. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED
FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE
DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE
PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE
AND SIZE PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK
SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR
COORDINATION PRIOR TO CONSTRUCTION.
4. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND
SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL,
MECHANICAL, PLUMBING AND STRUCTURAL SYSTEMS.
5. PRESSURE TEST PIPING AT 200 PSIG FOR A MINIMUM OF TWO HOURS. IF LEAKS
ARE FOUND THEN CONTRACTOR SHALL FIX LEAKS AND TEST AGAIN.
6. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE
WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP
SYSTEMS. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND
SPECIFICATIONS.
7. ALL PENETRATIONS OR OPENINGS FROM REMOVED
PIPES THROUGH EXISTING BUILDING
WALLS AND FLOORS SHALL BE SLEEVED AND /OR
PATCHED TO MATCH ORIGINAL. SEE ARCHITECTURAL
DRAWINGS FOR FINAL FINISHES.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE
TO EXISTING PIPING OR EQUIPMENT DUE TO NEW
CONSTRUCTION AND HE SHALL RESTORE EXISTING
WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE
OWNER.
9. WARRANTY /GUARANTEE
A. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY
OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION
FOR THE PERIOD OF ONE YEAR.
B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING
DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY
THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE
OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE
DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE
ORIGINAL DEFECT OR REPAIR THERETO.
10. THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS
AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE PROTECTION
DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED
FOR APPROVAL.
11. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED.
12. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES
OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE
EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES,
AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK
SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED
BY THE OWNER. ALL SUCH CONNECTIONS AND TIE -INS SHALL BE
COORDINATED THROUGH THE OWNERS PROJECT MANAGER.
I. THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR
WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE
OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT
(48) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE.
ANY AREA AFFECTED BY SHUTDOWN SHALL REQUIRE A 24 HOUR /7 DAYS PER
WEEK FIRE WATCH. 1
i
2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME
CHARGES FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND
WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE
OF THE CONTRACT.
13. CONTRACTOR SHALL COORDINATE WITH FIRE ALARM CONTRACTOR FOR THE
REMOVAL OF FIRE ALARM DEVICES.
14. CONTRACTOR SHALL PATCH WALLS, FLOORS, ROOFING AND CEILINGS TO MATCH
EXISITNG FINISHES FOR DEMOLITION OF FIRE PROTECTION SYSTEMS. COORDINATE
WITH ARCHITECTURAL DRAWINGS.
15. CONTRACTOR SHALL PROVIDE (2) COMPLETE SETS OF AS BUILT DRAWINGS ALONG
WITH ALL CLOSE OUT DOCUMENTS PRIOR TO PROJECT COMPLETION.
FIRE PROTECTION LEGEND
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
F
FIRE LINE OR MAIN
=
FIRE DEPARTMENT VALVE CABINET
—A/S—
AUTOMATIC SPRINKLER MAIN
FP -I, ETC
FIXTURE INDENTIFICATION
D
DRAIN LINE
F.SP.
CONNECTION TO EXISTING
R.P.B.P.
PIPE TURNED UP
0
FIRE EXTINGUISHER
a
PIPE TURNED DOWN
T.S.
FLOW SWITCH
F.S.
BALL VALVE
F.D.V.
CAP ON LINE
��—
CHECK VALVE
E.P.
HYDRAULIC CALCULATION PIPE NODE 1 -100
- --�{+—
UNION IN PIPE
HYDRAULIC CALCULATION SPRINKLER
NODE AC'S, BB'S, CC'S
--►�—
SECTIONAL CONTROL VALVE
FIRE HYDRANT WITH VALVE
- -fie(
REMOVE EXISTING HEAD AND PLUG FITTING
O.S. &Y. GATE OR BUTTERFLY VALVE
W / TAMPER SWITCH.
REMOVE EXISTING HEAD & EXTEND 1' BRANCH LINE
TO NEW HEAD LOCATION
---t
FIRE DEPARTMENT CONNECTION
PIPING TO BE REMOVED
,�-
CHECK VALVE
i---0 -o
SPRINKLER HEAD BELOW DUCT WORK
_xKr—
CONTROL VALVE AND CHECK VALVE WITH
FLOW AND TAMPER SWITCHES
FIRE PROTECTION ABBREVIATIONS
F.H.C.
FIRE HOSE CABINET
O.S. & Y.
OUTSIDE STEM AND YOKE
F.E.
FIRE EXTINGUISHER
S.C.V.
SECTIONAL CONTROL VALVE
A/S
AUTOMATIC SPRINKLER
F.H.
FIRE HYDRANT
F.SP.
FIRE STANDPIPE
R.P.B.P.
REDUCED PRESSURE BACKFLOW PREVENTER
RCV
RISER CONTROL VALVE
A.F.F.
ABOVE FINISHED FLOOR
T.S.
TAMPER SWITCH
F.S.
FLOW SWITCH
F.D.V.
FIRE DEPARTMENT VALVE
N.O.
NORMALLY OPEN
E.P.
ELECTRICAL PANEL
w
INFECTION CONTROL MEASURES--. -
I. CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL
RISK ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHPt- L- RCKIEW -
THE REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORD6Nr,F- WITH .
THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS -OF -"
THE CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO-THE p "
PHASING PLAN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED
WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER
THE SUPERVISION OF THE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA
COMMITTEE OFFICER.
2. TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL
ENDEAVOR TO MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS
SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE, AND ELSEWHtRE
IN THE FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRAREPORT WILL REQUIRE
MEASURES TO THIS EFFECT INCLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS
AND PROVISION OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE RELATIVE
TO OTHER AREAS OF THE FACILITY.
3.IN ADDITION TO THE MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE
CONTRACTOR AT A MINIMUM SHALL PROVIDE EQUIPMENTAND COMPONENTS
NECESSARY TO CREATE A NEGATIVE PRESSURE IN THE CONSTRUCTION WORK ZONE
RELATIVE TO ADJACENT AREA. EXISTING HVAC SYSTEMS AND COMPONENTS SHALL
NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY APPROVED BY THE OWNER'S
INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL
BE DONE IN ACCORDANCE WITH THE ICRA REQUIREMENTS AND AT A MINIMUM AS
FOLLOWS:
VERIFY ALL EXISTING FIRE PROTECTION WHICH PASSES THROUGH THE
CONSTRUCTION ZONE, AND IS TO REMAIN, IS SEALED AND PROTECTED
DURING THE CONSTRUCTION DURATION.
AIR REMOVED FROM THE CONSTUCTION ZONE SHALL BE FILTERED AND /OR
DISCHARGED AS DIRECTED BY THE ICRA REPORT.
PRESENT THE NEGATIVE AIR PRESSURE PLAN TO THE OWNER FOR APPROVAL
BY THE INFECTION CONTROL COMMITTEE.
PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING
MAINTAINED IN ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE
DOCUMENTATION TO THE OWNER AS REQUIRED.
4. COORDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER,
AND VERIFY BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE
RELATIONSHIPS WILL NOT BE ADVERSELY AFFECTED.
FIRE PROTECTION DRAWING INDEX
NO. SHEET TITLE
FPO.01
FIRE PROTECTION LEGEND, SCHEDULES & DRAWING INDEX
FPI.01
FIRST FLOOR - DEMOLITION - FIRE PROTECTION
FPI.02
SECOND FLOOR - DEMOLITION - FIRE PROTECTION
i
i I
^600 West Hillsboro, Suite 300
Po Dearfield Beach, FL 33441
h M (954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm certification - EB- 0000857
Alfred EsqutM PE - 45863
Erik S. Wafter PE - 63429
John E. Moulder PE - 33200
Michael A. Steward PE - 65701
SSR JOB # 0932026.0
<Z
CC W
z w
WV
U
T
J w Cr?
Q CL
w<
co �
0
M V-
O w
T
CI)
20 o=
Q CC) =)
-0 o
�z C0
F- 0
Z) 0
0(.)
�V -
k d ✓r
y� G
w
S i
r;
DRAWN
CHECKED
DATE 12/04/09
REVISED
SHEET NO.
FIRE PROTECTION
LEGEND, SCHEDULES &
DRAWING INDEX