Loading...
09-1110-0154,- W W w Q 0 vaL-rF- ni rirAL, HOSE CONNECTIONS BOTTOM CONCRETE LINK —SEAL NT WATERTIGHT 1DOWN / FIRE JNECTION TO 10'CWE kBOVE AL SIN NN IRE -TION BOTTOM CONCRETE LINK -SEAL :NT SEAL. f. f; f FIRST FLOOR NEW WORK - HVAC �N KEYED NOTES: _ ry O CONNECT TO EXISTING 20 PSI CONTROL AIR FROM EXISTING 10' CWS MOTOR n ry ACTUATED CONTROL VALVE TO 101 CWS MOTOR ACTUATED CONTROL VALVF,:-. R ry SEQUENCE 10' CWS MOTOR ACTUATED CONTROL VALVE WITH EXISTING 10 CWS n MOTOR ACTUATED CONTROL VALVE FOR RESPECTIVE COOLING TOWER. - - -- _ -- -- - CONTRACTOR SHALL THOROUGHLY CLEAN OUT EXISTING SUMPS OF ALL DEBRIS, SLUDGE AND DIRT. THE EXISTING CONDENSER WATER SYSTEM SHALL BE FLUSHED OUT AND RETREATED BY AQUA-CHEM. COORDINATE ALL FLUSHING AND CLEAN OUT WORK WITH AQUA -CHEM. KEEP SYSTEM DOWN TIME TO AN ABSOLUTE MINIMUM. O REPLACE EXISTING CWS BUTTERFLY VALVES, MANUAL VALVES, PROVIDE HAND WHEEL OPRATOR. VERIFY VALVE SIZES. Q ADD ALTERNATE No.I REPLACE EXISTING BUTTERFLY VALVES: A) CHILLER NO. I CWR, MANUAL VALVE, PROVIDE HAND WHEEL OPERATOR. B) CONDENSER WATER PUMP CWP -I, SUCTION AND DISCHARGE, MANUAL VALVE, HAND WHEEL OPERATOR. C) VERIFY VALVE SIZES. ADD ALTERNATE No.2 REPLACE EXISTING BUTTERFLY VALVES: A) CHILLER NO. 2 CWR, MANUAL AND PNEUMATIC VALVES, PROVIDE HAND WHEEL ON MANUAL VALVE. REUSE AND RECONNECT EXISTING PNEUMATIC ACTUATOR ON MOTORIZED VALVE. B) CONDENSER WATER PUMP CWP -2, DISCHARGE MANUAL VALVE, HAND WHEEL OPERATOR. C) VERIFY VALVE SIZES. NOTES: I. CORDINATE ALL SHUTDOWNS WITH HOSPITAL FACILITIES DEPARTMENT IN WRITING. ALL SHUTDOWNS SHALL BE BID AS PREMIUM TIME, CONTINUOUS SHIFTS TO MINIMIZE EACH SHUT DOWN. 2. TOTAL BUTTERFLY VALVE REPLACEMENT COUNT IS EIGHT INCLUDING ADD ALTERNATES No. I AND 2. CONFIRM ALL REPLACEMENT VALVES WITH FACILITIES DEPARTMENT. VALVE REPLACEMENT SHALL CONSIST OF LUG BODY DISC WAFER, OPERATOR, GASKETS AND BOLTING HARDWARE. REUSE EXISTING FLANGES. 3. ALL MANUAL VALVES NORMALLY OPEN UNLESS INDICATED OTHERWISE. SPLIT RING TYPE HANGER (SEE SPEC'S) 4NGER 0111111 W-11 SHEET METAL SADDLE CLEVIS TYPE PIPE HANGER SEE SPEC'S (PIPE HANGER SUPPORTS 3UCKLE QUIRED) CONSTRUCTION LEGEND DESCRIPTION rNE1W11 EXISTING TO REMAIN NEW CONSTRUCTION CONNECT TO EXIST.' ` THIS ��POINT mi h ei'Tnc 600 -West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certificirtion - EB-0000857 Alfred Esquivel PE - 45863 Erik S. Walter PE_ John E. Moulder PE - 332W Michael A. Steward PE - 65701 SSR JOB # 0932026.0 Q z W ZW Wv C") U T J W M <C CL w Q W F� IL cr C!3 O Cc CM LL CJw 0 j > Q ° F— o x co Q =) - 0 O z cn E- 0 :Do 0(.) DRAWN CHECKED DATE 12/04/09 REVISED SHEET N0. FIRST FLOOR - NEW WORK - HVAC M2.01