HVAC GENERAL NOTES
I.
HVAC DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND REPRESENT
Ii.
CONTRACTOR SHALL SUBMIT A COMPLETE LIST OF EQUIPMENT AND ITEMS TO
DUCT SMOKE DETECTORIS)
EXISTING CONDITIONS BASED ON DRAWINGS AND SITE OBSERVATIONS.
X
BE REMOVED TO THE OWNER. ALL ITEMS THAT THE OWNER WISHES TO RETAIN
IQ= HAND
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL ACTUAL
SMOKE DAMPERIS)
SHALL BE TURNED OVER TO OWNER.AND THE REMAINDER SHALL BE REMOVED
X
CONDITIONS INCLUDING PIPING LOCATIONS AND SIZES.
SECOND FLOOR - NEW WORK - HVAC
FROM THE SITE AND DISPOSED OF IN A PROPER MANNER BY CONTRACTOR.
2.
DUE TO DRAWINGS BEING DIAGRAMMATICAL IN NATURE RISERS & DROPS
X
CONTRACTOR TO GIVE OWNER A LIST OF SLAVAGABLE ITEMS.
II =PROVIDE EXTERNAL GEAR DRIVE
ARE NOT SHOWN - CONTRACTOR SHALL INCLUDE THESE IN THE BID -
SMOKE CONTROL
g=
3 = LADDER Q
X
WHERE NOT POSSIBLE ALL RISERS & DROPS SHALL BE CONSTRUCTED USING
12.
ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION ARE NOT SHOWN ON
45 DEGREE OR LONG RADIUS ELBOWS.
N0.
THE DRAWINGS. REFER TO EQUIPMENT INSTALLATION INSTRUCTIONS FOR
3.
PROVIDE AND INSTALL NECESSARY PIPING
ADDITIONAL REQUIREMENTS, INCLUDING CONNECTION LOCATION AND SIZES.
INCREASERS /REDUCERS AS REQUIRED FOR EQUIPMENT CONNECTIONS.
13.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PERFORM ALL WORK
E.W.B.
CONSULT MANUFACTURER'S DATA FOR ACTUAL PIPING
BASIN
TYPE
OPERATING
WEIGHT
CONNECTIONS SIZES, INCLUDING, BUT NOT LIMITED TO THOSE SHOWN.
STARTER
NECESSARY TO PREPARE THE STRUCTURE FOR THE INSTALLATION AND /OR
REMARKS
N0.
H.P.
DEMOLITION WORK OF THE MECHANICAL SYSTEMS. ALL HOLES, OPENINGS
4.
SCHEDULE NEW CONSTRUCTION WORK WITH THE OWNER WELL IN
LOCATION
AND ANY DAMAGED MATERIALS OR SURFACES SHALL BE REPAIRED
TYPE
ADVANCE. CONSTRUCTION WORK AND DEMOLITION SHALL BE PERFORMED
REFRIG
AT SUCH TIMES AND UNDER SUCH CONDITIONS AS SUITS THE OWNER.
AND FINISHED TO MATCH EXISTING.
PROVIDE OWNER 2 WEEK NOTICE OF PROPOSED PLANT SHUTDOWNS.
14.
ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241 AND THE REQUIREMENTS
5.
ALL FINISHES AND SURFACES TO REMAIN WHICH ARE DAMAGED DURING
CONSTRUCTION WORK SHALL BE REPAIRED OR REPLACED TO THE
OF THE OWNER.
SATISFACTION OF THE OWNER AT NO ADDITIONAL COST TO THE OWNER.
15.
IN ORDER TO MAINTAIN THE EXISTING ROOF WARRANTY, ALL ROOFING WORK
6.
SEAL ALL WALL, ROOF, AND FLOOR PENETRATIONS AIR TIGHT AT PIPE
3600
(CUTTING AND REPAIRS) SHALL BE PERFORMED BY THE OWNER'S ROOF WARRANTY
85
AND CONDUIT PENETRATIONS. ALL PENETRATIONS THRU
14'x24'x25'
VENDOR (PAID FOR BY THIS CONTRACTOR).
51,500 LBS
FIRE RATED WALLS TO BE SEALED AS PER UL DETAILS.
125
1800
7.
DO NOT BLOCK SERVICE SPACE ON EQUIPMENT WITH
16.
EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON
TffC
PIPING. (FLANGED OR REMOVABLE SECTIONS MAY BE
(1) (2)
AVAILABLE RECORD DRAWINGS. THIS INFORMATION IS ONLY
USED IN SOME INSTANCES WHERE TIGHT CLEARANCES EXISTS).
PARTIALLY VERIFIED. THE CONTRACTOR IS RESPONSIBLE
TO FIELD VERIFY AND INVESTIGATE ALL CONDITIONS THAT
BAC 31301CN
AFFECTS THE WORK PRIOR TO SUBMITTING THE BID.
8.
NO PIPING OR CONDUIT SHALL BE INSTALLED UNTIL IT IS
COORDINATED WITH ALL OTHER TRADES AFFECTED. PROVIDE ALL
17.
PROVIDE AIR VENTS AT ALL HIGH POINTS IN PIPING SYSTEMS
OFFSETS REQUIRED TO AVOID INTERFERENCES WITH OTHER TRADES;
18.
PROVIDE PROVIDE DRAIN VALVES AT ALL LOW POINTS IN PIPING
EXISTING CONDITIONS AND WITH THE STRUCTURE, INCLUDING, BUT NOT
LIMITED T0, THOSE SHOWN.
19.
PROVIDE VALVE TAGS ON ALL NEW VALVES THAT MATCHES THE
FACILITY'S STANDARD. TAGS SHALL BE NUMBERED SEQUENTIALLY
AND PROVIDE DRAWINGS AND SCHEDULES THAT INDICATES EXACT
9.
FIELD VERIFY TO ELECTRICAL, PLUMBING, FIRE PROTECTION, ARCHITECTURAL AND
LOCATION, SIZE AND SERVICE OF VALVES.
STRUCTURAL FOR COORDINATION WITH THESE DRAWINGS.
20.
PROVIDE MANUFACTURERS CERTIFIED DATA ON ALL EXTERIOR
10.
REFER TO DETAIL SHEETS AND SPECIFICATIONS FOR ADDITIONAL INSTALLATION
MOUNTED EQUIPMENT DURING SUBMITTAL PHASE, WHICH INDICATES
REQUIREMENTS.
THAT THE EQUIPMENT CAN MEET THE FLORIDA BUILDING CODE WIND
LOAD.
21.
PROVIDE CLEAR ACCESS TO VALVES.
HAZARDOUS MATERIAL NOTES
1. PORTIONS OF THE EXISTING SYSTEM CONTAIN HAZARDOUS MATERIAL.
COORDINATE WITH THE OWNER TO DETERMINE THE LOCATION AND TYPES OF
HAZARDOUS MATERIALS.
2. THE OWNER IS RESPONSIBLE FOR THE IDENTIFICATION. CONTRACTOR IS RESPONSIBLE FOR
REMOVAL AND DISPOSAL OF HAZARDOUS MATERIAL AND IS TO BE INCLUDED AS PART
OF THE WORK OF THIS CONTRACT. DISPOSAL SHALL BE IN ACCORDANCE WITH LOCAL,
STATE, AND FEDERAL REGULATIONS FOR EACH IDENTIFIED HAZARDOUS MATERIAL.
3. IF ANY MATERIAL APPEARS TO CONTAIN HAZARDOUS MATERIAL AND WAS NOT PREVIOUSLY
IDENTIFIED. THE CONTRACTOR IS TO INFORM THE OWNER TO RECEIVE INSTRUCTIONS ON HOW
TO PROCEED.
HVAC DESIGN REQUIRES
SHEET
NUMBER
YES
NO
DUCT SMOKE DETECTORIS)
COOLING.TOW
X
FIRE DAMPER(S) (
IQ= HAND
X
SMOKE DAMPERIS)
M2.01
X
FIRE RATED ENCLOSURE
SECOND FLOOR - NEW WORK - HVAC
X
FIRE RATED ROOF/FLOOR CEILING ASSEMBLY
DEPRESSED SUMP OUTLET
X
FIRE STOPPING (SEE ARCH)
II =PROVIDE EXTERNAL GEAR DRIVE
X
SMOKE CONTROL
g=
3 = LADDER Q
X
MECHANICAL DEMOLITION NOTES
I. FOR EQUIPMENT AND SYSTEMS TO REMAIN IT SHALL BE THE CONTRACTOR'S - - - _ -----
RESPONSIBILITY TO VERIFY THE CONDITION OF, EXACT SIZES AND LOCATOONt -OF
EXISTING PIPING BEFORE DEMOLITION WORK IS BEGUN. REPORT ANY
DISCREPANCIES BETWEEN PLANS AND ACTUALLY FIELD CONDITIONS TO THE
OWNER AND ENGINEER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK.
2. REMOVE THE INDICATED HVAC ITEMS AS SHOWN ON PLANS, THIS INCLUDES
ALL HANGERS AND RELATED MATERIAL AS DIRECTED THIS MATERIAL SHALL
BE REMOVED FROM THE SITE OR TURNED OVER TO THE OWNER (AS DIRECTED BY
THE OWNER).
3. PATCH AND MATCH OPENINGS IN WALLS TO MAINTAIN THE INTEGRITY OF THE WAIL
WHERE PIPING, ETC. HAVE BEEN REMOVED. (MAINTAIN THE EXITING RATINGS)
4. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATE ROUTING
OF NEW PIPING BEFORE FABRICATION BEGINS AS RISES AND DROPS MAY BE
NECESSARY DUE TO EXISTING FIELD CONDITIONS.
HVAC LEGEND
PIPING
CWS CONDENSER WATER � BUTTERFLY VALVE
SUPPLY
CyR CONDENSER WATER
RETURN � MOTOR ACTUAtE0
D DRAIN LINE BUTTERFLY VALVE
No REDUCER -���- SHUT -OFF VALVE
CONDENSER WATER
- CWE EQUALIZER CONTROL VALVE
STRAINER
STRAINER &SLOWDOWN
��- VALVE
- ���- -- PLUG COCK
�I ( COMPANION FLANGE
UNION
CHECK VALVE
i
GAUGE &GAUGE COCK
�- THERMOMETER
NOTE I:
DISCONNECT AND RECONNECT EXISTING SIEMENS CONTROLS TO TOWER 2 VARIABLE FREQUENCY DRIVE. REFER TO ELECTRICAL DRAWINGS EI.01 AND E2.01.
DRAWING INDEX
SHEET
NUMBER
SHEET TITLE
MO.00
COVER SHEET
COOLING.TOW
ER
IQ= HAND
RAIL 4Q
= 8' FLOW CONTROL VALVES
M2.01
7Q =INVERTER DUTY HI EFF. MOTOR
C =TOWER SHALL BE ALL STANLESS STEEL CONSTRUCTION
SECOND FLOOR - NEW WORK - HVAC
BASIN
COVERS SO=
DEPRESSED SUMP OUTLET
W/ REMOVABLE SCREEN
Q= BIRDSCREEN ON INTAKE LOUVERS
II =PROVIDE EXTERNAL GEAR DRIVE
(I) = COOLING TOWER TO BE CONSTRUCTED OVER EXISTING CONCRETE BASIN. REFER TO STRUCTURAL DWGS FOR SUPPORT REQUIREMENTS
g=
3 = LADDER Q
=MAKE-UP WATER VALVE
Q= 14'SUMP OUTLET W/ 14'PVC DRAIN
LINE INTO EXT'G SUMP
(2) FM APPROVAL
N0.
TYPE
NOM. CAP.
111
MANUFACTURER
& MODEL N0.
GPM
E.W.T.
L.W.T.
E.W.B.
APPROXIMATE SIZE
�L X W X H)
BASIN
TYPE
OPERATING
WEIGHT
STARTER
ACCESSORIES
REMARKS
N0.
H.P.
RPM
ELEC.
TYPE
LOCATION
Rh
TYPE
REFRIG
TOWER 2
INDUCED DRAFT
1200
MARLEY OR NC8414YANI
3600
95
85
19
14'x24'x25'
STSIN�LELSS
51,500 LBS
I
125
1800
480/3/60
VFD
ELECTRICAL ROOM
DIV.16
TffC
OO OO OO 4 5 6 7 COQ @
(1) (2)
BAC 31301CN
NOTE I:
DISCONNECT AND RECONNECT EXISTING SIEMENS CONTROLS TO TOWER 2 VARIABLE FREQUENCY DRIVE. REFER TO ELECTRICAL DRAWINGS EI.01 AND E2.01.
DRAWING INDEX
SHEET
NUMBER
SHEET TITLE
MO.00
COVER SHEET
MO.01
MECHANICAL LEGENDS AND SCHEDULES
M1.01
FIRST FLOOR - DEMOLITION - HVAC
M1.02
SECOND FLOOR - DEMOLITION - HVAC
M2.01
FIRST FLOOR - NEW WORK - HVAC
M2.02
SECOND FLOOR - NEW WORK - HVAC
mi h
ep Inan
el nc.
X600 -West Hillsboro, Suite 300
Z�eer5eld Beach, FL 33441
(954) 421 -1260
FAX; (954) 421 -1466
www.ssr- inc.com
Firm Certification - E84X000857
Alfred Esquival PE - 45663
Erik S. Wafter PE - 63929
John E. Moulder PE - 33200
Michael A. Steward PE - 6=1
SSR JOB # 0932026.0
..J
Z__
W
Z W
W
U
T
J �jM
<C CL W Q
F- Lv Ct o
CD 0
M V-
OW -
'17 3:
Q
0 °
F- o F-
Q
0
z Cl)
J
F- p
0
0(.)
to
ol
gw
t
Uj
f c�
DRAWN
CHECKED
DATE 12/04/09
REVISED
SHEET N0.
MECHANICAL
LEGENDS AND
SCHEDULES