08-957-030ELECTRICAL SPECIFICATIONS 16010 - BASIC ELECTRICAL. REQUIREMENTS A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO: 1. STATE OF FLORIDA Z CITY OF MIAMI 3. LIFE SAFETY CODE - NFPA 101 (2003) 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 56 NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. NATIONAL ELECTRICAL CODE - NFPA 70 (2005) 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) 9. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 10. INTERNATIONAL. POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 11. NATIONAL ELECTRICAL SAFETY CODE (NBS Handbook 81) 12. REQUIREMENTS OF LOCAL UTILITY COMPANY 13. FLORIDA ADMINISTRATIVE CODE 59A -3, (March 2003) 14. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2002) 15. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2002) 16. THE STATE FIRE PREVENTION CODE; 4A60 (2001) 17. BUILDING CODE FLORIDA BUILDING CODE (2004) WITH 2005 AND 2006 REVISIONS 18. AIA GUIDELINES (2006) 19. NFPA 110 (2002) 20. FIE MARSHALL'S RULE 4A3.012 F.A.C. adapted January 1. 2001 B. CODES AND STANDARDS REFERRED TO ARE MINIMUM. WHERE THE REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS GOVERN. C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED BY THE REGULATORY AUTHORITIES. FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS. INSPECTIONS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR. THE PRO -RATA COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL BE PAD FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS CONTRACT. D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE E ALL FISTING SYSTEMS, EQUIPMENT OR MATERIAL CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS. SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. F. EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L LABEL WHERE APPUCABLE; UNLESS NOTED OTHERWISE ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER. G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES. H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS. IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE/SHE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR 'OR EQUAL' ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS, ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL. PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER. J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND /OR MAINTENANCE RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERATION OR MAINTENANCE IS NOT RESTRICTED. K. INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC 110-26 AND 110 -34. L SHOP DRAWING SUBMITTALS 1. CONTRACTOR SHALL PREPARE AND SUBMIT SEVEN COPES OF ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND DEVICES INDICATED IN THE SCOPE OF WORK. 2. COMPLETE UST OF MATERIALS TO BE FURNISHED UNDER EACH SPECIFIC SECTION. 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE SPECIFICATION COMPLIANCE. 4. CATALOG SHEETS, CLEARLY MARKED FOR IDENTIFICATION OF ITEMS TO BE PROVIDED, INCLUDING DISCONNECT SWITCHES, BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY PREPARED SHOP DRAWINGS. 5. ALL SHOP DRAWING CUT SHEET'S SHALL CLEARLY IDENTIFY THE SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING MANUFACTURER. GENERIC CUT SHEETS, INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED WITHOUT IDENTIFYING THE SPECIFIC PRODUCT PROVIDED. WILL BE AUTOMATICALLY REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED DIMENSIONED LAYOUT DRAWING FOR ALL URGE ELECTRICAL EQUIPMENT AND ELECTRICAL ROOMS WHERE NEW EQUIPMENT IS BEING INSTALLED. M. EACH CONDUIT, REGARDLESS OF MATERIAL, WHICH PASSES THROUGH A CONCRETE SLAB, MASONRY WALL. OR ROOF OR PORTION OF THE BUILDING STRUCTURE SHALL BE FREE FROM THE STRUCTURE AND SHALL PASS THIROUGH A SLEEVE. ALL SLEEVES SHALL BE CONSTRUCTED FROM ELECTRIC- METALLIC TUBING OR EQUIVALENT WEIGHT GALVANIZED STEEL TUBING AND SHALL BE FLUSH ON BOTH SIDES OF THE SURFACE PEIETRATED, U.N.O. ALL SLEEVES PENETRATING THE ROOF AREAS SHALL EXTEND A MINIMUM 10 INCHES ABOVE THE ROOF WITH APPROVED WEATHERPROOF COUNTERFLASHING ATTACHED TO THE CONDUIT ABOVE THE ROOF. ALL SLEEVES PENETRATING FLOORS SHALL EXPEND A MINIMUM OF 6 INCHES A.F.F. THE SLEEVES SHALL BE SIZED TO ALLOW FREE PASSAGE OF THE CONDUIT TO BE INSERTED. SLEEVES PASSING THROUGH WALLS OR FLOORS ON OR BELOW GRADE OR IN MOIST AREAS SHALL BE CONSTRUCTED OF GALVANIZED RIGID STEEL AND SHALL BE DESIGNED WITH A SUITABLE RANGE INT HE CENTER TO FORM A WATERPROOF PASSAGE AFTER THE CONDUIT HAS BEEN INSTALLED IN SLEEVES, THE VOID SPACE AROUND THE CONDUIT SHALL BE CAULKED AND FILLED WITH AN ASPHALT -BASE COMPOUND TO INSURE A WATERPROOF PENETRATION. JUTE TWINE CAULKING SHALL NOT BE USED. N. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWING AT THE SITE, NOTING DALY ALL CHANGES MADE IN THESE DRAWING N CONNECTION WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW AND UNCOVERED FISTING UTILITIES TURN OVER A CLEAN, NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING 'AS INSTALLED' WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES. DATE EACH SHEET AND LABEL 'AS- BULTS' IN THE REVISION BLOCK ON THE DRAWING. CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF 'AS- BUILT' BLUEUNE PRINTS. 0. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPUCATF. PREPARED IN A NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE. Z APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES). 3. COPIES OF APPROVED SHOP DRAWINGS 4. OPERATING INSTRUCTIONS FOR ALL ELECTRICAL. SYSTEM EQUIPMENT. OPERATING INSTRUCTIONS SHALL ALSO INCLUDE RECOMMENDED MAINTENANCE PROCEDURES. 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS. 6. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING CONSTRUCTION. 7. REPAIR PARTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL SUPPLIER OR AGENT. P. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS BEFORE FINAL INSPECTION. 16020 - ELECTRICAL WORK IN EXISTING FACILITIES A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO EXISTING FACILITIES FROM EXISTING DOCUMENTS, MEASUREMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS„ AND OTHER OBSERVATIONS AT THE SITE. B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE CONSTRUCTION PERIOD, CARRY OUT THE WORK UNDER THIS DIVISION IN SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS G. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK N EXISTING FACILITIES. REINSTALL AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH ENSIING ADJACENT SURFACED UPON COMPLETION OF THE WORK. D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, N FULL COMPLIANCE WITH THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. G DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER. REPAIR AND RESTCRE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED DURING DISMANTLING OR REASSEMBLY OPERATIONS NEW MATERIALS AND ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. REMOVE CAREFULLY, IN REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE TO BE RELOCATED. PROTECT ITEMS UNTIL RELOCATION IS COMPLETE CLEAN AND REPAIR ITEMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, FITTING AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE SPECIFICATIONS, UTILIZING SKILLED WORKERS L RELOCATING DEVICES REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS. WIRE, CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED N E>aSTING- TO-BE- REMOVED CONSTRUCTION. 16084 - DROUGH- PENETRATION FlRESTOPPING FOR ELECTI)ICAL SYSTEMS A. ONLY TESTED FlRESTOP SYSTEMS SHALL BE USED IN SPECIFIC LOCATIONS AS FOLLOWS- 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WALLS AND PARTITIONS), HORIZONTAL BARRIERS (FLOOR /(FLUNG ASSEMBLIES), AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS. 2. COMPLETION OF FIRESTOP INSTALLATIONS TO MAINTAIN THE RATING INTEGRITY OF THE BARRIER PENETRATED. B. INSTALLER SHALL. CONSULT THE STRUCTURAL ENGINEER PRIOR TO PENETRATING ANY LOAD BEARING ASSEMBLY. C. ACCEPTABLE MANUFACTURERS: HILTI INC., TREMOO SEALANTS & COATINGS, 3M FIRE PROTECTION PRODUCTS, JOHN- MANVILLE FlRETDMP, OR OTHER MANUFACTURERS LISTED IN THE U.L FIRE RESISTANCE DIRECTORY - VOLUME 2. 16110 - SYSTEMS OF RACEWAYS A. CONDUIT I. RIGID STEEL CONDUIT (GRC - GALVANIZED RIGID CONDUIT): CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, CONFORMING WITH FED. SPEC. WNW- C -581E ANSI 080.1 AND UL 6. 2. INTERMEDIATE METAL CONDUIT (IMC): CONSTRUCTED OF ZINC COATED STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. WW-C- 581 -E, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. 3• ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE STEEL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO FED. SPEC. WW-C- 583 -A, ANSI C80-3, AND UL 797. 4. UQUIDTIGHT FLEXIBLE CONDUIT. FLEXIBLE METAL CONDUIT AS SPECIFIED HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY -APPUED NEOPRENE JACKET. LIQUID TIGHT FLXIBLE CONDUIT SHALL BE UL LISTED, EQUIVALENT TO ANACONDA 'SEALTITE7, TYPE UA. 5. CONTRACTOR SHALL SUPPLY TRENCH DUCT AS REQUIRED IN RADIOLOGY ROOMS IN ACCORDANCE WITH THE RADIOLOGY VENDOR'S DRAWINGS. DUCT SHALL BE AS REQUIRED BY VENDOR WITH A MINIMUM 11,C THICK REMOVABLE COVER PLATES. DUCT SHALL HAVE A SINGLE REVERSIBLE ALUMINUM TRIM WITH A SURFACE EXPOSURE THROUGH THE FLOOR TO RECEIVE FLOOR COVERING TRENCH DUCT SHALL BE MANUFACTURED BY SQUARE D. WALKER, OR GENERA. ELECTRIC 6. INSTALLATION OF BUILDING CONDUIT a. ALL INTERIOR RACEWAYS SHALL BE EMT. RACEWAYS IN DAMP OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE GRC OR INC. b. CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY OR EXCESSIVE STRAN, SHALL BE SECURED AT CABINETS AND BOXES WITH GALVANIZED LOCKNUTS, BOTH INSIDE AND OUTSIDE; AND SHALL HAVE APPROPRIATE BUSHINGS INSIDE BUSHING SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS. c. USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LIQUID TIGHT FLE>aBLE METAL CONDUIT, WITH APPROPRIATE CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS, AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS d. GROUND METALLIC CONDUITS AS REQUIRED BY NEC. e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN PULLS. IN AREAS WHERE THERE ARE NO SUSPENDED CIUNGS, RUN ALL CONDUITS PARAUn/PERPENDICULAR TO BUILDING SURFACE. f. IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN ADJACENT SWITCHES IN THE BOX SO THAT TWO DIFFERENT PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. g. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, PENETRATIONS, OR OTHER PARTITIONS, CAREFULLY FILL ANY SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TO PREVENT PASSAGE OF AIR, WATER, SMOKE. AND FUMES. FLUNG MATERIAL SHALL BE A UL LISTED, INTUMESCENT SEALING HAVING FIRE/SMOKE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL. PENETRATED. . ;, ..' I h• CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT 1' BE SMALLER THAN 3/4 INCH FOR FEEDERS,, MULTIPLE , BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF 1 CONDUCTORS LARGER THAN NO. 12. INDIVIDUAL BRANCH CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE ACCEPTABLE IN 3/4' CONDUIT, I.E. 2/12, 1#126, 3 /eC. 7. INSTALLATION OF UNDERGROUND CONDUIT a. INSTALL UNDERGROUND FEEDER CONDUCTORS IN RIGID NONMETALLIC CONDUIT (PVC), U.N.O. INSTALL. AT LEAST 30 INCHES BELOW FINISHED GRADE U.N.O. ON A BED OF SAND - BEFORE CONTINUING BACKFILL b. WHERE CONDUIT ENTERS INTO PULL OR JUNCTION BOXES AND AT ALL BENDS, CHANGE FROM PVC TO RIGID GALVANIZED STEEL CONDUIT BELOW GRADE c. PROVIDE A PULL BOX OF APPROPRIATE SIZE EVERY 500 FEET OF STRAIGHT RUN AND AT EVERY 90 DEGREE BEND. B. COUPLINGS AND TERMINATORS 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT FACTORY -MADE THREADED COUPLINGS OF SAME MATERIAL AS THE CONDUIT. 2. FOR ELECTRICAL METALLIC TUBING, USE STEEL COMPRESSION COUPLINGS AND NYLON INSULATED GROUNDING BUSHINGS. 3. FOR FLEXIBLE METAL CONDUIT. COUPLINGS AT CONNECTIONS BETWEEN FLEXIBLE CONDUIT AND EMT, AND NYLON INSULATED THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS WITH NYLON INSULATED TH IROAT AND L.00KNUTS AT ALL BOXES AND CABINET TERMINATIONS OR NON - INSULATED BOX CONNECTOR. LOCKNUT AND NYLON - INSULATED GROUNDING BUSHING ON ALL TUBING WHERE GROUNDING BUSHINGS ARE REQUIRED. C. JUNCTION AND PULL BOXES 1. SIZE BOXES N ACCORDANCE WITH THE REQUIREMENTS OF THE NEC. BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES SQUARE BY 1 -1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL TIMES. SET BOXES ON CONCEALED CONDUITS WITH COVERS FLUSH WITH THE FINISHED WALL OR CEILING LINE PROVIDE JUNCTION AND PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND CONDUCTORS NOTED, WHERE SHOWN AND WHERE NECESSARY FOR THE INSTALLATION AND PULLING OF CABLES AND WIRES. INSTALL COVERS ON JUNCTION BOXES AND CONOULETS AFTER WIRING AND CONNECTIONS ARE COMPLETED. 2. ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW VOLTAGE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE YELLOW (LIFE SAFETY BRANCH), ORANGE (CRITICAL BRANCH), GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BROWN (DATA/TELEPHONE). 3. INSTALLATION OF PULL AND JUNCTION BOXES a. FASTEN ALL BOXES SECURELY TO THE BUILDING CONSTRUCTION, INDEPENDENT OF CONDUIT SYSTEMS. b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE, SET BOXES FLUSH WITH FINISHED SURFACES FOR ACCESS, AND PROVIDE OVERLAPPING COVEIRS. C. ALL WIRING DEVICES FACEPLAIES SHALL BE ENGRAVED WITH THE PANUBOARD DESIGNATION AND CIRCUIT NUMBER SERVING THE OUTLET. LABEL TAPE WILL NOT BE ACCEPTABLE D. OUTLET BOXES 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES AND TYPES REQUIRED FOR THE APPLICATION. OUTLET BOXES SHALL BE SHEET STEEL, NO LIGHTER THAN 14 GAUGE, GALVANIZED AFTER FABRICATION. SET BOX SO FAO: OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. a. FOR LIGHTING FIXTURE OUTLETS: 4 INCH SQUARE BY 1- 1/2 INCHES DEEP WITH RAISED FIXTURE RING b. FOR WALL SWITCHES, RECEPTACLES, AND COMMUNICATION USE 4 INCH SQUARE, BY 1 -1/2 INCHES DEEP. USE BOXES WITH PLASTER RNG IN ALL PLASTERED WALLS WHERE WALL THICKNESS PERMITS. USE BOXES LESS THAN 1 -1/2 INCH DEEP ONLY N LOCATIONS WHERE DEEP BOXES CANNOT BE ACCOMMODATED BY CONSTRUCTION. E PULL CORDS 1. PROVIDE A NYLON POLYETHYLENE CORD, WITH A TENSILE STRENGTH OF NOT LESS THAN 200 POUNDS, IN EACH EMPTY CONDUIT TO FACILITATE THE FUTURE INSTALLATION OF CONDUCTORS INCORPORATE PLASTIC TAG FOR IDENTIFICATION. F. SEGREGATION OF WIRING SYSTEMS 1. SEGREGATION OF WIRING SYSTEMS SHALL NOT BE COMPROMISED BY THE USE OF COMMON PULLBOXE% WIREWAYS, CABINETS OR ANY OTHER TYPE OF ENCLOSURE 2. THE RACEWAY SYSTEM FOR EACH FEEDER SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. 3. THE RACEWAY SYSTEM FOR THE BRANCH CIRCUITS OF EACH PANELBOARD SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. 16120 - SYSTEM OF CONDUCTORS A. CONDUCTORS SHALL BE 98X CONDUCTIVITY SOFT DRAWN ANNEALED COPPER, 600 VOLT, THHN/IHWN INSULATION, 110 AND SMALLER - SCUD, #5 AND LARGER - STRANDED. B. NO CONDUCTORS SHALL BE SMALLER THAN NO. 12, EXCEPT FOR SIGNAL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS PERMITTED BY NEC. C. FOR HOME RUNS ON 12D -VOLT, 20- AMPERE BRANCH CIRCUITS. WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 LINEAR FEET, USE NO. 10 CONDUCTORS WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS. D. FOR HOME RUNS ON 277 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 LINEAR FEET, USE NO. 10 CONDUCTORS. WHERE LENGTH OF RUN IS 100 LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS. E NO MORE THAN FIVE CONDUCTORS (3 PHASE, 1 NEUTRAL. AND 1 GROUND) SHALL BE INSTALLED IN A COMMON BRANCH CIRCUIT CONDUIT. F. PROVIDE COLOR CODED CABLE SYSTEM APPROVED BY OWNER. IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING COLOR CODING: a.48OV/277 b. 208V/120 A PHASE - BROWN A PHASE - BUCK B PHASE - ORANGE B PHASE - RED C PHASE - YELLOW C PHASE - BLUE NEUTRAL - GREY NEUTRAL - WIHITE GROUND - GREEN GROUND - GREEN COLOR CODING SHALL BE CONTINUOUS ON INSULATION FOR #6 AWG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER THAN #6 AWG G. INSTALLATION OF CONDUCTORS 1. PULL NO CONDUCTORS INTO CONDUITS UN71L ALL WORK OF A NATURE WHICH MAY CAUSE INJURY TO CONDUCTORS IS COMPLETED. 2. RUN FEEDERS IN CONTINUOUS LENGTHS, WITHOUT JOINTS OR SPLICES, INSOFAR AS PRACTICABLE 3. RUN CONDUITS FOR EMERGENCY POWER CONDUCTORS SEPARATE FROM ALL OTHER WIRING. 4. CABLE TYPE AC OR MC IS NOT ALLOWED FOR HOMERUN AND FEEDER INSTALLATIONS. 16140 - WIRING DEVICES A. ALL WIRING DEVICES SHALL BE UL LISTED. B. ACCEPTABLE MANUFACTURERS: PASS & SEYMOUR, HUBBEL, LEVITON, AND COOPER. C. RECEPTACLES 1. RECEPTACLES SHALL BE HOSPITAL GRADE STANDARD STYLE THEY STINT BE 20A,125V. 2 -POLE, 3 -W11F, NHA 15-208 OONFIGU AW N, BACK AND SIDE WIRED 1111111111111 A GREEN EWFMW GRCIM SCREW OR AN AUTDIMIC GROIDING SYSTEM ATTACHED TD THE STRAP UXA 2. GFC RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES DOWNSTREAM ON THE SAME CIRCUIT. THEY SHALL BE UL RATED LASS 1 WITH 5rnA GROUND FAULT TRIP LEVEL. AND A 20A FEED- THROUGH RATING AND HAVE A NEMA 5-20R CONFIGURATION. 3. RECEPTACLE COLOR SHALL BE IVORY. THEY SHALL BE RED WHEN CONNECTED TTO AN EMERGENCY CIRCUIT. 4. PEDIATRIC LOCATIONS - ALL RECEPTACLES LOCATED IN PATIENT CARE AREAS SHALL BE LISTED TAMPER RESISITANT. D. SWITCHES 1. SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, HORSEPOWER RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE A GREEN GROUND SCREW ATTACHED TO THE MOUNTING STRAP. 2. WHERE UGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, PROVIDE WITH SPECIFICATION GRADE, HORSEPOWER RATED, UL LISTED, BACK- AND SIDE - WIRED, TOGGLE SWITCHES RATE) 20A, 120V OR 277 VOLTS SWITCHES SHALL BE SPST. DPST, 3-WAY OR 4-WAY, WITH OR WITHOUT PILOT LIGHT AS INDICATED ON THE DRAWINGS. 3. SWITCH COLOR SHALL BE IVORY OR RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. E DIMMER SWITCHES 1. DIMMER SWITCHES SHALL BE MANUFACTURED BY LUTRON. 2. ALL DEVICES SHALL BE CAPABLE OF OPERATING AT RATED CAPACITY WITHOUT ADVERSELY AFFECTING DESIGN LIFETIME 3. DIMMER CONTROL OF LIGHT INTENSITY SHALL. BE VIA LINEAR SLIDE 4. LINEAR SLIDE DIMMER SHALL PROVIDE INTENSITY AND ON /OFF CONTROL WITH MOVEMENT OF SLIDER. THIS SHALL APPLY TO SINGLE POLE AND 2- LOCATION DIMMERS. 5. ALL DIMMERS SHALL MEET UL20 AND BE APPROPRIATELY MARKED. 6. SWITCH RATING SHALL BE 20A, 12OVAC, FOR TUNGSTEN OR INDUCTIVE LOADS. F. WALL PLATES 1. WALL PLATES SHALL BE PROVIDE) FOR ALL SWITCHES, RECEPTACLES, BLANKS, 7ELEPHONE/bATA. AND SPECIAL PURPOSE OUTLETS. THE WALL PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR WHICH IT IS TO COVER WITH COLOR MATCHING MOUNTING SCREWS COLOR OF THE WALL PLATES SHALL MATCH THE DEVICE, U.N.O. 2. WALL PLATES SHALL BE THERMOPLASTIC, NON - COMBUSTIBLE, AND HIGH-IMPACT RESISTANT. THEY SHALL BE P -UNE SMOOTH PLATES. THEY SHALL BE OF THE SAME MANUFACTURER AS THE WIRING DEVICE IT IS TO COVER. 3. WEATHERPROOF: WIRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY MARKED 'SUITABLE FOR WET LOCATIONS MILE IN USE' AND 'UL LISTED'. THERE SHALL BE A GASKET BETWEEN THE COVER/ENCLOSURE AND THE MOUNTING SURFACE, AND BETWEEN THE HINGE) COVER AND MOUNTING PLATE/BASE TO ASSURE PROPER SEAL THE COVE'R/ENMOSURE SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY TAYMAC CORPORATION OR EQUAL G. INSTALLATION OF WIRING DEVICES I. EACH WIRING DEVICE SHALL BE MOUNTED IN A METALLIC OUTLET BOX IN GENERAL, DEVICES IN FINISHED SPACES SHALL BE FLUSH MOUNTED DEVICES AND DEVICES N UNFINISHED SPACES SUCH AS ELECTRICAL AND MECHANICAL ROOMS SHALL BE SURFACE MOUNTED. VERIFY THE REQUIREMENTS OF ALL SPACES WITH ARCHITECT. 2. MOUNT RECEPTACLES A.F.F. TO THE DEVICE CENTERLINE, U.N.O. MOUNT SWITCHES A.F.F. TO THE DEVICE CENTERLINE AND 6' FROM A DOOR STRIKE, U.N.O. 3. MAINTAIN GROUNDING CONTINUITY BETWEEN DEVICES AND METALLIC RACEWAY SYSTEM IN ADDITION TO PROVIDING A GREEN EQUIPMENT GROUNDING CONDUCTOR RUN WITH ALL CIRCUIT CONDUCTORS AS INDICATED ON THE DRAWINGS 4. MOUNT RECEPTACLES THROUGHOUT THE PROJECT WITH GROUND POLE AT THE TOP OF THE CONFIGURATION WHEN MOUNTED VERTICALLY AND ON THE RIGHT WHEN MOUNTED HORIZONTALLY. 5. ALL EXTERIOR RECEPTACLES SHALL BE GFC1 WITH A WEATHERPROOF COVER/ENCLOSURE 16190 - SUPPORTING DEVICES A ACCEPTABLE MANUFACTURERS: UNISTRUT CORP., B -LINE SYSTEMS, INC., AND MIDLAND ROSS- IINDORF. B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRED BY RACEWAY SYSTEMS. C. HANGERS SHALL BE SUPPORTED BY MEANS OF UNCOATED SOUD STEEL RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS LOCK NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCI( ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO LOCK NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: NOMINAL CONDUIT SIZE ROD DIAMETER 1/2' THROUGH 2' /. 2-11r ROUGH 3' 3/8' 4' AND 5' 1/2' D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF RACEWAY. BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER 8' -0' OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1' DIAMETER SHALL BE SUPPORTED AT LEAST EVERY 6' -0'. E WHERE NUMEROUS CONDUITS ARE RUN PARALLEL TO ONE ANOTHER, THEY MAY BE SUPPORTED FROM A TRAPEZE TYPE HANGER ARRANGEMENT WITH STRUT BOTTOM. F. SUPPORT OF HANGERS SHALL BE BY MEANS OF SUFFICIENT QUANTITIES OF INDIVIDUAL AFTER SET STEEL EXPANSION SHIELDS, OR BEAM CLAMPS ATTACHED TO STRUCTURAL STEEL. G. STIFF -LEG SHALL. BE FURNISHED AND INSTALLED N CASES WHERE SUPPORT FROM OVERHEAD STRUCTURE IS NOT POSSIBLE H. CEILING MOUNTED LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AT TWO OPPOSITE CORNERS. THE CONTRACTOR SHALL PROVIDE FIXTURE HANGERS TO PROPERLY INTERFACE WITH THE CELING SYSTEM. I. FURNISH AND INSTALL COMPLETE ANY ADDITIONAL STRUCTURAL SUPPORT STEEL BRACKETS, FASTENERS. ETC. AS REQUIRED TO ADEQUATELY SUPPORT ALL RACEWAY AND EQUIPMENT. J. SUPPORT OF HANGERS FROM CONCRETE SLABS SHALL BE BY MEANS OF SUFFICIENT QUANTITY OF 'U' BRACKETS ATTACHED WITH AFTER SET EXPANSION SHIELDS AND BOLTS 16195 - ELECTRICAL IDENTIFICATION A. PROVIDE ELECTRICAL IDENTIFICATION FOR THE FOLLOWING: 1. SWITCHGEARS, SWITCHBOARDS, MOTOR CONTROL (ENTERS, PANEBOARDS, MOTOR STARTERS, CONTACTORS, DISCONNECT SWITCHES, CIRCUIT BREAKERS, AND OTHER ELECTRICAL EQUIPMENT WITH NAMEPLATE IDENTIFYING THE ITEM OF EQUIPMENT SERVING THE SAME. 2. RACEWAYS, JUNCTION BOXES, AND PULL BOXES. 3. WIRING DEVICES, WIRING, AND THREE PHASE MOTOR ROTATION. B. PROVIDE THE FOLLOWING COLOR CODING FOR ALL EQUIPMENT NAMEPLATES: NORMAL SYSTEM -BUCK W/ WHITE LETTERS CRITICAL BRANCH - RED W/ WHITE LETTERS LIFE SAFETY BRANCH - YELLOW W/ WHITE LETTERS EQUIPMENT SYSTEM - GREEN W/ WHITE LI=TTERS C. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH BEVELED EDGES. MINIMUM 1/16' THICK. LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4' HIGH, CUT THROUGH THE SURFACE TO THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. D. ALL NAMEPLATES SHALL INCLUDE VOLTA F, PHASE, WIRE, BRANCH OF POWER CONNECTED 70, AND SOURCE OF POWER EQUIPMENT IS FED FROM. NAMEPLATES SHALT. BE LAMINATED, WHITE CORE, PLASTIC WITH BEVELED EDGES, MINIMUM 1/16' THICK. LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 114' HIGH, OUT THROUGH THE SURFACE TO THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL NOT BE USED. E IDENTIFICATION OF JUNCTION AND PULL BOXES SHALL BE WITH A BLACK PERMANENT MARKING PEN ON THE TOP OF THE 4' X 4' JUNCTION BOX COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES SHALL BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM SERVED. F. ON THE FACE OF THE WIRING DEVICE WALL PLATE, MACHINE ENGRAVE THERMOPLASTIC PLATES WITH THE PANELBOARD AND BRANCH CIRCUIT NUMBER THE DEVICE IS SERVED FROM. ADHESIVE LABELS ARE NOT ALLOWED. G. RACEWAY IDENTIFICATION SHALL BE PROVIDED AT A MINIMUM OF EVERY 50', AT EACH END F LESS THAN 50', AND A MINIMUM OF ONCE PER ROOM OR SPACE THROUGH WHICH IT PASSES H. CONDUIT, RACEWAYS AND BOXES SHALL BE SPOT PAINTED. CONDUIT SHALL BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE THE ENTIRE BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR CODING SCHEME: NORMAL SYSTEM - WHITE FIRE ALARM - RED CRITICAL BRANCH - BRIGHT ORANGE COMMUNICATIONS - BROWN LIFE SAFETY BRANCH - BRIGHT Yam TELEPHONE /COMPUTER - BUCK EQUIPMENT SYSTEM - KELLY GREEN NURSE CALL - ROYAL BLUE TV - LIGHT PINK 16450 - GROUNDING A. EXPOSED METALLIC PARTS OF THE ELECTRICAL SYSTEM WHICH ARE NOT INTENDED TO CARRY CURRENT. INCLUDING SYSTEM COMPONENTS SUCH AS BUSDUCTS, SWITCHBOARDS, PANELBOARDS AND RACEWAY SYSTEMS, AND INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS WIRING SYSTEMS, SHALL BE GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS., B. PROVIDE COPPER CLAD STEEL GROUND RODS 3/4 INCH DIAMETER 10 FEET LONG DESIGNED FOR DRIVEN INSTALLATION. C. PROVIDE EXOTHERMIC TYPE CHEMICAL WELDED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RCDS, GROUNDING PLATES AND SPLICING OF CONDUCTORS. PROVIDE COMPRESSION AND BOLTED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND BARS D. PROVIDE MECHANICAL TYPE CONNECTORS FOR JOINING OF ALL EQUIPMENT AND ISOLATED GROUND CONDUCTORS. E SIZE GROUNDING CONDUCTORS N ACCORDANCE WITH TABLES 250-66 AND 25G -122 OF THE NEC. F. PROVIDE GROUNDING BUSHINGS ON ALL RACEWAYS TERMINATING WITHIN ALL ELECTRICAL ENCLOSURES CONSTRUCTED OF SEPARATE ENCLOSURE PANELS WHICH ARE NOT INTEGRALLY WELDED TOGETHER PROVIDE GROUNDING CONDUCTORS FROM SUCH BUSHINGS TO THE FRAME OF THE ENCLOSURE. GROUND BUS AND EQUIPMENT GROUNDING STRAP WHERE ONE OCCURS. G. PROVIDE A SEPARATE GREEN - INSULATED EQUIPMENT GROUNDING CONDUCTOR. WITH INSULATION OF THE SAME RATING AS THE PHASE CONDUCTORS, FOR ALL FEEDERS AND BRANCH CIRCUITS. INSTALL THE GROUNDING CONDUCTORS N THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS. WHERE PARALLEL CONDUCTORS N SEPARATE RACEWAYS OCCUR, PROVIDE A GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING CONDUCTORS TO GROUND TERMINALS AT EACH END OF THE RUN, TO THE END THAT THERE WILL BE NO UNINTERRUPTED GROUNDING CIRCUIT FROM THE POINT OF GROUND FAULT BACK TO A POINT OF CONNECTION OF THE EQUIPMENT GROUND AND SYSTEM NEUTRAL. H. CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH DRY TYPE TRANSFORMER TOGETHER AND RUN A GROUNDING ELECTRODE CONDUCTOR FROM THEIR COMMON POINT OF CONNECTION TO THE BUILDING GROUNDING ELECTRODE SYSTEM. L PERFORM THE FOLLOWING TESTS: 1. TEST THE CONTINUITY OF, AND THE PROPER CONNECTION OF. EACH GROUND CONDUCTOR AND SYSTEM, TO ASSURE THAT THE GROUNDING SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE PERFORMED USING LABORATORY- ACCURACY TEST INSTRUMENTS OF SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS SHALL BE PROVIDED UNDER DIVISION 16. 2. TEST GROUNDING CONDUCTORS, PHASE CONDUCTORS AND NEUTRAL CONDUCTORS FOR CONTINUITY AND FOR POSSIBLE DAMAGE TO INSULATION. EACH CONDUCTOR SHALL BE TESTED FOR INSULATION FROM GROUND AND FROM OTHER CONDUCTORS 3. MY PORTIONS OF THE INSTALLATIONS WHICH FAIL TO PASS THESE TESTS SHALL BE REPLACED, REPAIRED OR OTHERWISE CORRECTED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, AND COMPLETELY RETESTED TO SHOW PROPER CONFORMITY. 4, CONTRACTOR IS RESUME FOR TE.51NC THE E>riT]MNIESS OF THE GROUNDING SYSR31 FOR ALL ELECIRKTAL DEMCES N 1HE SCOPE OF WOMK ARiFJA BY VOLTAGE AND IPEDANCE 1EASURE7EN15 AS INDICATED N NFPA 1% 43.3.13 Mt 443.1.4 RESPEICTIIIEH.Y. THE RESTS SHALL BE Fimm D w1HR A MM THAT HAS BEEN CALIBRATED YIIFNN THE LAST 12 MONTHS THE METER AND TYPED OR PRINTED tIFCgRDED RESLL73 SHALL BE MACE AVAILABLE AT TIE OF FINAL NSPE>CIM 16475 - OVERCURRENT PROTECTIVE DEVICES A. PROVIDE DATA SHEETS SHOWING ELECTRICAL CHARACTERISTICS INCLUDING TIME - CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL B. FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE G CIRCUIT BREAKERS 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE SWITCHBOARD/PANELBOARD/MOTOR CONTROL CENTER MANUFACTURER. 16500 - UGHTING FIXTURES A CONTRACTOR SHALL QUOTE THE SPECIFIED LIGHT FIXTURES IN BASE BID. ANY PROPOSED ALTERNATES MUST BE SHOWN AS AN EXCEPTION TO BASE BID AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID. ANY PROPOSED ALTERNATE FIXTURES SHALL MATCH THE FOLLOWING SPECIFIED LIGHTING FIXTURE CHARACTERISTICS: PHYSICAL SIZE AND DIMENSIONS, CONSTRUCTION, MATERIAL. LAMP AND BALLAST TYPE, LENS AND REFLECTOR TYPE, PAINT APPLICATION PROCESS, AND PHOTOMETRIC CHARACTERISTICS. ALL RATINGS INCLUDING, BUT NOT LIMITED TO WATTAGE; FIRE RATINGS, AND SPECIAL LOCATION RATINGS SHALL ALSO MATCH. ANY PROPOSED ALTERNATES NOT MEETING ANY OF THESE CHARACTERISTICS SHALL BE REJECTED. B. FIXTURES SHALL BE COMPLETE WITH LAMPS, BALLASTS AND RELATED AUXILIARY EQUIPMENT AND ACCESSORIES NECESSARY TO THE INTENDED OPERATION, INCLUDING MOUNTING DEVICES REQUIRED FOR EACH TYPE OF INSTALLATION. C. ALL LIGHTING FIXTURES SHALL BEAR THE UL LABEL D. WHERE LIGHTING FIXTURES ARE SCHEDULED WITH PLASTIC LENSES, PROVIDE ACRYLIC LENSES HAVING A THICKNESS OF 0.125 INCHES. E LAMPS 1. EACH LIGHTING FIXTURE SHALL BE FURNISHED WITH A NEW SET OF LAMPS OF THE TYPES INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. LAMPS SHALL BE MANUFACTURED BY GENERAL ELECTRIC. PHILIPS; OR OSRAM- SYLVANIA, EXCEPT WHERE SCHEDULED OTHERWISE 2. INCANDESCENT LAMPS: IN GENERAL, THEY SHALL INSIDE FROSTED, ENERGY SAVING STYLE DESIGNED FOR 130V OPERATION WITH A RATED LIFE OF 2,500 HOURS (EXTENDED SERVICE). WHERE REFLECTOR STYLE LAMPS ARE SCHEDULED, FURNISH BEAM PATTERN INDICATED. 3. FLUORESCENT LAMPS: IN GENERAL. THEY SHALL BE 3500K 48-NCH LENGTH, T8, RAPID START, ENERGY SAVING LAMPS WITH AN INITIAL NOMINAL. OUTPUT OF 2,850 LUMENS AT 32W, AND AN AVERAGE RATED LIFE OF 20,000 HOURS. 4• HIGH INTENSITY DISCHARGE (HID) LAMPS: SHALL BE OF THE TYPE AND WATTAGES SCHEDULED. WHERE METAL HALIDE LAMPS ARE INDICATED, SELF-EXTINGUISHING LAMPS SHALL BE FURNISHED WHERE AVAILABLE IN THAT WATTAGE RANGE F. FLUORESCENT BALLASTS SHALL BEQUAL TO MOTOROLA LIGHTING INC. RAPD START HIGH PERFORMANCE ELECTRONIC TYPE . G. INSTALLATION _ _ 1. • THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE , SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS. PROVIDE HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY N PUCE Z THE WIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS PROVIDE HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY N PUCE 3. THE MOUNTING BRACKETS SHALL BE INSTALLED TO OVERLAP THE CEILING SUPPORT CHANNELS IN ORDER TO PREVENT THE CHANNELS FROM SHIFTING FROM UNDERNEATH THE FIXTURES. 4. THE LIGHTING FIXTURE INSTALLATION SHALL NOT INTERFERE WITH THE INSTALLATION OR REMOVAL OF ADJACENT CEILING PANELS 5. RECESSED FIXTURES IN DROPPED CEILING AREAS SHALL BE CONNECTED USING FLEXIBLE CONDUIT. CONDUIT SHALL BE CONNECTED TO FIXTURE AND OUTLET BOX EACH PIECE SHALL HAVE A SEPARATE INSULATED GREEN GROUNDING CONDUCTOR #14 MIN. FOR GROUNDING CONTINUITY BETWEEN THE FIXTURE AND THE CONDUIT SY51EUL GROUNDING CONDUCTOR SHALL BE MECHANICALLY CONNECTED IN A PERMANENT AND EFFECTIVE MANNER TO FIXTURE AND CONDUIT SYSTEM AND BE ELECTRICALLY CONTINUOUS. 16721 - FIRE ALARM SYSTEM (MODIFICATION) A FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS AND RELOCATIONS AS INDICATED ON THE DRAWINGS, COMPATIBLE AND CONSISTENT WITH THE EXISTING SYSTEM. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING CONTINUAL SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR EXPANSION. C R IS THE RESPOiMM OF THE EIECIRICAL OWRAC70 R TO PROVIDE EMANIME MODULES, POWER SUPPLE% HARDWARE, SOFTWARE, ETC 10 THE FIRE ALARM SYSTEM N ORDER TO ACCOMMODATE THE ADOIIONAL FIRE ALARM Or" C S D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW SMOKE DETECTORS. E THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. W..� �� ��__ J J C> it 0 dMiz .. Icz 0 W V W . p rn: �. I 11 Z) co V 2121 Por op., de Leol I Blvd., suite 350 >, f °'6°ti1�0 4 °�PCO Coral GGble�, FL,U34 '- ___ _ __ _ 1,0 ' LL LL -i phone: 305.569.1692 F. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED *Nessional Consulting Engineers "-k r► ' THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE fax: 305.569.1693 �' ) SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FraIIaS •Houston •Nashville •Miami •Richmond - o,U CCOYMOUNRCAATTIOON N . COOORDINATEAALLaREQU�iREMENTS WITH DIVISION 115. ccrd project number: 408283 G VISUAL STROBE DEVICES SHALL MEET THE REQUIREMENTS OF ADA. UL. EB00007658 ,,• AND NFPA. H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS t, WITH A PEAK OUTPUT OF 96dB AT 10' -0'. I. ALL WIRING SHALL BE STRANDED AND N CONDUIT. COLOR SHALL BE THE O FACILITY'S STANDARD OR RED. &a Q J. PROVIDE NEW CONDUIT AND WIRING AS REQUIRED FOR NEW FIRE ALARM B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL WIRING, w 0 DEVICES. CONNECT AND PROGRAM DEVICES EXISTING FIRE ALARM CONTROL ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION WIRING NOT SHOWN PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH I ON THE ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. OWNER. NEW DANCES ARE TO MATCH EXISTING ONES AND E UL LISTED WITH TEMPERATURE CONTROL. ENERGY MANAGEMENT SYSTEM AND BUILDING 0 1 P I EXISTING FIRE ALARM SYSTEM. PROVIDE NEW POWER SUPPLIES AS NECESSARY AUTOMATION SYSTEM WRING IS DEFINED AS THE INTERLOCK OR L6 N C EXPANSION MODULES OR ANY SOFTWARE HARDWARE INTERCONNECTING WIRING REQUIRED BETWEEN SYSTEM CONTROL DEVICES, M: ACCESSORIES TI REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL APPURTENANCES AND CONTROL PANELS TO ALLOW THE SYSTEM TO FUNCTION DEVICES SHALL MEET ADA REQUIREMENTS ICES SHALL AUTOMATICALLY. THIS INCLUDES HARING BETWEEN THE FIRE ALARM SYSTEM, K• CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL, ENERGY MANAGEMENT LOCATION, TYPE, CABLING, AND BATTERY CALCULATIONS. AND BUILDING AUTOMATION SYSTEM. L ALL WIRING SHALL BE IN 3/4'C. MINIMUM. G PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND /OR ELECTRICALLY - M. VEDA SHALL RE-CUM THE SYSIETY AND PROVIDE COW0II0114 OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHAD_ ALLOW `% MO Sim OEllxlDIR SE?19111M REPORT PRIOR TO ANY NSPECIM THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. N. SYNCHRONIZE ALL AUDIO/VLSUAL DEVICES. D. CONTROL WIRING WILL, UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES. FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE MU SHALL SHUT DOWN E EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY-INSTALLED, INTEGRAL 0 WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE MOTORS, AN ELECTRIC MOTOR OF REQUIRED SIZE AND ELECTRICAL W OW INTERLOCKED WITH THE AHU STARTER. LOCATE FIRE ALARM RELAY WITHIN CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS 3' -0' OF STARTER. FOR EACH ITEM OF MOTOR -DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL 41 V ■d INSTALLATION OF THESE MOTORS IN ACCORDANCE WITH APPROVED WIRING 16741 - TELEPHONE AND DATA COMMUNICATIONS = LM A. AT ALL WALL DATA/VOICE OUTLET LOCATIONS, PROVIDE A 4 11/16' SQUARE F. WHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE NOT PROVIDED WHERE DI CI c BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLATE 1' MIN. EMPTY WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL CC014 CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE APPURTENANCES PROVIDE AND INSTALL ALL DISCONNECT SWITCHES CORRIDOR CEILING SPACE. WHERE CORRIDORS DO NOT HAVE ACCESSIBLE AND/ 011 REQUIRED BY THE NATIONAL ELECTRICAL CODE AND OR INDICATED.' PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM G WHERE POSSIBLE, TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS. COVERING THE ENTIRE LENGTH OF NON - ACCESSIBLE CEILING CAVITY. NUMBER WHERE MOTORS ARE NOT PROVIDED WITH CONDUIT BOXES, TERMINATE AND SIZE OF CONDUIT /SLEEVES SHALL BE PER MANUFACTURER'S CABLING THE CONDUITS IN CONDUIT FITTINGS AT THE MOTORS. REQUIREMENTS. B. PROVIDE A MINIMUM OF A 3/16' DIAMETER, TWISTED NYLON PLASTIC CORD N ALL EMPTY RACEWAYS. PROVIDE A IDENTIFICATION TAG ON EACH END INDICATING THE LOCATION OF THE OTHER END. - C• INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR ' I ..z ^ ' 't CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. D• WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 31,C THICK APA A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) COATS OF LIGHT GRAY PAINT. BACKBOARDS SHALL BE MOUNTED SIX (67 INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT (8' -0') FEET OR TO THE . CEILING GRID IF LESS THAN B' -0'. 16763 - NURSE CALL /CODE BLUE SYSTEMS A. SUBMITTALS - SHOP DRAWINGS: DETAIL THE SYSTEM INCLUDING THE FOLLOWING: 1. CABLING DIAGRAMS SINGLE -UNE BLOCK DIAGRAMS SHOWING CABLING INTERCONNECTION OF ALL COMPONENTS FOR THIS SPECIFIC EQUIPMENT. INCLUDE CABLE TYPE FOR EACH CONNECTION. 2. WIRING DIAGRAMS: POWER, SIGNAL AND CONTROL WIRING. 3. STATION INSTALLATION DRAWING FOR BUILT -IN EQUIPMENT; DIMENSIONED AND TO SCALE 4. EQUIPMENT CABINET DRAWINGS: DIMENSIONED AND TO SCALE B. SUBMITTALS - COORDINATION DRAWINGS: DETAIL SYSTEM COMPONENTS THAT FIT, MATCH, AND LINE UP WITH PROVISIONS MADE IN EQUIPMENT SPECIFIED IN OTHER SECTIONS OR IN SEPARATE CONTRACTS: 1. PATIENT HEAD -WALL UNITS . ' 2. PATIENT CONSOLES. , ' . 3. BEDS WITH BUILT -IN NURSE CALL FEATURES I I . . O. SUBMITTALS - MANUFACTURER CERTIFICATES: SIGNED BY MANUFACTURERS . . .1 " CERTIFYING THAT THE NURSE CALL EQUIPMENT COMPLIES WITH REQUIREMENTS. . ' ` . - I . D. COORDINATION . ' - 1. COORDINATE PATIENT CONTROL UNITS WITH ITEMS CONTROLLED THAT ARE - -- . NOT PART OF THE NURSE CALL EQUIPMENT SUCH AS TV AND LIGHTS. I • - • • • I COORDINATE WIRING PATHS AND MAINTENANCE ACCESS AT LOCATIONS ' LISTED BELOW. COORDINATE TRIM FEATURES AND FINISHES AT PATIENT , HEAD -WAIL UNITS, PATENT CONSOLES, PATIENT BEDS NTH BUILT-IN . .. . NURSE CALL FEATURES, AND NURSE STATIONS TO PRESENT A UNIFIED . ., , . • • DESIGN APPEARANCE . E EXTRA MATERIALS: FURNISH EXTRA MATERIALS DESCRIBED BELOW THAT MATCH ' PRODUCTS INSTALLED AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH LABELS DESCRIBING CONTENTS. . . 1. LAMPS FOR CORRIDOR DOME LIGHTS AND ZONE LIGHTS EQUAL. TO 20% . OF AMOUNT INSTALLED. - ' 2. FUSES: ONE FOR EVERY TEEN (10) OF EACH TYPE AND RATING BUT NOT I . FEWER THAN TWO (2. . 3. PRINTED CIRCUIT BOARDS: EACH KIND EQUAL TO 1OX OF AMOUNT • - INSTALLED, BUT NOT FEWER THAN ONE (1) UNIT. 4• MASTER STAII(>rl PRIVACY HANDSET ONE (1). • F. MANUFACTURER SHALL BE SELECTED BY OWNER. . - . ' G. EXPANSION CAPABILITY: EQUIPMENT RATINGS, HOUSING VOLUME. SPARE KEYS, - SWITCHES, RELAYS, ANNUNCIATOR MODULES, TERMINALS, AND CABLE . , CONDUCTOR QUANTITIES ADEQUATE TO INCREASE THE NUMBER OF STATIONS IN . THE FUTURE BY 25X ABOVE THOSE INDICATED WITHOUT ADDING INTERNAL OR EXTERNAL COMPONENTS OR MAIN TRUNK CABLE CONDUCTORS , H. EXISTING SYSTEM COMPATIBILITY: FUNCTIONALITY AND ELECTRONICALLY COMPATIBLE WITH EXISTING SYSTEM SO COMPONENTS AND WIRING OPERATE AS AN EXTENSION OF THE EXISTING SYSTEM AND ALL FUNCTIONAL PERFORMANCE - OF THE EXISTING SYSTEM APPLIES TO THE FINAL SYSTEM. COLORS, TONES, TYPES, AND DURATIONS OF SIGNAL MANIFESTATION ARE COMMON BETWEEN NEW AND EXISTING SYSTEMS I. INSTALLATION . 1. INSTALL WIRING IN RACEWAY EXCEPT WITHIN CONSOLES, DESKS, AND • - COUNTERS; AND EXCEPT IN ACCESSIBLE CEILING CEILING SPACES AND IN ' GYPSUM BOARD PARTITION$ WHERE CABLE WRING METHOD MAY BE • . USED. USE UL LISTED PLENUM CABLE AND RACEWAY WIRING EXCEPT IN • UNFINISHED SPACES. 2. INSTALL CABLES WITHOUT DAMAGING CONDUCTORS, SHIELD, OR JACKET. 3. SEPARATE SPEAKER- MICROPHONE, UNE - LEVEL, SPEAKER - LEVEL, AND POWER -WIRING RUNS RUN IN SEPARATE RACEWAYS OR, IF EXPOSED OR IN SAME ENCLOSURE PROVIDE 12 -INCH MINIMUM SEPARATION BETWEEN CONDUCTORS TO SPEAKER MICROPHONES AND ADJACENT PARALLEL POWER AND TELEPHONE WIRING PROVIDE SEPARATION AS RECOMMENDED BY EQUIPMENT MANUFACTURER FOR OTHER CONDUCTORS J. EXISTING SYSTEMS 1. EXAMINE EXISTING SYSTEMS FOR PROPER OPERATION, COMPATIBILITY WITH NEW EQUIPMENT AND DEFICIENCIES. IF DISCREPANCIES OR IMPARMENTS TO SUCCESSFUL CONNECTION AND OPERATION OF INTERCONNECTED EQUIPMENT ARE FOUND, REPORT THEM AND DO NOT PROCEED WITH INSTALLATION UNTIL DIRECTED. SCHEDULE EXISTING SYSTEMS' • EXAMINATION SO THERE IS REASONABLE TIME TO RESOLVE PROBLEMS WITHOUT DELAYING CONSTRUCTION. K. GROUNDING 1. CABLE SHIELDS AND EQUIPMENT TO ELIMINATE SHOCK HAZARD AND TO MINIMIZE GROUND LOOPS, COMMON -MODE RETURNS, NOISE PICKUP, _ CROSS TAU(, AND OTHER SIGNAL IMPAIRMENTS. , , - " , , i , 2. SIGNAL GROUND TERMINAL LOCATE AT MAIN EQUIPMENT CABINET. 1. ' , , .' , ' ;,� _;' � I. ` ' ISOLATE FROM POWER SYSTEM AND EQUIPMENT GROUNDING EXCEPT AT . CONNECTION TO MAIN BUILDING GROUND BUS 3. COMPLY WITH SECTION 16450 - GROUNDING ELECTRICA.X.. SECTIADNI L VENDOR SHALL PROWDE A TECHNICIAN AVAILABLE AT THE OF FINAL INSPECTIONS THAT DEMONSTRATE THE OPERATION THE NURSE CALL 'a�_�/D_ SYSIEIII TD TEE WECI SATISFACIION,VIE DOR SHALL PROVIDE A CERIFIGUTHON REPORT FOR ALL DEVICES N THE SCOPE OF WORK AREA. APPROVED BY: M, CONTRACTOR AND VENDOR ARE FASO SHB TD DIM THAT ALL NEW OR DOSING TO REMAIN CODE BUMF STATIONS N THE SCOPE OF WORK D AREA ANINNOATE AT THE LOCAL NURSE STATION AND THE FACUTE'; DATE' H' • p 24 HOUR MINED LOCATION SUCH AS PBDL 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING A. THE FURNISHING AND INSTALLATION OF CONTROL POWER WIRING REQUIRED FOR EQUIPMENT FURNISHED UNDER DIVISION 15 AND NOT SHOWN ON THE ELECTRICAL DRAWING SHALL BE FURNISHED UNDER DIVISION 15. CONTROL POWER WIRING IS DEFINED AS THE LINE VOLTAGE (1201) POWER WIRING FOR EQUIPMENT CONTROL CABINETS, TEMPERATURE CONTROL. ENERGY MANAGEMENT, OR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/FIRE DAMPERS. J J C> it 0 dMiz .. Icz 0 W V W . p rn: �. I 11 Z) co ' CU >, f °'6°ti1�0 4 °�PCO n 1,0 ' LL LL -i C TM Mr "-k r► ' r` V r- r' N Q_ �' ) e Horn 'T r- co, o,U y, cm to CM co W , ,,• V t, ' W< O &a Q U. w w 0 E _ ' LL 0 1 L6 N M: N a ■� W H- CO ; CO U.Cn �, E J `% 5 0� Q U co O 0 2 W i 2 O U 0 o � 0 Ch � 0 co 00) ' CU N C, o c 0 q C3 °'6°ti1�0 4 °�PCO E..V 1,0 ' LL LL -i C TM Mr "-k r► ' r` V r- r' N >-qw, �' ) e Horn 'T r- co, o,U y, cm to CM co -) i u. I �N ~O N�O �tL vT? 0 Ln`- ' CU N C, o c 0 q C3 3 J2cYicoa[LEQU¢ 0CL(n `- 1,0 ' LL LL -i C TM Mr Comm. No: 08061 co 07/0 ]/08 Drawn: * Revised: C TM Mr "-k r► ' ■O �' ) e fr Co I O ir U. w E 0 1 ■w 6 , a ■� CO ; CO �, E `% 5 co O 0 CO 0 ■Co 2 W OW N : O 0 � = 41 V ■d "9 'r = LM O a :o :� c V ♦ 5: CC014 O V Comm. No: 08061 Date: 07/0 ]/08 Drawn: * Revised: -'N, ,a; , "-k r► ' r e 1 0 !.;6 "'. ; ,. • , � ♦� Jr i `K y • .WV � �y , . Is �� .. W e`f !. .x'06; ' . ' i , @ 2008 HARVARD JOLLY,`IN;LF' E6 :0*0 . T �" I A .. ' ;' A_'__�� _.4 ,i I � �" 1 1 I -44 �' �1.1 I �' I , 4 � . N 4 .' 11 i .I f _'...- ."� ".j'A'a'n i .1 �' I