Loading...
08-957-028i PANED 51-3 ❑C DEVICE TYPE, Breaker ENCLOSURE, NEMA 1 MAINS(A)i ML❑ CONTINU❑US(A)i 225 LOCATION, 3RD FLOOR DEVICE FAMILY, Bolt On MOUNTING, Flush WIRING, 3 -Phase 4 -Wire AIC RATING(A)i 10000 FED FROM: XFSC 500KVA VOLTAGE: 208/120 FAULT CURRENT(A)i 7639 EXISTING PANEL CKT DESCRIPTI ❑N NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTI ❑N CKT C CODE AMPS P AMPS P 0 CODE C 1 LIGHTING 503 -506 EXISTING LOAD LIGHTING 800 20 1 A 20 1 750 LIGHTING EXISTING LOAD LIGHTING 521 -524 2 3 LIGHTING 502 -505 EXISTING LOAD LIGHTING 900 20 1 B 20 1 1050 LIGHTING EXISTING LOAD LIGHTING 522 -525 4 5 LIGHTING 501 -504 EXISTING LOAD LIGHTING 800 20 1 C 20 1 880 LIGHTING EXISTING LOAD LIGHTING 523 -526 6 7 LIGHTING ISOLATI ❑N EXISTING LOAD LIGHTING 750 20 1 A 20 1 900 RECEPTACLES EXISTING LOAD HALLWAY RECEPTACLE 8 9 LIGHTS ELECTRICAL CL EXISTING LOAD LIGHTING 850 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 10 11 PT RM FAN COIL 526 NOTE 1 MOTOR LOADS 763 20 1 C 20 1 900 RECEPTACLES EXISTING LOAD HALLWAY RECEPTACLE 12 13 HALLWAY RECEPTACLE EXISTING LOAD RECEPTACLES 720 20 1 A 20 1 540 RECEPTACLES EXISTING LOAD HALLWAY RECEPTACLE 14 15 NURSE LOUNGE EXISTING LOAD RECEPTACLES 540 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD NURSE LOUNGE 16 17 LIGHTING 522 EXISTING LOAD LIGHTING 850 20 1 C 20 1 0 SPARE EXISTING LOAD SPARE 18 19 SPARE NOTE 1 SPARE 0 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 20 21 FAN C ❑IL UNIT 522 -52 EXISTING LOAD RECEPTACLES 700 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 22 23 SPARE EXISTING LOAD SPARE 0 20 1 C 20 1 0 SPARE EXISTING LOAD SPARE 24 25 SPARE EXISTING LOAD SPARE 0 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 26 27 SPARE EXISTING LOAD SPARE 0 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 28 29 SPARE EXISTING LOAD SPARE 0 20 1 C 20 1 0 SPARE EXISTING LOAD SPARE 30 31 SPARE EXISTING LOAD SPARE 0 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 32 33 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 34 35 SPACE 0 0 1 C 0 1 0 SPARE SPACE 36 37 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 0 1 0 SPARE SPACE 38 39 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 40 41 SPACE i 0 0 1 C 0 1 0 RECEPTACLES EXISTING LOAD SPACE 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 13. 41 37. 2 x A -N 4460.0 37. 1 CONNECTED 35.91 TOTAL DEMAND 5.82 16. 2 X B -N 4760.0 39. 6 DEMAND 21. 00 TOTAL DESIGN 6.59 18. 3 x C -N 4192. 6 34. 9 DESIGN 21.77 NOTE 1i PR ❑VIDE NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE, PANED 5L4 ❑C DEVICE TYPE; Breaker ENCL❑SUREi NEMA 1 MAINS(A); ML❑ C❑NTINU❑US(A); 225 LOCATIONS 3RD FLOOR DEVICE FAMILYi Bolt On M❑UNTINGi Flush WIRINGi 3 -Phase 4 -Wire AIC RATING(A)i 10000 FED FROM; XFSC 500KVA VOLTAGE; 208/120 FAULT CURRENT(A); 7275 EXISTING PANEL CKT DESCRIPTION NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTI ❑N CKT C CODE AMPS P AMPS P 0 CODE C 1 RECEPTACLE 503 -506 EXISTING LOAD RECEPTACLES 720 20 1 A 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 503 -506 2 3 RECEPTACLE 503 -506 EXISTING LOAD RECEPTACLES 720 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 502 -505 4 5 RECEPTACLE 501 -504 EXISTING LOAD RECEPTACLES 720 20 1 C 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 501 -504 6 7 RECEPTACLES 501 -504 EXISTING LOAD RECEPTACLES 720 20 1 A 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 521 -524 8 9 RECEPTACLES 522 -525 EXISTING LOAD RECEPTACLES 720 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 522 -525 10 11 RECEPTACLE 522 -526 EXISTING LOAD RECEPTACLES 1080 20 1 C 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 522 -526 12 13 SPARE EXISTING LOAD SPARE 0 20 1 A 20 1 720 RECEPTACLES EXISTING LOAD RECEPTACLES 522 -525 14 15 CORRIDOR RECEPTACLES EXISTING LOAD RECEPTACLES 540 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 16 17 GENERAL RECEPTACLES EXISTING LOAD RECEPTACLES 720 20 1 C 20 1 0 SPARE EXISTING LOAD SPARE 18 19 ROOM 526 U.C. REFRIG NOTE 1 RECEPTACLES 500 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 20 21 ROOM 526 RECEPTACLES NOTE 1 RECEPTACLES 720 20 1 B 20 2 875 MOTOR LOADS EXISTING LOAD EXISTING LOAD 22 23 SPACE EXISTING LOAD RECEPTACLES 0 0 1 C "' 875 SPARE EXISTING LOAD "" 24 25 EXISTING LOAD EXISTING LOAD MOTOR LOADS 900 20 2 A 20 2 700 MOTOR LOADS EXISTING LOAD EXISTING LOAD 26 27 EXISTING LOAD EXISTING LOAD MOTOR LOADS 900 "' B '" 700 MOTOR LOADS EXISTING LOAD "" 28 29 EXISTING LOAD EXISTING LOAD MOTOR LOADS 675 20 2 C 60 2 2000 MOTOR LOADS EXISTING LOAD EXISTING LOAD 30 31 R# EXISTING LOAD MOTOR LOADS 675 "' A "" 2000 MOTOR LOADS EXISTING LOAD "' 32 33 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 34 35 SPACE 0 0 1 C 0 1 0 SPARE SPACE 36 37 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 0 1 0 SPARE SPACE 38 39 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 40 41 SPACE i 0 0 1 C 0 1 0 RECEPTACLES EXISTING LOAD SPACE 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 22. 50 62. 5 x A -N 8398.0 69. 9 CONNECTED 22.50 TOTAL DEMAND 15, 18 42. 1 X B -N 6628.2 55. 2 DEMAND 15. 18 TOTAL DESIGN 15. 18 42, 1 )K C -N 7581. 6 63. 1 DESIGN 15, 18 NOTE 11 PR ❑VIDE NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE. PANEL; 5E1 ❑C DEVICE TYPE; Breaker ENCL OSURE NEMA 1 MAINS(A)i ML❑ CONTINU❑US(A)i 225 L ❑CATIONS 3RD FLOOR DEVICE FAMILY, Bolt On MOUNTING+ Flush WIRINGS 3 -Phase 4 -Wire AIC RATING(A)i 10000 FED FROM, XFSC 500KVA V❑LTAGEi 208/120 FAULT CURRENT(A)i 5372 EXISTING PANEL CKT DESCRIPTION NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTION CKT C CODE AMPS P AMPS P 0 CODE C 1 PATIENT RM LIGHTING EXISTING LOAD LIGHTING 950 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 2 3 PYXIS EXISTING LOAD RECEPTACLES 300 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD NURSE STATI ❑N RECEPT 4 5 OMNICELL EXISTING LOAD RECEPTACLES 350 20 1 C 20 1 900 RECEPTACLES EXISTING LOAD NURSE STATI ❑N RECEPT 6 7 SPARE EXISTING LOAD SPARE 0 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 8 9 SPARE EXISTING LOAD SPARE 0 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 10 11 ROOM 501,504,507,510 EXISTING LOAD RECEPTACLES 540 20 1 C 20 1 980 LIGHTING EXISTING LOAD ROOM 517, 520, 523, 526 12 13 ROOM 502,506,509,512 EXISTING LOAD RECEPTACLES 720 20 1 A 20 1 880 LIGHTING EXISTING LOAD ROOM 513,518,523,524 14 15 ROOM 502,505,509,511 EXISTING LOAD RECEPTACLES 720 20 1 B 20 1 700 LIGHTING EXISTING LOAD ROOM 516,522,525 16 17 NURSES STATION EXISTING LOAD RECEPTACLES 720 20 1 C 20 1 720 RECEPTACLES EXISTING LOAD ROOM 527 18 19 PATIENT RM LTS 513 EXISTING LOAD LIGHTING 780 20 1 A 20 1 720 RECEPTACLES EXISTING LOAD ROOM 513 20 21 SPARE EXISTING LOAD SPARE 0 20 1 B 20 1 950 LIGHTING EXISTING LOAD PATIENT RM LTS 514 22 23 SPACE EXISTING LOAD RECEPTACLES 0 0 1 C 20 1 0 SPARE EXISTING LOAD SPARE 24 25 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 20 1 0 SPARE EXISTING LOAD SPARE 26 27 EXISTING LOAD EXISTING LOAD MOTOR LOADS 1248 20 2 B 20 2 936 MOTOR LOADS EXISTING LOAD EXISTING LOAD 28 29 "" EXISTING LOAD SPARE 1248 "' C "' 936 SPARE EXISTING LOAD "' 30 31 EXISTING LOAD EXISTING LOAD MOTOR LOADS 1267 20 3 A 30 3 2067 MOTOR LOADS EXISTING LOAD EXISTING LOAD 32 33 "" EXISTING LOAD RECEPTACLES 1267 "' B "" 2067 RECEPTACLES EXISTING LOAD "" 34 35 SPACE 1267 "' C "' 2067 SPARE "' 36 37 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 0 1 0 SPARE SPACE 38 39 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 40 41 SPACE i 0 0 1 C 0 1 0 RECEPTACLES EXISTING LOAD SPACE 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 26.02 72.2 x A -N 7383.3 61. 5 CONNECTED 26.02 TOTAL DEMAND 19. 03 52. 8 x B -N 8996.1 74, 9 DEMAND 19. 03 TOTAL DESIGN 19.55 54. 3 X C -N 9808, 7 81. 7 DESIGN 19. 55 1,10 W-1r. PANED 7L3 ❑C DEVICE TYPES Breaker ENCLOSUREi NEMA 1 MAINS(A), ML❑ C❑NTINUOUS(A), 225 LOCATION, 7TH FLOOR DEVICE FAMILY, Bolt On M❑UNTINGi Surface WIRINGS 3 -Phase 4 -Wire AIC RATING(A), 10000 FED FROM: PNL 2DL VOLTAGE; 208/120 FAULT CURRENT(A)i 6640 EXISTING PANEL CKT DESCRIPTION NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTI ❑N CKT C CODE AMPS P AMPS P 0 CODE C 1 PATIENT RM 703 -706 EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 500 LIGHTING EXISTING LOAD PT RM LTS 724 -727 2 3 PATIENT RM 702 -705 EXISTING LOAD RECEPTACLES 720 20 1 B 20 1 500 LIGHTING EXISTING LOAD PT RM LTS 725 -728 4 5 PATIENT RM 701 -704 EXISTING LOAD RECEPTACLES 720 20 1 C 20 1 1180 LIGHTING EXISTING LOAD PT RM LTS 724 -729 6 7 HALLWAY, CLOSET HW EXISTING LOAD LIGHTING 800 20 1 A 20 1 500 LIGHTING EXISTING LOAD PT RM LTS 727 -730 8 9 HALLWAY, CLOSET HW EXISTING LOAD LIGHTING 700 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD REC TV ROOMS 727 -730 10 11 HALLWAY, CLOSET HW EXISTING LOAD LIGHTING 1000 20 1 C 20 1 720 RECEPTACLES EXISTING LOAD REC TV ROOMS 727 -730 12 13 PATIENT RM 729 REC NOTE 1 RECEPTACLES 720 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 14 15 PATIENT RM UC REFRIG NOTE 1 RECEPTACLES 500 20 1 B 20 1 0 SPARE EXISTING LOAD SPARE 16 17 SPARE SPARE 0 20 1 C 20 1 360 RECEPTACLES EXISTING LOAD REC RM 725 BATH 18 19 REC RM 726 EXISTING LOAD RECEPTACLES 360 20 1 A 20 1 510 MOTOR LOADS NOTE 1 PT RM FAN CO 729 20 21 REC RM 725 EXISTING LOAD RECEPTACLES 540 20 1 B 20 1 400 MOTOR LOADS EXISTING LOAD PT RM FAN CO 702 -707 22 23 REC RM 726 EXISTING LOAD RECEPTACLES 360 20 1 C 20 1 400 MOTOR LOADS EXISTING LOAD PT RM FAN CO 701 -704 24 25 REC RM 724 EXISTING LOAD RECEPTACLES 720 20 1 A 20 1 400 MOTOR LOADS EXISTING LOAD PT RM FAN CO 703 -706 26 27 CLEAN UTILITIY HD NU EXISTING LOAD RECEPTACLES 540 20 1 B 20 1 360 RECEPTACLES EXISTING LOAD REC RM 724 BATH 28 29 SPARE EXISTING LOAD SPARE 0 20 1 C 20 1 0 SPARE EXISTING LOAD SPARE 30 31 HEAD NURSE SINK ❑FFI EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 0 SPARE EXISTING LOAD SPARE 32 33 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 34 35 SPACE 0 0 1 C 0 1 0 SPARE SPACE 36 37 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 0 1 0 SPARE SPACE 38 39 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 40 41 SPACE i 0 0 1 C 0 1 0 RECEPTACLES EXISTING LOAD SPACE 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 15.31 42. 5 X A -N 5590, 4 46.6 CONNECTED 36.72 TOTAL DEMAND 7. 15 19. 8 X B -N 4980. 0 41. 5 DEMAND 15. 71 TOTAL DESIGN 7.67 21. 3 x C -N 4740. 0 39.5 DESIGN 16.23 NOTE 1i PROVIDE NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE, PROVIDE 2 #12, 1 #12G IN 3/4'C• PANED 7L4 ❑C DEVICE TYPE: Breaker ENCLOSURE; NEMA 1 MAINS(A); ML❑ CONTINUOUS(A); 225 LOCATIONS 7TH FLOOR DEVICE FAMILY] Bolt On MOUNTING, Surface WIRINGi 3 -Phase 4 -Wire AIC RATING(A), 10000 FED FROM: XFSC 500KVA VOLTAGE; 208/120 FAULT CURRENT(A): 6361 EXISTING PANEL CKT DESCRIPTI ❑N NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTION CKT C CODE AMPS P AMPS P 0 CODE C 1 RM 703 -706 EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 540 RECEPTACLES EXISTING LOAD RM 703 -706 2 3 RM 702 -705 EXISTING LOAD RECEPTACLES 720 20 1 B 20 1 720 RECEPTACLES EXISTING LOAD RM 702 -705 4 5 RM 701 -704 EXISTING LOAD RECEPTACLES 540 20 1 C 20 1 540 RECEPTACLES EXISTING LOAD RM 701 -704 6 7 REC RM 727 -730 EXISTING LOAD RECEPTACLES 540 20 1 A 0 1 0 SPARE EXISTING LOAD SPARE 8 9 REC RM 727 -730 EXISTING LOAD RECEPTACLES 360 20 1 B 0 1 0 SPARE SPARE 10 11 NURSERY RECEPTACLE EXISTING LOAD RECEPTACLES 540 20 1 C 20 1 1080 RECEPTACLES EXISTING LOAD PATIENT ROOM 729 12 13 ROOM 728,731 REC EXISTING LOAD RECEPTACLES 720 20 1 A 0 1 0 SPARE EXISTING LOAD SPARE 14 15 HALLWAY REC EXISTING LOAD RECEPTACLES 360 20 1 B 0 1 0 SPARE EXISTING LOAD SPARE 16 17 SPARE SPARE 0 0 1 C 0 1 0 SPARE EXISTING LOAD SPARE 18 19 FC UNIT 727 -728 EXISTING LOAD RECEPTACLES 500 20 1 A 0 1 0 SPARE EXISTING LOAD SPARE 20 21 FC UNIT 724 -725 EXISTING LOAD RECEPTACLES 500 20 1 B 20 2 780 RECEPTACLES EXISTING LOAD EXISTING LOAD 22 23 SPARE SPARE 0 0 1 C '" 780 SPARE "' 24 25 EXISTING LOAD EXISTING LOAD RECEPTACLES 728 20 2 A 30 2 1560 RECEPTACLES EXISTING LOAD EXISTING LOAD 26 27 " ' SPARE 728 "' B 20 1 1560 RECEPTACLES EXISTING LOAD N. CARE NORTH WALL 28 29 EXISTING LOAD EXISTING LOAD RECEPTACLES 2600 60 2 C 20 2 936 RECEPTACLES EXISTING LOAD EXISTING LOAD 30 31 "' EXISTING LOAD RECEPTACLES 2600 "" A "" 936 RECEPTACLES EXISTING LOAD ON 32 33 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 34 35 SPACE 0 0 1 C 0 1 0 SPARE SPACE 36 37 SPACE EXISTING LOAD RECEPTACLES 0 0 1 A 0 1 0 SPARE SPACE 38 39 SPACE EXISTING LOAD RECEPTACLES 0 0 1 B 0 1 0 RECEPTACLES EXISTING LOAD SPACE 40 41 SPACE i 0 0 1 C 0 1 0 RECEPTACLES EXISTING LOAD SPACE 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 21, 41 59, 4 x A -N 8693. 9 72. 4 CONNECTED 21. 41 TOTAL DEMAND 8.56 23. 8 )K B -N 5793.8 48. 2 DEMAND 8. 56 TOTAL DESIGN 8.56 23. 8 )K C -N 7194, 2 59.9 DESIGN 8. 56 NOTE 11 PR ❑VIDE NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE. PR ❑VIDE 2 #12, 1 #12G IN 3/4'C, PANED 7E1 ❑C DEVICE TYPE: Breaker ENCLOSURE: NEMA 1 MAINS(A); ML❑ C❑NTINUOUS(A)i 225 LOCATION: 7TH FLOOR DEVICE FAMILYi Bolt On M❑UNTINGi Flush WIRINGi 3 -Phase 4 -Wire AIC RATING(A)i 10000 FED FROMi PNL 2DLE VOLTAGE+ 208/120 FAULT CURRENT(A)i 4702 EXISTING PANEL CKT DESCRIPTI ❑N NOTES DEMAND VA ❑C PHASE ❑C VA DEMAND NOTES DESCRIPTI ❑N CKT C CODE AMPS P AMPS P 0 CODE C 1 STORAGE RM EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 800 LIGHTING EXISTING LOAD LTS ROOMS 724 -726 2 3 NURSE STATI ❑N LTS EXISTING LOAD LIGHTING 900 20 1 B 20 1 900 LIGHTING EXISTING LOAD LTS ROOMS 723 -727 4 5 SPARE 0 CO SPARE 0 20 1 C 20 1 200 RECEPTACLES EXISTING LOAD PYXIS 6 7 SPARE SPARE 0 20 1 A 20 1 540 RECEPTACLES EXISTING LOAD RECEPTACLES 8 9 SPARE SPARE 0 20 1 B 20 1 0 SPARE SPARE 10 11 RM 701 -704, 707 -710 EXISTING LOAD LIGHTING 1000 20 1 C 20 1 1040 LIGHTING EXISTING LOAD ROOM 723- 726 -729 12 13 RM 703 - 706 - 709 -712 EXISTING LOAD LIGHTING 900 20 1 A 20 1 1000 LIGHTING EXISTING LOAD ROOM 724 -727 14 15 RM 702- 705 - 708 -711 EXISTING LOAD LIGHTING 900 20 1 B 20 1 800 LIGHTING EXISTING LOAD ROOM 714 - 715 - 722 -725 16 17 NURSE STATION 728 -73 RECEPTACLES 720 20 1 C 20 1 900 LIGHTING EXISTING LOAD ROOM 719 -731 18 19 SPARE SPARE 0 20 1 A 20 1 700 LIGHTING EXISTING LOAD ROOM 713 20 21 SPARE SPARE 0 20 1 B 20 1 540 RECEPTACLES EXISTING LOAD STORAGE ROOM 22 23 SPARE SPARE 0 20 1 C 20 1 0 SPARE SPARE 24 25 VENTILATOR RM 707 EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 0 SPARE SPARE 26 27 SPARE ' SPARE 0 20 1 B 20 1 540 RECEPTACLES EXISTING LOAD N. CARE NORTH WALL 28 29 COPY MACHINE EXISTING LOAD RECEPTACLES 500 20 1 C 20 1 720 RECEPTACLES EXISTING LOAD N. CARE S❑UH WALL 30 31 VENTILATOR RM 707 EXISTING LOAD RECEPTACLES 540 20 1 A 20 1 540 RECEPTACLES EXISTING LOAD N. CARE EAST WALL 32 33 EXISTING LOAD EXISTING LOAD RECEPTACLES 780 20 2 B 20 1 540 RECEPTACLES EXISTING LOAD VENTILATOR RM 722 34 35 11 780 "' C 20 1 0 SPARE SPARE 36 37 GLUC ❑METER EXISTING LOAD RECEPTACLES 400 20 1 A 20 1 0 SPARE SPARE 38 39 NURSE ROOM REC EXISTING LOAD RECEPTACLES 360 20 1 B 20 1 600 RECEPTACLES EXISTING LOAD REFRIGERAT ❑R 40 41 SPACE i 0 0 1 C 20 1 540 RECEPTACLES EXISTING LOAD NURSE ROOM REC 42 ALL CONNECTED KVA 3P AVE,AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 19.76 54. 8 X A -N 6500. 0 54. 1 CONNECTED 19. 76 TOTAL DEMAND 7. 90 21. 9 X B -N 6874. 8 57.2 DEMAND 7.90 TOTAL DESIGN 8. 89 24, 7 X C -N 6415.8 53.4 DESIGN 8. 89 "ITY OF SOUili riiANI-i ELECTRICAL SECTION APPROVED BY: �5 GATE' I 1 J J 0 • 0 DC Q aC Q Z C) rn n co q us �- a oi 0 UM M M .J LL WW J W TLL i 04 N N W H U? m d J NO m Q U 2 w 0 C3 M 1 0 ca cO�M t Oto doff , NLh oo E I T co op 8 04 c:) (QOM p>� cn � T L N O EN N p =M '- N I a5 12 r -0 00o m � ca �+ y r N a) d o 2 JAY W EQVQ I LLn0 LL a.MF- Comm. No: 08061 Date: 07/07/08 Drawn: Revised: C SO) ■O 4W C 0 C � O Y� LL .- E Cd a .F+ _cc 0 CO 0 0 m E ..1.. ai ■_ E co 0 cis M cl) v/ 0 LM 0 a. 0 a C/) > 04 co 0 V Comm. No: 08061 Date: 07/07/08 Drawn: Revised: -o y 2008 HARVARD JOLLY, Ilya E4.00