08-957-014MECHANICAL SPECIFICATIONS 1. MECHANICAL GENERAL CONDITIONS A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. THIS SHALL INCLUDE ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK COMPLETE IN ALL ASPECTS AND READY FOR OPERATION. ALL WORK BY THIS CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES, THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), THE ENVIRONMENTAL PROTECTION AGENCY (EPA) AND THE LOCAL AUTHORITIES HAVING JURISDICTION. B. CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS. SUBMISSION OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. C. CCRD PARTNERS HAS NOT PERFORMED ANY ASBESTOS INSPECTION AND IS NOT AWARE OF, NOR WILL BE RESPONSIBLE FOR, ANY ASBESTOS RELATED ITEMS. ASBESTOS RELATED ITEMS WILL BE HANDLED UNDER A SEPARATE CONTRACT WITH THE BUILDING OWNER. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNERS ASBESTOS ABATEMENT CONTRACTOR FOR TESTING AND REMOVAL PRIOR TO ANY ACTUAL CONSTRUCTION. D. ALL PERSONS PROPOSING TO SUBMIT QUOTATIONS FOR THIS PROJECT IN ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS ARE EXPECTED TO VISIT THE SITE OF THE WORK COVERED BY THE DOCUMENTS AND ARE TO FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS AS THEY AFFECT THE PROJECT. CLAIMS RESULTING FROM A FAILURE TO VISIT THE SITE OR INSPECT THE EXISTING CONDITIONS WILL NOT BE CONSIDERED. E. ADJACENT AREAS OF THE BUILDING WILL BE OCCUPIED DURING THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL VERIFY WITH THE OWNERS REPRESENTATIVE FOR ACCESS TO THESE AREAS SHOULD THE NEED ARISE. SYSTEM SHUTDOWNS WILL REQUIRE SCHEDULING WITH THE OWNERS REPRESENTATIVE. F. NEW MATERIALS AND EQUIPMENT FURNISHED UNDER THIS CONTRACT SHALL BEAR THE U.L LABEL WHERE APPLICABLE, UNLESS NOTED OTHERWISE. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND ACCEPTANCE BY THE OWNER. G. DRAWINGS ARE DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL RUNS AND LOCATIONS OF PIPING, EQUIPMENT AND FIXTURES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL COORDINATION OF TRADES WITH EXISTING STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL AND SPRINKLER SYSTEMS AND PROVIDING NECESSARY OFFSETS, TRANSITIONS, PIPE REROUTING, MATERIALS AND LABOR TO ARRANGE EQUIPMENT, DUCTWORK AND PIPING AS REQUIRED FOR A PROPER AND ACCESSIBLE INSTALLATION. CLOSE COORDINATION WILL BE REQUIRED FOR ALL SERVICES ABOVE CEILING. H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS IN CASE OF DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT/ENGINEER AND THE OWNER IN WRITING OF SUCH DIFFERENCE. SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR "OR EQUAL' APPROVAL BY THE ENGINEER. WHERE MORE THAN ONE MANUFACTURER IS LISTED IN THE NOTES do EQUIPMENT SPECIFICATIONS, ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR APPROVAL J, SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED AT NO COST TO THE OWNER. K. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND EXISTING EQUIPMENT REQUIRING OPERATION AND /OR MAINTENANCE RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT OPERATION OR MAINTENANCE IS NOT RESTRICTED. L DO NOT RUN PIPING OR DUCTWORK, OR LOCATE EQUIPMENT, WITH RESPECT TO SWITCHBOARDS, PANEL BOARDS, POWER PANELS, MOTOR CONTROL CENTERS OR DRY TYPE TRANSFORMERS, WITHIN 42 INCHES IN FRONT OF EQUIPMENT, OVER EQUIPMENT, OR WITHIN 36 INCHES HORIZONTALLY OF SAME SPACE. M. CODES AND STANDARDS THE MECHANICAL SYSTEM INSTALLATION SHALL BE IN FULL COMPLIANCE WITH THE FOLLOWING CODES AND STANDARDS: 1. STATE, COUNTY, AND CITY HEALTH AND BUILDING CODES. 2. NFPA 51B, 1999 EDITION. 3. NFPA 70, 2002 EDITION. 4. NFPA 72, 2002 EDITION. 5. NFPA 90A, 2002 EDITION. 6. NFPA 99: STANDARD FOR HEALTH CARE FACILITIES, 2002 EDITION. 7. NFPA 101, LIFE SAFETY CODE, 2003 EDITION. B. FLORIDA BUILDING CODE, BUILDING 2004 EDITION WITH 2006 SUPPLEMENTS 9. FLORIDA BUILDING CODE, MECHANICAL 2004 EDITION WITH 2006 SUPPLEMENTS 10. FLORIDA BUILDING CODE, PLUMBING 2004 EDITION WITH 2006 SUPPLEMENTS 11. OTHER REFERENCED NFPA CODES. 12. ANSI A117.1- 1992 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES. 13. THE AMERICANS WITH DISABILITIES ACT(ADA), ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES -1991. 14. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTH CARE FACILITIES (GUIDELINES 2006 EDITION) 15. NFPA 13, 2002 EDITION. 16. FLORIDA FIRE MARSHALL'S RULE CHAPTER 69A -3.012 17. FLORIDA ADMINISTRATIVE CODE (FAC ADOPTED AUGUST 8, 2005) >a 2. MECHANICAL DEMOLITION A. THE WORK OF THIS SECTION SHALL INCLUDE FURNISHING ALL LABOR AND MATERIAL FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING PIPING, DUCTWORK, AND EQUIPMENT AS INDICATED ON THE DRAWINGS. B. CONTRACTOR SHALL VERIFY ALL EXISTING FIELD CONDITIONS IN ORDER TO ACCURATELY COORDINATE LIMITS OF DEMOLITION WITH NEW WORK FOR THIS AREA. EXISTING DUCTWORK AND PIPING SHOWN ON PLANS MAY NOT EXACTLY MATCH THE ACTUAL FIELD CONDITIONS. IT IS NOT NECESSARY TO REWORK THE EXISTING DUCTWORK OR PIPING TO MATCH WHAT IS DEPICTED ON THE PLANS. CONTRACTOR SHALL VERIFY EXISTING DUCTWORK AND PIPE ROUTING AND LOCATIONS AND MAKE ADJUSTMENTS AS REQUIRED TO AVOID CONFLICTS. C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING SCRAP MATERIALS AND DEBRIS ASSOCIATED WITH THIS WORK FROM THE SITE. ASCERTAIN AS TO WHAT MATERIAL OR EQUIPMENT IS TO REMAIN IN POSSESSION OF THE OWNER. D. ALL EQUIPMENT, DUCTWORK, ETC. DESIGNATED FOR REMOVAL; SHALL INCLUDE ALL HANGERS, SUPPORTS AND APPURTENANCES. ANY SERVICE NOT TOTALLY REMOVED OR REUSED SHALL BE CAPPED, SEALED, OR OTHERWISE TERMINATED IN AN ACCEPTABLE MANNER. E. SELECT TOOLS AND EQUIPMENT APPROPRIATE TO THE SCALE AND SIZE OF CONSTRUCTION. AVOID USE OF NOISE PRODUCING EQUIPMENT WHEN POSSIBLE. F. REMOVE DUCTWORK, AND EQUIPMENT WHERE INDICATED ON THE DRAWINGS OR WHERE REMOVAL IS REQUIRED FOR COMPLETION OF NEW WORK UNDER THIS CONTRACT. G. TAKE ALL NECESSARY PRECAUTIONS TO PROTECT THE EXISTING STRUCTURE, ITS CONTENTS AND AREAS OF THE SITE NOT WITHIN CONSTRUCTION LIMITS; TAKE ANY MEASURES NECESSARY TO PROTECT PERSONNEL FROM THE HAZARDS OF CONSTRUCTION. H. WHERE EXISTING MATERIALS OR ASSEMBLIES ARE TO BE REMOVED, MODIFIED OR OTHERWISE INCORPORATED IN THE WORK, TAKE CARE TO PREVENT DAMAGE. PROVIDE TEMPORARY PROTECTION WHERE NEW OR EXISTING OPENINGS IN ROOF OR WALLS ARE REQUIRED. I. WHERE FINISHES ARE INDICATED TO BE PATCHED OR REPAIRED, PERFORM DEMOLITION WORK WITH CARE TO PREVENT DAMAGE TO SURROUNDING AREAS AND TO FACILITATE THE PATCHING AND REPAIRING WORK. 3. PRODUCTS, EQUPMENT AND EXECUTION A. CEILING SUPPLY OUTLETS, GRILLES AND REGISTERS SHALL BE PROVIDED AS SCHEDULED ON THE DRAWINGS BY TITUS, METALAIRE, KRUGER, OR EQUAL B. PROVIDE COMPOSITE INSULATION (INSULATION JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVE) WITH FLAME- SPREAD RATINGS OF 25 OR LESS AND A SMOKE - DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM K04 (HFFA 255) METHOD. C. MAINTAIN INTEGRITY OF VAPOR BARRIER JACKETS ON PIPE AND DUCTWORK INSULATION, AND PROTECT TO PREVENT PUNCTURE OR OTHER DAMAGE SEAL OPEN ENDS OF INSULATION WITH MASTIC. SECTIONALLY SEAL ALL BUTT ENDS WITH WHITE VAPOR BARRIER COATING. EXTEND INSULATION WITHOUT INTERRUPTION THROUGH WALLS, FLOORS AND SIMILAR PIPING PENETRATIONS, EXCEPT WHERE OTHERWISE INDICATED. D. FURNISH AND INSTALL SMOKE, FIRE AND /OR FIRE /SMOKE DAMPERS WHERE SHOWN ON THE DRAWINGS, AND REQUIRED BY THE GOVERNING AUTHORITY. DAMPERS SHALL BE INSTALLED AS RECOMMENDED BY SMACNA AND COMPLY WITH U.L AND LOCAL ORDINANCES AS REQUIRED BY THE GOVERNING AUTHORITY. E HOT WATER PIPING SHALL BE AMERICAN MANUFACTURED SCHEDULE 40 BLACK STEEL OR TYPE "L" COPPER PIPE IN ACCORDANCE WITH THE FOLLOWING: 1. 2 -1/2" AND SMALLER: STANDARD WEIGHT, BLACK STEEL (AMERICAN MANUFACTURED) PIPE WITH BLACK MALLEABLE IRON SCREWED FITTINGS OR TYPE 'L' COPPER WITH WROUGHT COPPER FITTINGS ASSEMBLED WITH 95/5 SOLDER. F. PIPE, EQUIPMENT, ETC., SHALL BE PROPERLY SUPPORTED FROM STRUCTURE WITH THE USE OF APPROVED TYPE CLEVIS, TRAPEZE HANGERS OR FLOOR STANDS WITH SPACING AS FOLLOWS: 1. STEEL PIPE OR COPPER TUBING - 1 -1/2" OR LESS, 6 FOOT INTERVALS. 2. FITTINGS - WITHIN 2' -0" OF EACH CHANGE OF DIRECTION. 2 -1/2" AND SMALLER: STANDARD WEIGHT, BLACK STEEL (AMERICAN MANUFACTURED) PIPE WITH BLACK MALLEABLE IRON SCREWED FITTINGS OR TYPE 'L' COPPER WITH WROUGHT COPPER FITTINGS ASSEMBLED WITH 95/5 SOLDER. G. PROVIDE AND INSTALL UNIONS AT PROPER POINTS TO PERMIT REMOVAL OF A PIPE, EQUIPMENT, ETC., WITHOUT INJURY TO OTHER PARTS OF THE SYSTEM AND TO PREVENT CORROSION DUE TO ELECTROLYSIS. ALL EQUIPMENT SHALL BE INSTALLED IN A MANNER TO PERMIT ACCESS FOR SERVICE WITHOUT DISASSEMBLY. UNIONS SHALL BE DIELECTRIC WHERE DISSIMILAR MATERIALS OCCUR. PRESSURE RATINGS SAME AS FITTINGS. H. MAINTAIN INTEGRITY OF VAPOR BARRIER JACKETS ON PIPE AND DUCTWORK INSULATION, AND PROTECT TO PREVENT PUNCTURE OR OTHER DAMAGE. SEAL OPEN ENDS OF INSULATION WITH MASTIC. SECTIONALLY SEAL ALL BUTT ENDS OF CHILLED WATER INSULATION OF FITTINGS WITH WHITE VAPOR BARRIER COATING. EXTEND PIPING INSULATION WITHOUT INTERRUPTION THROUGH WALLS, FLOORS AND SIMILAR PIPING PENETRATIONS, EXCEPT WHERE OTHERWISE INDICATED. INSTALL PROTECTIVE METAL SHIELDS AND FOAM GLASS INSERTS WHERE PIPE HANGERS BEAR ON OUTSIDE OF INSULATION. I. ISOLATION VALVES FOR HEATING HOT WATER SYSTEM SHALL BE EQUAL TO MILWAUKEE "BUTTERBALL" OR NIBCO BALL VALVES AND PROVIDED AT EACH PIECE OF EQUIPMENT. PROVIDE AUTO AIR VENTS IN HEATING WATER PIPING WHERE HIGH POINTS OCCUR. 4. DUCTWORK AND ACCESSORIES A. RECTANGULAR 'LOW PRESSURE" SHEET METAL DUCT SHALL BE GAUGE STEEL SHEETS AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS FOR 1.0' W.C. (DUCTS FOR MEDICAL WORK FABRICATED OF CONTINUOUS HOT DIP MILL GALVANIZED MINIMUM 26 SHALL NOT BE LINED, BUT WILL BE WRAPPED WITH INSULATING MATERIAL) B. 'LOW PRESSURE' DUCT FITTINGS SHALL BE FABRICATED OF CONTINUOUS HOT DIP MILL GALVANIZED MINIMUM 26 GAUGE STEEL SHEETS AND INSTALLED IN ACCORDANCE WITH SMACNA RECOMMENDATIONS FOR 0.5" W.C. C. RECTANGULAR SHEET METAL DUCT AND FITTINGS SHALL BE FABRICATED OF FITTINGS SHALL BE FABRICATED OF CONTINUOUS HOT DIP MILL GALVANIZED MINIMUM 26 GAUGE STEEL SHEETS AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS FOR 3.0' W.C. (DUCTS FOR MEDICAL WORK SHALL NOT BE LINED, BUT WILL BE WRAPPED). CONSTRUCTION METHODS: 1. RECTANGULAR - DUCT MATE SYSTEM 2. ROUND - SPIRAL DUCT SYSTEM, METAL INNER LINER D. RECTANGULAR DUCTS SHALL BE INSULATED WITH 3/4 POUND PER CUBIC FOOT MINIMUM DENSITY, 2" THICK, COMMERCIAL GRADE, OWENS - CORNING FIBERGLASS FOIL BACKED ALL SERVICE DUCT WRAP, OR EQUAL E. FLEXIBLE DUCTS SHALL BE METAL FLEX. INNER DUCT LINER FOR ALL DUCTS TO BE METAL FLEXIBLE DUCTS SHALL BE LISTED AS U.L 181 CLASS (1) AIR DUCT AND SHALL COMPLY WITH NFPA STANDARDS 90A AND 90B. F. CONTRACTOR SHALL BALANCE THE HVAC SYSTEMS FOR DESIGNATED AIR CFM QUANTITIES AND SHALL BE N.E.B.B. OR A.A.B.C. APPROVED. SUBMIT REPORT ON NEBB, AABC, OR SMACNA FORMS FOR APPROVAL BY THE ENGINEER. EXTENT OF BALANCING WORK TO INCLUDE RE BALANCING OF EXISTING SUPPLY RETURN AND EXHAUST SYSTEMS AS REQUIRED TO ACHIEVE DESIGN CFM ON SUBJECT PROJECT. CONTRACTOR SHALL INSTALL MECHANICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES. G. DUCT ACCESS DOORS: PROVIDE RIGID AND CLOSE FITTING DOORS OF GALVANIZED STEEL WITH SEALING GASKETS AND QUICK FASTENING LOCKING DEVICES. FOR INTERNALLY LINED OR INSTALLED DUCTWORK, INSTALL MINIMUM ONE INCH THICK INSULATION WITH SHEET METAL COVER. INSTALL AT EACH FIRE DAMPER. DOORS TO BE EQUAL TO FLEX MASTER 'THE INSPECTOR SERIES.' H. DUCT PENETRATIONS THROUGH FIRE/SMOKE RATED PARTITIONS /WALLS SHALL BE SEALED WITH FIRE RATED SEALANT WHICH SHALL MAINTAIN THE RATED INTEGRITY OF THE WALL WHERE DUCTS PENETRATE FIRE WALLS OR PARTITIONS, FIRE DAMPERS SHALL BE INSTALLED IN THE CONSTRUCTION IN A MANNER DIRECTED BY THE MANUFACTURER OF THE DAMPERS. WHERE DUCTS ARE NOT RATED AS FIRE WALLS, INSTALL 1 -1/2 x 1 -1/2 ANGLE COMPLETELY FRAMING THE OPENING ON FOUR SIDES. J. DUCT SUPPORTS: SUPPORT HORIZONTAL DUCTWORK ON HANGERS AT INTERVALS OF NOT MORE THAN 8' APART. ATTACH HANGERS TO OVERHEAD STRUCTURE WITH THE USE OF APPROVED STRUCTURAL INSERTS AND SUPPORT HARDWARE SUPPORT HARDWARE SHALL COMPLY WITH MSS SP -69 SPECIFICATIONS. C- CLAMPS SHALL NOT BE ALLOWED. DUCT HANGER STRAPS AND SUPPORT RODS SHALL COMPLY WITH SMACNA STANDARDS. 5. DUCT INSULATION A. ALL SHEET METAL DUCTWORK SHALL BE EXTERNALLY INSULATED. WITH 2' THICK FIBERGLAS DUCT WRAP HAVING A 0.25K FACTOR 0 75' F. B. THE CONTRACTOR SHALL PROVIDE COMPLETE SUBMITTALS ON ALL INSULATION MATERIALS TO BE PROVIDED. C. ACCEPTABLE MANUFACTURERS: OWENS- CORNING, JOHNS - MANVILLE, MANSON (CERTAIN TEED), KNAUFF OR EQUAL D. WRAP FLEXIBLE FIBERGLASS INSULATION AROUND DUCTS AND SECURE WITH OUTWARD - CLINCHING STAPLES. ADDITIONALLY, DUCTS 24 INCHES WIDE AND LARGER SHALL SECURE INSULATION WITH STICK CUPS ON 18" CENTERS. LAP INSULATION A MINIMUM OF FOUR (4) INCHES, AND SEAL SEAMS AND PENETRATIONS WITH AN APPROVED MASTIC REINFORCED WITH THREE (3) INCHES OF GLASS MESH REINFORCEMENT, OR THREE (3) INCHES FOIL/VAPOR- BARRIER TAPE SEAL RAW GLASS TO DUCT WHERE INSULATION TERMINATES. SEAL ALL LAPS AND PENETRATIONS IN VAPOR BARRIER JACKET WITH AN APPROVED VAPOR BARRIER MASTIC. E. BUTT INSULATION TOGETHER AND SECURELY STAPLE IN PLACE WITH OUTWARD - CLINCHING STAPLES ON 3" CENTERS. INSTALL FACTORY- FURNISHED LAPS AT THE BUTT JOINTS. NEATLY BEVEL AND FINISH INSULATION WHERE IT TERMINATES. SEAL ALL LAPS AND PENETRATIONS IN VAPOR BARRIER JACKET WITH AN APPROVED VAPOR BARRIER MASTIC. USE OF DOUBLE TAPE SELF - SEAUNG ADHESIVE SYSTEMS WILL NEGATE REQUIREMENT FOR STAPLES. F. PROVIDE COMPOSITE INSULATION (INSULATION JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVE) WITH FLAME- SPREAD RATINGS OF 25 OR LESS AND A SMOKE - DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM K04 (HFFA 255) METHOD. -71 --- ----- 02121 Porce de Leon BF d., Suit6 350 Coral Gab- les,-FL 33 1,34 - -- - - - -- phone: 305.569.1692 Professional Consulting Engineers fax: 305.569.1693 Dallas . Houston . Nashville . Miami , Richmond ccrd project number: 408283 EB00007658 6. PIPE INSULATION A. INSULATION SHALL BE PROTECTED AT HANGERS BY A SECTION OF CALCIUM SILICATE PIPE INSULATION AND A 12" LONG HALF -ROUND SHEET METAL SHIELD ON THE OUTSIDE OF THE INSULATION. EXTEND PIPING INSULATION FULL THICKNESS WITHOUT INTERRUPTION THROUGH WALLS, FLOORS AND SIMILAR PENETRATIONS. B. HOT WATER PIPING SHALL BE INSULATED WITH OWENS - CORNING ASJ- SSL -II OR APPROVED EQUAL 1 X " THICK FOR HOT WATER PIPE INSULATION. FITTINGS AND VALVES SHALL BE FINISHED WITH WHITE 25/50 PVC COVERS OVER MOLDED INSULATION FITTINGS. ALL JOINTS AND LAPS SHALL BE VAPOR SEALED. C. PROVIDE INSULATION PRODUCTS MANUFACTURED BY JOHNS- MANVILLE, OWENS- CORNING, ARMSTRONG AND CERTAINTEED. FIBERGLASS PIPE INSULATION SHALL BE ASTM C547 -77, CLASS 1. PROVIDE BANDS, WIRES, AND CEMENT AS RECOMMENDED BY INSULATION MANUFACTURER FOR THE APPLICATIONS INDICATED. FLEXIBLE FIBERGLASS DUCTWORK INSULATION SHALL BE ASTM C553 -70, TYPE I, CLASS B3. D. PROVIDE COMPOSITE INSULATION (INSULATION JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVE) WITH FLAME- SPREAD RATINGS OF 25 OR LESS AND A SMOKE - DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM K04 (HFFA 255) METHOD. 7. TEMPERATURE CONTROLS A. ALL TEMPERATURE CONTROLS NECESSARY FOR THE RENOVATION AND FINISH -OUT OF THE SPACE SHALL COMPLY TO THE BASE BUILDING SYSTEM AND CONTROL SPECIFICATIONS. BUILDING STANDARD CONTROL SYSTEM COMPONENTS SHALL BE UTILIZED. B. NEW THERMOSTATS OR SENSORS IF REQUIRED SHALL MATCH THE EXISTING THERMOSTATS OR SENSORS. C. ALL CONTROL HARING AND POWER HARING FOR CONTROLS SHALL BE BY THE CONTROLS SUB - CONTRACTOR. D. AT THE COMPLETION OF CONSTRUCTION, ALL NEW AND EXISTING THERMOSTATS AND SENSORS SHALL BE CALIBRATED. 8. TEST AND BALANCE A. THE GENERAL CONTRACTOR SHALL RETAIN THE SERVICES OF AN INDEPENDENT CERTIFIED AIR BALANCE FIRM TO PERFORM THE FINAL TESTING AND BALANCING AND PREPARE REPORTS. IF THE MECHANICAL CONTRACTOR IS NEBB CERTIFIED, THEY CAN BALANCE THE SYSTEM. B, TESTING AND BALANCING SHALL BE PERFORMED IN ACCORDANCE WITH THESE SPECIFICATIONS AND IN ACCORDANCE WITH THE ASSOCIATED AIR BALANCE COUNCIL NATIONAL STANDARDS FOR FIELD MEASUREMENT AND INSTRUMENTATION, SECOND EDITION, 1974, OR NATIONAL ENVIRONMENTAL BALANCING BUREAU STANDARDS. C. THE CONTRACTOR SHALL BALANCE ALL EQUIPMENT INCLUDING NR DEVICES AND VERIFY ALL CONTROLS. RESPONSIBILITIES, BALANCE SUPPLY AIR AND RETURN AIR GRILLS, REGISTERS, ETC. D. READINGS AND TEST OF DIFFUSERS, GRILLES AND REGISTERS SHALL INCLUDE DESIGN, INITIAL TEST, AND FINAL ADJUSTED FPM VELOCITY AND CFM. ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE BALANCED BY A HOOD THAT HAS BEEN CALIBRATED, INCLUDING A MANOMETER, AND PILOT TUBE READINGS SHALL BE TAKEN TO ESTABLISH TOTAL CFM FLOW IN ALL MAIN DUCTS. 9. RECORDS FOR OWNER A. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS ON THE JOB, NOTING DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW AND UNCOVERED EXISTING UTILITIES AND SHALL, WITH HIS REQUEST FOR FINAL PAYMENT, TURN OVER A CLEAN, SET OF r SCALED SET OF DRAWINGS (ONE SET OF PLOTS AND ONE CD) SHOWING 'AS INSTALLED" WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER. CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET AND LABEL 'AS- BUILTS" IN THE REVISION BLOCK ON THE DRAWINGS. CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF BLUE LINE PRINTS FROM THE 'AS- BUILTS ". B. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE. 2. APPROVED FIXTURE BROCHURES (ORIGINAL DATA, NO COPIES). 3. COPIES OF APPROVED SHOP DRAWINGS. 4. TEST AND BALANCE REPORTS REQUIRED BY THESE SPECIFICATIONS. 5. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING CONSTRUCTION. C. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS BEFORE FINAL INSPECTION. >- w C3 �, 00 0 X CL cri 0 Ucr, M • J LL W W O J W ❑ g LL N N W i■�i� m 0 J Q � m J W W 0 U 0 N o 2 .; o CC",' _ P_ m � ° 81 '- Mr- �o?N 8 0 ,6C ?c�07 -'' W o)NO19o0i MC U 0) � = W ioc�mtico=N rn � LL EN- ovEMCn cv 0 c 0 yv0o Co Z ENV r C7 _J U m ca EUQQ M ww -5OainFc° -a � 0 Comm. No: 08061 co 07/07/08 Drawn: Revised: T .O � C U. w E A a .0 _cc 0 co 0 C O E = O ._ n co v 0 E 0 as co M C0 CO) :3 0 O EL O C _ CID V Comm. No: 08061 Date: 07/07/08 Drawn: Revised: M4.00