08-823-003V
3
� I
Gk k• ARMOVERS GREATER THAN
24" IN LENGTH SHALL BE
Uj
®
rM
SUPPORTED BY A HANGER.
SCHEDULE
1. EXISTING DROP TO BE
REMOVED.
2. EXISTING BRANCHLINE.
3. 1" ARMOVER."
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
Typical Relocation Detail
NO SCALE
1 /2 ±1 /8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2 -7/8" DIA.
CPVC
(73,0 mm)
1/2" (12,7 mm)
2 -1/4" DIA.
1/4" (6,4 mm)
(57,2 mm)
DESIGN CRITERIA
tert,on Association, in aft-Pon to ttty
CLASSIFICATION:
MOUNTING
HAZARD:
PLATE
MAX. HEAD COVERAGE:
225
SCOPE OF WORK
ingpurisdBYlcm. failure to do so may
1/8"
39
ADDED FIRE SPRINKLERS:
15
OUTLETS PLUGGED:
(3,2 mm)
ALL MATERIALS: HEADS, PIPE AND HANGERS
ARE PER NFPA 13.
vices
LEGEND
SERIES
TY -FRB
1 -5/16" (33,3 mm)
1 -1/16" (27,0 mm)
■
Fire Sprinkler Pi in-1 Plan
=J SCALE-:1/8"=V-0"
N
LO
VERS GREATER THAN
-ENGTH SHALL BE
ID BY A HANGER.
SCHEDULE
2. EXISTING BRANCHLINE.
3. 1" ARMOVER.*
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
Typical Relocation Detail
NO SCALE
0.
SCHEDULE
1. NEW MECH -TYPE
TEE.
2. EXISTING BRANCHLINE.
3, ARMOVER.*
4. 1" DROP.
## ARMOVERS GREATER THAN 5, NEW FIRE SPRINKLER HEAD
24 IN LENGTH SHALL BE
SUPPORTED BY A HANGER.
ATTACH COUPONS FOR
FIELD INSPECTOR.
Typical Relocation Detail
NO SCALE
F59
v
0
POWDER ACTUATED
PIN 318' ALL THREAD ROD (ATR)
ATTACHED TO CONCRETE
WITH 3/8' POWDER ACTUATED
RN 3 3/8' ROD CPLQ (FOR
USE WITH 4' PIPE 3 S &LER).
GALVANIZED HANGER
RING.
Hanger Detail
No Scale
GENERAL NOTES
DESCRIPTION
CPVC
I XL
40
ALL PIPE TO BE:
ble staricUrds cl Me National Fire Pro
X
DESIGN CRITERIA
tert,on Association, in aft-Pon to ttty
CLASSIFICATION:
OFFICE
HAZARD:
LIGHT HAZARD
MAX. HEAD COVERAGE:
225
SCOPE OF WORK
ingpurisdBYlcm. failure to do so may
RELOCATED FIRE SPRINKLERS:
39
ADDED FIRE SPRINKLERS:
15
OUTLETS PLUGGED:
-
ALL MATERIALS: HEADS, PIPE AND HANGERS
ARE PER NFPA 13.
vices
LEGEND
EXISTING PIPE
- - - --
NEW PIPE
!
NEW HANGER
-�
NEW QUICK RESPONSE SPRINKLER
QQ
NEW ARMOVER
vices rn proper operating cond,f(cri.
TY1131 - Upright 2.8K, 112'NPT
V t
that which would otnerw�sh 'on ob.
The instalfrrtg coorraeror or s;"nnAletr
TY1231 - Pendent 2.81, 1/2'NPT
manufacturer should De contacted
FIRE PROTEC TION GENERAL NOTES
1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, AND ALL APPLICABLE.STATE �
AND LOCA; CODES.
2. ADHERE TCAND OBTAIN-ALL PERMITS, L10E.4SE3 AND GOVERNMENT f K
REQUIREMENTS. t
m
3. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE DEPARTMENT, AND
ARCHITECT /ENGINEER. '
5. CUTTING OF STRUCTURAL AND /OR ARCHITECTURAL MEMBERS TO BE DONE ONLY
WITH THE WRITTEN APPROVAL OF THE ARCHITECT.
6. PIPE ROUTING SHOWN SHALL BE USED AND ANY ADDITIONAL OFFSETS OR FITTINGS
REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES,
AND /OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY
EXISTING STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID
ANY /ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE P
ROUTING.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC. FLASH AND COUNTERFLASH ROOF PENETRATIONS. (SEE FIRE RATED PIPE
PENETRATION DETAIL).
8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON - ACCESSIBLE CEILINGS AND
CHASES.
9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL EXISTING /NEW DIFFUSERS,
SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS.
10. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN
ACCORDANCE WITH N.F.P.A. 13.
11. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN
ACCORDANCE WITH N.F.P.A. 13.
12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL
BE FACTORY MARKED "UL" AND "FM ", 175 WORKING PRESSURE.
13. ALL VALVES ON THE FIRE PROTECTION SYSTEM TO BE ELECTRICALLY
SUPERVISED. TYPE AND EXACT LOCATION OF FLOW, PRESSURE AND
SUPERVISORY SWITCHES SHALL FACTORY MARKED "UL" AND "FM ", 175 WORKING
PRESSURE.
14. ALL POWER WIRING SHALL BE ACCOMPLISHED UNDER THE ELECTRICAL DIVISION.
ALL CONTROL AND INTERLOCK WIRING SHALL BE ACCOMPLISHED UNDER THIS
SECTION OF THE SPECIFICATIONS IN ACCORDANCE WITH THE REQUIREMENTS IN
THE ELECTRICAL DIVISION. COORDINATE ALL ELECTRICAL ITEMS WITH ELECTRICAL
CONTRACTOR AND INSURE PROPER COORDINATION.
15. SPRINKLERS SHALL COVER THE ENTIRE AREA OF THE ROOM INCLUDING ALCOVES.
SPRAY SHALL NOT BE BLOCKED BY WALLS OR PARTITIONS.
16. ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4"
AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL
INTERSECTING SURFACE.
17. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY.
18. MAINTAIN A MINIMUM OF 18 INCHES FROM THE BOTTOM OF THE SPRINKLER
DEFLECTOR TO THE TOP OF STORAGE/FILE STORAGE.
19. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER
+ti[ ca" Fire & Building
Products
Technical Services: Tat, (800) 381.9312; Fax; (800) 79t -,500
Series TY -FRB - 2.8, 4.4 5.6, and 8.0 K- factor . 'r
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY -FREi, 2.8, 4 2,5 6, and
8.0 K- factor, Ulpright and Pendent
Sprinklers described in this data sheet
are quick respwse - standard cover-
age, decorative 3 mm glass bulb type
spray sprRnkters designed for use in
light or ordinary hazard, commercial
occupar,cfes such as banks, hotels,
shopping ma °Is, etc,
ta,lied whwn exposed to CorrcSive at-
mospheres. Alincugh corrosion resis-
tant Coaled spr,nk:ers have passed the
standard correslcer tests of the appli-
canle approval agencles, the testing is
not repretentabve of all pose bte cor-
ros've atmvspheray. Consequently, it
is •ecommerIcIM that the end user be
crn-ku lted with re! pest to th a suitability
o1 these aat,ngs for any given torro-
sive envwr"meni They effects of eimbi-
ent temperature, cc- ncentraticn cf
chernrcals, and {1Rs'chemcal velocity,
should be cons deted, as a minmum,
r.
s-
1' .a
eat
r
The recpsEed version of the Series along with the corrosive nature of the �
'TY•FRi Pendent Sprinkler, where ap•
pticable, is intended for use in areas
with a finished Ceiling It uses either a
two -piece Style 1D (112 inch UPT) or
Style 40 (1'4 inn NPT) Recessed Es-
cutcheon wile! 1-2 inch (12 >7 mm) of
recessed ad;ustneent or up to 314 inch
(19,1 mm) of total adjustment !torn the
gush poncent position, or a t.vo-p ectl
Style 2011/2 Incet NPTI or Style 30 (3,4
inch NPT) Recessed Escu%hec:t with
14 Inch (CA min) o1 recessed adiust-
chem -cal to which the sprnk'ers will be
exposed.
An intermediate level versions of the
Series TY -FRB Pendent Sprinklers
ato detailed In Technical Data Sheet
TFP356, and Sprinkler Guards we dei-
ta -ad in Te,-hn•ca, Data SheetTFP780
WARNINGS
The Series TY -FRB Spr;nVers de-
sctbed herein must by tnsfaned any
maintained in Compliance with this
r
v
ment or up to 1;2 Inch (12,7 rnm) of
documertt, as liwifas wftrt file apptcg-
Pendent 4.21, 112'14PT,- '
Uptight 5.6K, 1/2'NPT "'
total adjustment from the ttush pen-
ble staricUrds cl Me National Fire Pro
a.Y
dont positron. The rid ustment pro-
tert,on Association, in aft-Pon to ttty
TY4231 -
Pendent 8.0K. 3/4•NP7
videdby the Recessed25cutcrconre-
standards o /any other oulhonh29traV-
Model /Sprinkler,+ '�
dukes the accuracy to which the fixed
ingpurisdBYlcm. failure to do so may
pipe drops to the sprinkfers must be
Impair the performance ofthmde-
Identification
cut.
vices
Corrosion resistant coaLn where
gs•
'S r
The owner rs rc.,pons,b.st for mamfa�n-
Numbers
!
appricable, are utitim to extend the
ing their fie protW .ionsy stem and de.
.,
life of copper alloy sprinklers beyond
vices rn proper operating cond,f(cri.
TY1131 - Upright 2.8K, 112'NPT
V t
that which would otnerw�sh 'on ob.
The instalfrrtg coorraeror or s;"nnAletr
TY1231 - Pendent 2.81, 1/2'NPT
manufacturer should De contacted
TY2131 - Uprlght 42K 112'NPT•,
n,r9 any cations.
TY2231 -
TY3131 -
Pendent 4.21, 112'14PT,- '
Uptight 5.6K, 1/2'NPT "'
TY3231 -
Pendent 5.611, 112 -NPT
a.Y
TY4131 -
Upright 8.0K, 3/4•NPT
-
TY4231 -
Pendent 8.0K. 3/4•NP7
J
k
Y
1�
a.Y
J