08-823-002La
Fire Sprinkler Piping o Plan
SCALE: N.T.S
Fire Sprinkler Pi in "_l Plan
SCALE: /8 " =1' -0"
N
1 /2 ±1 /8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2 -7/8" DIA.
CPVC
(73,0 mm)
1/2" (12,7 mm)
2 -1/4" DIA.
1/4" (6,4 mm)
(57,2 mm)
DESIGN CRITERIA
CLASSIFICATION:
MOUNTING
HAZARD:
PLATE
MAX. HEAD COVERAGE:
225
SCOPE OF WORK
1/8"
RELOCATED FIRE SPRINKLERS:
39
ADDED FIRE SPRINKLERS:
16
(3,2 mm)
-
ALL MATERIALS: HEADS, PIPE AND HANGERS
ARE PER NFPA 13.
LEGEND
SERIES
TY FRB
1 -5/16" (33,3 mm)
1 -1 /16" (27,0 mm)
G 161
rzwA
r24" I I
ID, \ RS GREATER THAN
NGTH SHALL BE
D BY A HANGER.
SCHEDULE
1. EXISTING DROP TO BE
REMOVED.
2. EXISTING BRANCHLINE.
3. 1" ARMOVER.*
4. 1" DROP,
5. NEW FIRE SPRINKLER HEAD
Typical Relocation Detail
NO SCALE
W, r;]
'" .ARMOVERS GREATER THAN
24 IN LENGTH SHALL BE
SUPPORTED BY A HANGER.
ATTACH COUPONS FOR
FIELD INSPECTOR.
SCHEDULE
1. NEW MECH -TYPE
TEE.
2, EXISTING BRANCHLINE.
3. ARMOVER."
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
Typical Relocation Detail
NO SCALE
GENERAL NOTES
DESCRIPTION
CPVC
XL
40
ALL PIPE TO BE:
X
DESIGN CRITERIA
CLASSIFICATION:
OFFICE
HAZARD:
LIGHT HAZARD
MAX. HEAD COVERAGE:
225
SCOPE OF WORK
RELOCATED FIRE SPRINKLERS:
39
ADDED FIRE SPRINKLERS:
16
OUTLETS PLUGGED:
-
ALL MATERIALS: HEADS, PIPE AND HANGERS
ARE PER NFPA 13.
LEGEND
EXISTING PIPE
- - - -
NEW PIPE
NEW HANGER
-�-
NEW QUICK RESPONSE SPRINKLER
NEW ARMOVER
�--f -Q
No. Date Revisions By Water Supply Information Design Criteria Sprinklers/ Spacing
1 5 -12 -08 SUBMIT FOR APPROVAL JRGN Static Pressure - System No. Symbol Qty Size K Temp Description SIN
2 5 -27 -08 CITY COMMENTS JRGN Residual Pressure - Design Area Area #1 Area #2 55 1/2" 5.6 155 TYCO -QUICK RESPONSE WHITE TY -FRB SEMI REC PENDENT TY -3231
Pitot Reading - Density - -
Flow In G.p.m. - Design Area S.f. - -
Date Of Test 1 - Psi Req'd 0 City Main - -
Time Of Test - Gpm Req'd ® City Main - -
Test Taken By - Gpm Req'd 0 Basr - -
- No. Spkr. In Dsgn. Area - -
Hydrant Location - Elev. ® Highest Spkr - -
- Domestic /outside Hose - -
- 55 Total This Sheet
FIRE PROTEC'riON GENERAL NOTES
1. FIRE PROTECTION SYSTEM TO ZOM?LY \VITH NFPA 13, AND ALL APPLICABLE.STATE
AND LOCAL: CODES. _ :
2. ADHERE TO AND OBTAIN ALL PERMITS, LICENSES AND GOVERNMENT
REQUIREMENTS.
3. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE DEPARTMENT, AND
ARCHITECT /ENGINEER.
5. CUTTING OF STRUCTURAL AND /OR ARCHITECTURAL MEMBERS TO BE DONE ONLY
WITH THE WRITTEN APPROVAL OF THE ARCHITECT.
6. PIPE ROUTING SHOWN SHALL BE USED AND ANY ADDITIONAL OFFSETS OR FITTINGS
REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES,
AND /OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY
EXISTING STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID
ANY /ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE
ROUTING.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC. FLASH AND COUNTERFLASH ROOF PENETRATIONS. (SEE FIRE RATED PIPE
PENETRATION DETAIL).
8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON - ACCESSIBLE CEILINGS AND
CHASES.
9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL EXISTING /NEW DIFFUSERS,
SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS.
10. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN
ACCORDANCE WITH N.F.P.A. 13.
11. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN
ACCORDANCE WITH N.F.P.A. 13.
12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL
BE FACTORY MARKED "UL" AND "FM ", 175 WORKING PRESSURE.
13. ALL VALVES ON THE FIRE PROTECTION SYSTEM TO BE ELECTRICALLY
SUPERVISED. TYPE AND EXACT LOCATION OF FLOW, PRESSURE AND
SUPERVISORY SWITCHES SHALL FACTORY MARKED "UL" AND "FM ", 175 WORKING
PRESSURE.
14. ALL POWER WIRING SHALL BE ACCOMPLISHED UNDER THE ELECTRICAL DIVISION.
ALL CONTROL AND INTERLOCK WIRING SHALL BE ACCOMPLISHED UNDER THIS
SECTION OF THE SPECIFICATIONS IN ACCORDANCE WITH THE REQUIREMENTS IN
THE ELECTRICAL DIVISION. COORDINATE ALL ELECTRICAL ITEMS WITH ELECTRICAL
CONTRACTOR AND INSURE PROPER COORDINATION.
15. SPRINKLERS SHALL COVER THE ENTIRE AREA OF THE ROOM INCLUDING ALCOVES.
SPRAY SHALL NOT BE BLOCKED BY WALLS OR PARTITIONS.
16. ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4"
AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL
INTERSECTING SURFACE.
17. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY.
18. MAINTAIN A MINIMUM OF 18 INCHES FROM THE BOTTOM OF THE SPRINKLER
DEFLECTOR TO THE TOP OF STORAGE/FILE STORAGE.
19. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER
"tqco Fire & Building
Products
Technical Services: Ter: (8001381-9312 1 Fax: (6WJ 791.5500
Series TY -FRB - 2.81 4 "2, 5.6, and 8.0 K- factor
upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The S;,nes TY -FRS, 2 8, 4 2.5 6, and
8,0 K•tactar, Upright and Pendent
Sprinklers ctescnbed+n this data sheet
are autck response - standard cover-
age, decorat va 3 mm glass bulb type
Spray sprinklers designed for use in
fight or orcin,ary hazard, ccmmerc.al
cccuparciii such as banks, hors's,
shopping ma'ls, Eli,
toned when exposed to corrosive al•
mospieres. Allhcugh corrosion reSis-
ta ^t Coaled spnn k:ers hate passed the
standard corrosicn tests of Me appil-
=Ae apprevat agencles, the testing is
not representative of all possible cor-
rosive atntuspheres. Consequently, it
is'ec,,mmer,dir_,J that the end user be
consulted with respect to the sudabil,ty
of 11he5e ccatings for any given cflrro-
sive envim -nmenl The ettects of ambi-
ent tenp?rature, concentraticn cf
rhem-cals, and gasi'chemcrd velocity,
should be considered, as a mnmurr,,
The re^etsed version of the Senes along w2h the corrosive nature of the
TY•FRB Pendent Sprinkler, where ap•
pric•,.ble, is rntnnded for use in areas
with a fir,ishied ceiling. It uses either a
two-piece Style 10 (11`2 inch NPT) or
Style 40 ('14 Inch NPT) Recrossed Es-
culcheon witty 1,2 inch (12.7 rim) of
recessed ad;ustment or up to 314 inch
(19,1 mm) of total adjustment from the
twee penctnt position, or a tio,piece
Style 2011/2 Inch 1`11"T1 or Style 30 (314
inch NPT) Recessed Escutcheon with
1.4 Inch 164 mm) of recessed adiust-
them cal to which the scar,nk`,erts will be
emxsed_
A.n irrtenmed,ate krvel ver5ipns of the
Serle,s T11-FR9 Pendent Sprinklers
are detailed in Tccrinlcal Data Shoot
TFP356. and Sprinkler G,:ards we Be-
ta, ed In "re-,tin-cal Data Sheet TFP780
WARNINGS
The Series TY -FRB SPrinAler3 de-
scribed h&&a trust W lrtstafied ai.7
nrarntarned
in cempt,snce wdh this
ni or up to 1!2 Inch fl2,7 mm) of ctocu,Tre,nt, as wed as kwr:r theapplica-
total adjustment from the hush pen • bte star*dards cl the Ivahonaf Fire Pro.
dent posrt'on. The adjustment pro- tochnn AssocjaNm, in ad<t,'t,on to Vie
videdbythe Recessed Escutcheonre- 57,11of any other sutbonheshav- Model /Sprinkler
duces the accuracy to which the fixed Mg1unrdr.t ern, Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut vii
resistant coat ngs, while Toe owrre, is respcins,t�re. for,mavtts,rt• Numbers
appicabfe, are utilized to extend the iii hheir fee protevicinsystem and de-
"lie of copper Ahoy sprinklers beyond v +sets 40 proper apershng cond,t'on. TY1131 - Upright 2.811 112'NPT
that which would otherwise to chi The installing ctrtraclor or sprinkler TY1231 - Pendent 2.8K, 11Y'NPT
manufacturer should be contacted TY213 - .2K, 112'NPT
inch anY cuesflorl Pendent 2K, 1/2-NPT
DISAPPROVED BYWY3231 - Pendent 6K, VVNPT
Always refer f Tec7msal late
SheetTFP7i70f tits 7f CSTAtL11' J#4JEtJrghit K,3/4'NPT
WARNING' thsf rovdi cautLons dent K, W4 -NPT
irfth res"ct to h ndri l - D AD E COUNTY FIREXP
W-on c (sprinkle fem
ponents, tmnp t rid rjg arid m- / -- O� SITE
atalP wort can r W � IT
a s rirrhror s st
nertts and cause a >prrnhrer fo fail c gii _Ep'd F. i 6
tcoperatstnalre ltuatloncrcazusa ��, I,y
it to operrte prom rely,
DATE
Project
DR. LOPEZ
�.�..�. ,� ,);.� SOUTH MIAMI HOSPITAL
Fire s
Is 6200 �.�;,���` 6200 SUNSET DRIVE SUITE 305
• t `•rl
r ` ' • 'S U � MIAMI, FLORIDA
RINK: :-R
1 N C.
01. systerri No. 1 Date: 5 -27 -08
Down By: Scale:
All Fire Sprinklers
7570 N.W. 82nd Street Checked eY' All Fire Sprinklers AN: Miami Dade
Medley,Florida 33166 Total A/s: 55
TEL:(305) 403 -4455 FAX:(305) 403 -4488 contract No.
State Certification # 56528000012005 08 -43 FP-1 Of