08-1195-0254009 Notification' Appliance Extender Panel Battery Calculation
- NAC #6 SOUTH MIAMI HOSPITAL EAST TOWER ROOF 7TH & 811 FLOOR 3
WIRE
GAUGE
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
I LENGTH
MAXIMUM
ALLOWABLE
CIRCUIT
LENGTH
2 3
WP SPKR STRB
TOTAL
CIRCUIT
LOAD
Standby
Total
Alarm
Total
Module
scri tion
TOTAL
CIRCUIT
RES.
Current
Standby
Current
Alarm
Panel Equipment
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
LAST
DEVICE
VOLT
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE)
75CO
CIRCUIT
Ni -1
4009- 9201
1 4009 IDNEI` NAC EXTENDER, 120 VAC
0.1380
1 0.085000
1 0.085000
0,185000
1 0.185000
1.0370
3
AMPS
1.461
Total Panel Stby
1 0.085000
Total Panel Alarm
0.185000
Peripheral Devices
OHMS
2.4
VOLTS
3.5
I %
17.0%
VOLTS
16,9
N1 -2
ISPARE
EXISTING
2
EXSISTING LOADS
0.000000
0.000000
0.000000
1.745000
1.745000
Er7OWP- 2475W -FR
3
WHEELOCK WEATHERPROOF SPEAKER STROBE
0.000000
0.000000
0.138000
0.414000
N/A
N A
Total Standby Ampsl
Total Periph Stby
0.000
Total Peri h Alarm
2.159
0.00307
at the last appliance on the NAC under worst case conditions.
Standby
Total Standby Amps
0.085
Total Alarm Amps
2.344
0.00
Battery Calculations
Current
Standby
Current
Alarm
N A
N1 -4
8TH FLOOR
Battery Calculations
Current
14
Current
150
798
0.7080
0
Control Panel Card Power
0,085
0.65
0.185
19.7
4.9
3.5
17.0%
Power For External Peripheral Devices
0.00000
-
< -- Totals ->
2.15900 '
UQ �
z
i
Additional Battery Capacity Required 0%
0.085
< -- Totals - ->
2.344
Q
L
U)
a z
W
0C3
Additional Battery Capacity Required 0%
0.000
Standby Ah
0.000
u
EL
Standby Time = 4 Hrs
0.340
Standby Ah
w
z
Alarm Time = 15 Mins.
0,586
Alarm Ah
'
°�
Battery Required 2081 -9272 6.2
0.926
Total Ah
❑
Battery Required 2081 -9272 6.2
2.431
Ah
4009 Notification, Appliance Extender Panel Battery Calculation -
NAC #7 SOUTH MIAMI HOSPITAL EAST TOWER GROUND FLOOR 3
WIRE
GAUGE
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
I LENGTH
MAXIMUM
ALLOWABLE
CIRCUIT
LENGTH
2 3
WP SPKR STRB
TOTAL
CIRCUIT
LOAD
Standby
Total
Alarm
Total
Module
Qty Description
TOTAL
CIRCUIT
RES.
Current
Standby
Current
Alarm
Panel Equipment
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
LAST
DEVICE
VOLT
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE)
75CO
CIRCUIT
Ni -1
4009 -9201
1 1 14009 IDNET NAC EXTENDER, 120 VAC
0.1380
0.085000
0.085000
0.185000
0.185000
1.0370
3
AMPS
1.461
Total Panel Stb
0.085000
Total Panel Alarm
0.185000
Peripheral Devices
OHMS
2.4
VOLTS
3.5
I %
17.0%
VOLTS
16,9
N1 -2
ISPARE
4906- 9101 *75
1 9 ITRUEALERT MULTI - CANDELA STROBE RED,
WALL 0 75 CANDELA
0.000000
1. 0.000000
0.186000
1.674000
0
0.000
1 0.0
Total Peri h Stb
0.000
Total Peri h Alarm
1.674
N A
N/A
N A
Total Standby Ampsl
01085
Total Alarm Ampsl
11859
14
0.00307
at the last appliance on the NAC under worst case conditions.
Standby
O.000D
Alarm
0.000
0.0
0.00
Battery Calculations
Current
N/A
Current
N A
N A
N1 -4
8TH FLOOR
Control Panel Card Power
0.085
14
0.185
150
798
0.7080
0
Power For External Peripheral Devices
0.00000
0.65
1.67400
19.7
4.9
3.5
17.0%
16.9
0.085
-
< -- Totals ->
1.859
UQ �
z
i
Additional Battery Capacity Required 0%
0.000
0.000
Q
L
U)
a z
W
0C3
Standby Time = 4 Hrs
0.340
Standby Ah
u
EL
Alarm Time = 15 Mins.
0.465
Alarm Ah
w
z
<
0.805
Total Ah
'
°�
Battery Required 2081 -9272 6.2
2.047
Ah
❑
4009 Notification Appliance Extender Panel Battery Calculation - NAC # 6 SOUTH MIAMI HOSPITAL EAST TOWER GROUND FLOOR VOLTAGE DROP TOTALS
NAC SCHEDULE / VOLTAGE DROP CALCULATION
17% MAXIMUM VOLTAGE DROP
CIRCUIT OUTPUT VOLTAGE FOR CALCULATIONS 20.4
CIRCUIT
TYPE
V/0
WIRE
GAUGE
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
I LENGTH
MAXIMUM
ALLOWABLE
CIRCUIT
LENGTH
2 3
WP SPKR STRB
TOTAL
CIRCUIT
LOAD
MAX
CIRCUIT
CAP.
Lowest Voltage at any Device: 16.9 V 106%
:
AS DESIGNED
MAX ALLOW. CIRC. LENGTH
AT
MAX ALLOW, CIRC, LENGTH
TOTAL
CIRCUIT
RES.
EXISTING
ET70WP- 2475W -FR
TOTAL
CIRCUIT
RES.
ACTUAL
VOLTAGE
DROP
LAST
DEVICE
VOLT
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
LAST
DEVICE
VOLT
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE)
75CO
CIRCUIT
Ni -1
DESCRIPTION
I 7TH FLOOR
1.0000
0.1380
AWG
14
OHM FT
0.00307
FT
300
FT
389
1.0370
3
AMPS
1.461
AMPS
2.000
2.000
2.000
2.000
OHMS
1.8
VOLTS
2.67
%
13.1%
VOLTS
17.7
OHMS
2.4
VOLTS
3.5
I %
17.0%
VOLTS
16,9
N1 -2
ISPARE
ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
0.930
1 14
0.00307
8.4%
N/A
0.0000
0
0.000
1 0.0
0.00
0.07.1
20.4
N/A
N A
N/A
N A
N1 3
SPARE
Please note that 16VDC is the lowest operating voltage that is allowed
1.2
14
0.00307
at the last appliance on the NAC under worst case conditions.
N A
O.000D
0
0.000
0.0
0.00
0.0%
20.4
N/A
N/A
N A
N A
N1 -4
8TH FLOOR
0,0
V 0
14
0.00307
150
798
0.7080
0
0,708
0.9
0.65
3.2%
19.7
4.9
3.5
17.0%
16.9
- Strobe designs are constant wattage and the maximum RMS current
rating occurs at the lowest allowable operating voltage.
-
3 APPLIANCE / QUANTITIES / CURRENT DRAW ® MAXIMUM RMS
4009 Notification Appliance Extender Panel Batter Calculation NAC #7 SOUTH MIAMI HOSPITAL EAST TOWER GROUND FLOOR VOLTAGE DROP TOTALS
NAC SCHEDULE / VOLTAGE DROP CALCULATION
17% MAXIMUM VOLTAGE DROP
CIRCUIT OUTPUT VOLTAGE FOR CALCULATIONS = 20.4
CIRCUIT
TYPE
yo
2.159
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
LENGTH
METHOD USED TO CALCULATE VOLTAGE DROP:
2 3
TOTAL
CIRCUIT
LOAD
Total NAC Load: 2.16 A 27%
AS DESIGNED
Lowest Voltage at any Device: 16.9 V 106%
:
[(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS / FT)]
MAX ALLOW. CIRC. LENGTH
Wire Resistance At WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE UNCOATED SOLID COPPER WIRE
( )
Largest Single Circuit Load: 1.45 A 73%
TOTAL
CIRCUIT
RES.
ACTUAL
VOLTAGE
DROP
LAST
DEVICE
VOLT
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
Lowest Voltage at any Device: 16.9 V 106%
75CD
CIRCUIT
7N1 -1
Wire Resistance At
WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE)
AWG
14
OHM FT
0.00307
FT
100
FIT
3,037
75 Degrees Celsius
NOTE:
AMPS
2.000
2.000
2.000
2.000
Total NAC Capacity: 8 A
VOLTS
0.11
I %
0.6%
Ohms / ft
LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN
VOLTS
3.5
Single Circuit Capacity: 2.0 A
VOLTS
15.9
7N1 -2
10 OA = 0.001210
OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN
V 0
IMinimum Device Voltage; 16 V
0.00307
300
12 GA = 0.001930
ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
0.930
1.8
1.71
8.4%
14 GA 0.003070
LENGTH, CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE.
Note:
17.0%
16 GA = 0.004890
7N1 -3
'Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC
18 GA _ 0.007770
14
per UL standard 1971. This voltage is the absolute operating range.
200,
1,012
3
Please note that 16VDC is the lowest operating voltage that is allowed
1.2
0.69
3.4X
at the last appliance on the NAC under worst case conditions.
6.2
3.5
17.0%
The maximum RMS current listed is the nameplate rating.
- Strobe designs are constant wattage and the maximum RMS current
rating occurs at the lowest allowable operating voltage.
-
3 APPLIANCE / QUANTITIES / CURRENT DRAW ® MAXIMUM RMS
4009 Notification Appliance Extender Panel Batter Calculation NAC #7 SOUTH MIAMI HOSPITAL EAST TOWER GROUND FLOOR VOLTAGE DROP TOTALS
NAC SCHEDULE / VOLTAGE DROP CALCULATION
17% MAXIMUM VOLTAGE DROP
CIRCUIT OUTPUT VOLTAGE FOR CALCULATIONS = 20.4
CIRCUIT
TYPE
yo
WIRE
GAUGE
WIRE
RESIST
AS DESIGNED
ESTIMATED
CIRCUIT
LENGTH
MAXIMUM '
ALLOWABLE
CIRCUIT
LENGTH
STROBE
TOTAL
CIRCUIT
LOAD
MAX
CIRCUIT
CAP.
AS DESIGNED
Lowest Voltage at any Device: 16.9 V 106%
:
AT
MAX ALLOW. CIRC. LENGTH
Wire Resistance At WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE UNCOATED SOLID COPPER WIRE
( )
4906- 9101 *75
TOTAL
CIRCUIT
RES.
ACTUAL
VOLTAGE
DROP
LAST
DEVICE
VOLT
TOTAL
CIRCUIT
RES.
MAXIMUM
VOLTAGE
DROP
LAST
DEVICE
VOLT
75CD
CIRCUIT
7N1 -1
DESCRIPTION
GROUND FLOOR SOUTH EAST
0.1860
AWG
14
OHM FT
0.00307
FT
100
FIT
3,037
1
AMPS
0,186
AMPS
2.000
2.000
2.000
2.000
OHMS
0.6
VOLTS
0.11
I %
0.6%
VOLTS
20.3
OHMS
18.6
VOLTS
3.5
%
17,0%
VOLTS
15.9
7N1 -2
GROUND FLOOR SOUTH WEST
V 0
14
0.00307
300
607
5
0.930
1.8
1.71
8.4%
18.7
3.7
3.5
17.0%
16.9
7N1 -3
GROUND FLOOR NORTHWEST
V 0
14
0,00307
200,
1,012
3
0,558
1.2
0.69
3.4X
19.7
6.2
3.5
17.0%
16,9
7N1 -4
NOT INSTALLED
14
0.00307
N/A
0
0.000
0,0
0.00
0.0X
1 20.4
N A
I N/A
N/A
I N/A
nr era. � x1L1L1_ i'1Ri /,tJAN
FIFIE WATER i J11�i
DATE:
\ \..0 .6..11 \rT,1d1. \C0 ..... 3,..,,JHH
- 1.674 -
METHOD USED TO CALCULATE' VODAGE DROP: 9 Total NAC Load: 1.67 A 21%
HrAl, Il"xrfR.-
( L, SIIF)\.dlUlli M61A71 HOSPITAL EASE TOWER RENOVATIONS 91.9372021 \SG \R@N3 \5{IH G4Ct' EIOBIdF !&CMIY.RfllicLr8r8A37M1p2744wG
[(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS / FT)] - Largest Single Circuit Load: 0.93 A 47%
AATE SAVED: December 19, 2007
Lowest Voltage at any Device: 16.9 V 106%
:
1"
Wire Resistance At WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE UNCOATED SOLID COPPER WIRE
( )
75 Degrees Celsius NOTE: Total NAC Capacity: pa Ity 8 , -%
Ohms / ft LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN Single Circuit Capacity: 2.0 A
10 GA = 0.001210 OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN Minimum Device Voltage: 16 V
12 GA = 0,001930 ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT
14 GA _ 0.003070 LENGTH, CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE. Note:
16 GA = 0.004890 "Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC
18 GA = 0.007770 per UL standard 1971, This voltage is the absolute operating range.
P 9 P 9 9
Please note that 16VDC is the lowest operating voltage that is allowed
at the last appliance on the NAC under worst case conditions.
nr era. � x1L1L1_ i'1Ri /,tJAN
FIFIE WATER i J11�i
DATE:
\ \..0 .6..11 \rT,1d1. \C0 ..... 3,..,,JHH
HrAl, Il"xrfR.-
( L, SIIF)\.dlUlli M61A71 HOSPITAL EASE TOWER RENOVATIONS 91.9372021 \SG \R@N3 \5{IH G4Ct' EIOBIdF !&CMIY.RfllicLr8r8A37M1p2744wG
DATE PLOTTED: December 19, 2007
AATE SAVED: December 19, 2007
L. TRIANA & ASSOCIATES, INC.
c (�
ONSUL, f'
rWC r
�INEE 'S
r
R
hi "Wr
CERTIFICATE OffVUTAOR Z TiOt�: 26644
5 3,W.' G j
X151 �8tYTs�� I�,U - f
MIAMI, F•L6RIDA 33 I55
rL tl CI
LEI 'IPA T�'A 01
Florida Re�i�jafbn .6 65707
$ {.r {aszW-
r
1"
w
"..
Z
Q .,
0
m
1 1.
¢
ro'y.
w "o ao
L�
W M
1
M
�
a
W -I T
1,
C%
L�i4
UQ �
z
O
Q
L
U)
a z
W
0C3
-aizL
u
EL
=
w
z
<
'
°�
im
❑
--' w
w>
z
Z
�W
�w
J W
F-
O J
Q
N
O
m
IX
U
U
H
z
W
Z
O
F
a
O
U
tr
U)
U
U
0
U
W
W
o
Z
Z
O
F..
g
O
O
O
>
FF-
Ix
Z,
U
U
W
F- J
U
W
w
Z
O
U
FE
W
W
U
F--
0_
CY
0
O
W
W
W
{i.
LI..
W
WW
W
❑
U
a,
Q
o_
Q
a
Q
N
°
r,
4
o
co
Q
❑
O
1
N
O
Z
N
Sh
U
�
(rrte,
ai
Y
U)
r--I ko
C-t in
Z
Q
E� 0 20
,..w.4p
3 Q
O
„9' U
F
U
W
W aY
W ra.xy W
F_ Yr
M °
z
W
O -i
Z;: W
O Z
Q
z a
any' g
Q,
;,y' ,
O
bO
a LU
ca
r I
LL a;
WW Q
a� Q
-F-)
W O T
Y)
Q)
LL w
° a
a ❑ >�
W
❑ O
it
ao Q
O
F__ F C) ,� y . 0
N O
F_s
7 zJ y
0
Z , W'#
r ,-(� O
c
Z
U z
V • r-1
w J`
0 F-
U
O
z Z
z. - O
O
cn
F- J
J
FBI
F-r I
q
Q
O „ Z „ {`
d
(D W Z
Q U
r{
(j
C' ]
❑ D (D
Z J W
� a
Q) s
Q
�r-iI
_
I
ra U
rl O q
- F-
Q�
a.
::D
E-i cc0
vl O
LL
z ❑
W
o
-
❑
a
ej
w
0 O (� off
x
z >+ z I-
❑° z0
Pa, W
0
Of Z
' a t Q :0
DRAVVN BY:
DA
RC
7-31 -07 a .
DESIGNED BY:
;DATE:
APPROVED BY:
ATE:
PROJECT NUMBER:
263- 403461 /929372021
A^
SHEET TITLE/ PATH
2003 \SOU THMI
{
AMIHOSP I AL\
SMH ET
RENOVATION
,�
y
r .
`�
x
7
SHEET NUMBER:
k
`
'
°'r
FA-
f
16
'j SIZE: D(24'X36,
r