08-1177R-015AIR DISTRIBUTION SCHEDULE
SYMBOL
�
DESIGN CFM
CFM MIN
MAX BOX
CFM
DESIGNATION
A
B
.)MODEL
NUMBER
30% EFFICIENCY
VAV 308B
VAV -`I 13
MANUFACTURER
TITUS
TITUS
2000
2771 '1 160
TITUS
TITUS
VAV -1 116
'1090
2000
MODEL NO. AND /OR
TITUS
VAV -111
'1310
2000
PASS
PAR
TITUS
VAV -1 'I 2
C ATALOG 1,10.
2000
TITUS
VAV-'I'I 4
24 X 24
24 X 24
2000
FRAME Tl'PE
LAY -IN
LAY -IN
VAV -308
'1200
DEVICE TYPE
PERFORATED
PERFORATED
.......
TITUS
FUNCTION
SUPPLY
RETURN
PATTERN
SEE DRAWING
SEE DRAWING
OPPOSED BLADE DAMPERS
YES
YES
NOTES:
'I. ALTERNATE MANUFACTURERS CARNES, METALAIRE MAY BE SUBMITTED FOR APPROVAL.
2, ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY G'ASKETED.
3. UNLESS OTHERWISE NOTED, ALL AIR DEVICES FINISH SHALL BE BAKED OFF - WHITE.
4. SUPPLY, RETURN OR EXHAUST OUTLETS SERVED BY AN INDIVIDUAL DUCT BRANCH PROVIDED VVITH AN ACCESSIBLE MANUAL VOLUME DAMPER
SHALL BE SUPPLIED WITHPOUT INTEGRAL O.B.D.
5. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, PROVIDE THE REQUIRED INSULATED SQUARE TO ROUND TRANSFFION.
EXISTING VAV TERMINAL UNIT SCHEDULE
SYMBOL
SIZE
DESIGN CFM
CFM MIN
MAX BOX
CFM
EH KW &
STAGES
V I PH 1 HZ
MANUF.
.)MODEL
NUMBER
30% EFFICIENCY
VAV 308B
VAV -`I 13
720
080
1400
2000
2771 '1 160
TITUS
TITUS
VAV -1 116
'1090
2000
TITUS
VAV -111
'1310
2000
TITUS
VAV -1 'I 2
1210
2000
TITUS
VAV-'I'I 4
`1360
2000
TITUS
VAV -308
'1200
2000
TITUS
REMARKS: 1. ALL UNITS TO BE PRESSURE INDEPENDENT NORMAL OPEN WITH ELECTRONIC
CONTROL OPERATOR.
2. ALL VARIABLE VOLUME BOXES SHALL BE DOUBLE WALL CONSTRUCTION VVITH
INSTALLED R /ALUE OF 3.5 MIN. INSULATION BETWEEN WALLS.
3. MAXIMUM NOISE CRITERIA (25 NC }.
REMARKS: 1. ALL UNITS TO BE PRESSURE INDEPENDENT11ORMAL OPEN WFFH ELECTRONIC
CONTROL OPERATOR.
2, ALL VARIABLE VOLUME BOXES SHALL BE DOUBLE WALL CONSTRUCTION WITH
INSTALLED R -VALUE OF 3.5 MIN. INSULATION BETWEEN WALLS.
3. MAXIMUM NOISE CRFFERIA (25 NC).
N E W V A V T E R M I N A L U N I T S C H E D U L E
SYMBOL
SIZE
DESIGN CFM
CFM MIN
MAX BOX
CFM
EH KW &
STAGES
V l F'H I HZ
MANUF.
MODEL
NUMBER
30% EFFICIENCY
VAV 308B
'10
720
280
1400
-
2771 '1 160
TITUS
DESV 10
2
REMARKS: 1. ALL UNITS TO BE PRESSURE INDEPENDENT NORMAL OPEN WITH ELECTRONIC
CONTROL OPERATOR.
2. ALL VARIABLE VOLUME BOXES SHALL BE DOUBLE WALL CONSTRUCTION VVITH
INSTALLED R /ALUE OF 3.5 MIN. INSULATION BETWEEN WALLS.
3. MAXIMUM NOISE CRITERIA (25 NC }.
�I
EXISTING AHU # 1 DATA (BEFORE DEMOLITION)
AREA SERVED
FIRST FLOOR
LOCATION
MECHANICAL ROOM 107
AIR FLOW - CFM
15,680
OUTSIDE AIR - CFM
2,825
PRE - FILTER (PFi
30% EFFICIENCY
FINAL FILTER (FF)
95% EFFICIENCY
SMOKE DETECTOR
YES ON SUPPLY AND RETURN DUCT (EXISTING.)
EXISTING AHU #1 DATA (AFTER NEW CONSTRUCTION)
AREA SERVED
FIRST FLOOR
LOCATION
MECHANICAL ROOM 107
AIR FLOW - CFM
15,680
OUTSIDE AIR - CFM
3,265
PRE - FILTER (PF)
30% EFFICIENCY
FINAL FILTER (,FF)
95% EFFICIENCY
SMOKE DETECTOR
YES ON SUPPLY AND RETURN DUCT (EXISTING.)
NOTE: THE O/A MUST BE ADJUSTED TO OBTAIN 3,265 CFM AS SHOVVN ON SCHEDULE
AFTER NEVV CONSTRUCTION IS FINISHED.
EXISTING EF -G (BEFORE DEMOLITION) DATA
AREA SERVED
FIRST FLOOR
LOCATION
CEILING
CFM
2,300
EXISTING EF-G
AREA SERVED
FIRST FLOOR
LOCATION
CEILING
CFM
2,740
NOTE: THE EXHAUSTAIR MUST BE ADJUSTED TO OBTAIN 2,740 CFM AS SHOWN ON
SCHEDULE AFTER THE NEW CONSTRUCTION IS FINISHED.
1
PR01. No 18056 F30000924
LQU O J. AGUIRRE & ASSOCIATES P.A.
OONSULTING ENGINEERS
2600 DOUGLAS RD. SUITE 605
CORAL GABLES, FLORIDA 33134
TELEPICNE: (305) 444 -1679
FAX: (305) 448 -1405
L -MAI,_ ADDRFSS: GRALMAIL@LJAAPA.COM
Revisions:
2/0/09
OWNER CHANGE
COORDINATION
0
0
0
0
0
L iI
c� <
m °CC)
o 0 -
-J _J O
J
Q
cry
Q
a D
C-) o
o
w w
z
w I
J
El-
cry ~
w "'
m o
m
_ w36
�— - w I-)
w z m00
w
0-
r� co
V�-
o
FT__) N W
cD I—
^1 v
o
[c
� E
0 U
+-J
aM
U �
N p rtl
w d
Q �
�<
4 m F =
ca
Ld
a
O � g
VA
�I
_D
C-) <
W
U
V)
-RMIT SE
DRAWN:
CHECKED: P_q.
DATE: Oe -25 -08
SCALE: AS NOTED
SEAL
„.. MEC� IAINI,CAL
�" ESTS,.SA.N,TA2A P,E.
IG i E 078a
Sheet No.
M6,00
JOB # err t ?3