08-1177R-013HVAC GENERAL NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF HVAC SYSTEM IN ACCORDANCE WITH THESE DRAWINGS. FLORIDA BUILDING CODE 2004 ANS /ASHRAE 15 -'1994 NFPA PAMPHLETS 90A, 9OB -91 -2002 SMACNA -1 995 ASH RAE -2001 OSHA -2005 2. THE WORK INCLUDES PROVIDING THE HVAC SYSTEMS, INCLUDING DUCTWORK, DIFFUSERS AND GRILLES, INSULATION, CONTROLS AND EQUIPMENT NECESSARY FOR A COMPLETE FUNCTIONING SYSTEM. HVAC SYSTEM INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING: SUPPLY, RETURN AND EXHAUST DUCTWORK SYSTEMS WITH GRILLES, DIFFUSERS FILTERS AND DAMPERS. 3. TEMPERATURE CONTROL SYSTEM INCLUDING LOW VOLTAGE WIRING AND CONDUIT, TRANSDUCERS, ACTUATORS, CONTROLLER. 4. WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED PROJECT. S. DRAWINGS FOR HVAC: WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, LAYOUT AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENTS. REFER TO MANUFACTURER'S STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION REQUIREMENTS AS REQUIRED. FURNISH AND INSTALL ALL DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS AND MATERIALS NECESSARY TO FACILITATE THE SYSTEM FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT INDICATED. 6. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES, ESPECIALLY WITH THE LOCATION OF STRUCTURAL MEMBERS, PIPING, SPRINKLERS, CONDUITS AND LIGHTING OUTLETS AND /OR FIXTURES. 7. ALL MATERIAL AND EQUIPMENTS SHALL BE NEW OF U.S. MANUFACTURER AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED 30 AS TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK. ALL WORK THROUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY SUFFICIENT NUMBER OF SKILLED PERSONNEL. S. FLEX DUCT: PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1 -1/2" THICK 'I PCF FIBERGLASS INSULATION R -6 AND REINFORCED OUTER PROTECTIVE COVER/VAPOR BARRIER. FLEX DUCT SHALL MEET NFPA 90A WITH FLAME SPREAD UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR 2" W.G. PRESSURE AND 0 TO 250 DEGREES FAHRENHEIT. PROVIDE METAL ADJUSTABLE CLAMPING DEVICES, SCREW OPERATED. USE TWIST -LOCK CONICAL TAP COLLARS AT CONNECTIONS INTO SHEET METAL DUCTWORK. FLEXIBLE DUCTWORK MAY BE USED FOR BRANCHES TO DIFFUSERS AS INDICATED ON DRAWINGS. DO NOT EXCEED EIGHT (8) FEET IN LENGTH FOR ANY FLEX DUCT. 9. BALANCING DAMPERS: FABRICATED OF SAME MATERIAL AS DUCT, TWO METAL GAUGES HEAVIER THAN DUCT. MOUNT ON 3/8 " SQUARE ROD WITH SAW SLOT POSITION INDICATOR. PIVOT AND BEARING, LOCKING POSITION REGULATOR. 10. ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND WITH MANUFACTURER'S WARRANTY. 11. PROVIDE DOUBLE THICKNESS TURNING VANES AT ELBOWS AND EXTRACTOR DAMPERS AT ALL DUCT BRANCHES AND TAKE -OFFS. 12. ALL EXHAUST DUCTWORK SHALL BE OF GALVANIZED SHEET METAL FABRICATED IN ACCORDANCE WITH SMACNA STANDARD FOR PRESSURE CLASS ACCORDING TO EACH SYSTEM. EXHAUST AIR DUCTWORK SHALL BE UNINSULATED. 13. FLEXIBLE CONNECTOR: WHERE REQUIRED PROVIDE U.L. LABELED NEOPRENE COATED FIBERGLASS FABRIC DUCT CONNECTORS. 14. CONTRACTOR SHALL BE RESPONSIBLE TO TEST &: BALANCE THE HVAC SYSTEMS AS PER ASSOCIATED AIR BALANCE COUNCIL STANDARDS. 15. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL EQUIPMENT, MATERIALS AND LAYOUTS PRIOR TO INSTALLATION. 16. CONTRACTOR SHALL PRINT UP INSTRUCTIONS FOR OWNER'S OPERATION OF SYSTEMS. 17. THE CONTRACTOR SHALL PAY ALL INSPECTION FEES. ALL COSTS OF PERMITS AND ALL OTHER C08TS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK UPON FINAL ACCEPTANCE A CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY SHALL BE FURNISHED TO THE OWNER. 10. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE LOCATION OF EXISTING EQUIPMENT, DUCTWORK, PIPING, CONDUITS, ETC., AND /OR ANY CONDITION THAT MAY AFFECT HIS WORK. I9. ALL AIR CONDITIONING DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL INSULATED WITH 2 INCH THICK AND 1.0 PCF GLASS FIBER FLEXIBLE BLANKET INSULATION WITH ALUMINUM FOIL REINFORCED WITH GLASS FIBER FASING rFSKL) JOHN- MANVILLE MICROLITE (R-6 INSTALLED) OR APPROVED EQUIVALENT, DUCT SIZES SHOWN ARE NET FREE AREA. PROVIDE DOUBLE THICKNESS TURNING VANES AND EXTRACTORS AT ALL ELBOWS AND TAKE -OFFS. 20. ALL CONCEALED SUPPLY AIR DUCTS SHALL BE EXTERNALLY INSULATED WITH DUCT WRAP AS INDICATED IN GENERAL NOTES. 21. CONSTRUCTION FILTER: PROVIDE TWO SETS OF TEMPORARY 2 INCH THICK FIBERGLASS THROW AWAY FILTERS DURING CONSTRUCTION AND START UP. CONSTRUCTION FILTERS TO BE 35`,`4 EFFICIENT. CONSTRUCTION FILTERS PROVIDED FOR ALL FILTER APPLICATION. REPLACE FILTER REGULARLY BUT NOT TO EXCEED 7 DAYS DURING CONSTRUCTION. FINAL FILTERS: SHALL CONSIST OF A SINGLE 2 INCH THICK, DISPOSABLE, PLEATED PARTICULATE FILTER, ASHRAE 52.1 -92 RATED AT 40- 45% PERCENT ATMOSPHERIC DUST SPOT EFFICIENY (ADS), LOCATED IN FILTER BOX OF EACH COIL. 22. RETURN AIR DUCTS LOCATED ABOVE UNCONDITIONED SPACES SHALL BE INSULATED THE SAME AS THE SUPPLY AIR DUCTS. 23. DUCT FINISHES AND SEALERS SHALL HAVE A SMOKE DEVELOPED RATING OF LESS THAN 50 AND A FLAME SPREAD OF 25 OR LESS, 24. DURING CONSTRUCTION, ALL SUPPLY AND RETURN DUCTWORK OPENINGS SHALL BE FITTED WITH BLANKET TYPE, DISPOSABLE 'I" THICK SYNTHETIC MEDIA IN ORDER TO PREVENT CONSTRUCTION DEBRIS FROM ENTERING AND ACCUMULATING INSIDE THE DUCT SURFACES. UPON COMPLETION, CONTRACTOR SHALL CLEAN ALL DUST AND DEBRIS IN AREAS WHERE WORK WAS CONDUCTED. y "I III i AIR DISTRIBUTION LEGEND DUCT FIRST FIGURE IS SIDE PAIR AT 10 FT. SPACING PA IR AT 8 FT. SPACING PAIR AT 5 FT. SPACING DUCT MTD. SMOKE DETECTOR DUCT PERIMETER STRAP WIRDROD STRAP WIRE/ROD SHOWN WIREIROD STRAP WIRE/ROD W /@EMOTE � TEST SWITCH 1" X 22 _a. �J ❑ AD 0 SD FC AM U.C. " 1" X 22 ga. (PROVIDE ACCESS DOOR) DUCT SECTION: SUPPLY IS RETURN FLEXIBLE DUCT; FLEXIBLE CONNECTION (FC) ALL ELBOW MUST BE PROVIDED 1" X '18 ga. WITH TURNING VANES WHETHER 1" X 20 ga. UNDERCUT DOOR 1" X 22 ga. OR SHOWN ON DWGS. (SEE SPECS) 1" X 22 ga. 1/4" P12 = 96" TYP. 450 TAP -OFF WITH 318" VOLUME DAMPER 3/8" THERMOSTAT OT VOLUME DAMPER MOTORIZED DAMPER ❑M SPLITTER DAMPER VARIABLE VOLUME BOX WITH ELECTRIC HEATER 1/2" 1" X 16 ga. 3/8" VAV 3/8" 1" X 20 ga. 1/4" P/2 = 168" 'I '1/2" X 16 ga. 1/2" 1 1/2" X 16 ga. FIRE DAMPER 1" X 16 ga. A.D. ❑ EQUIPMENT OR DUCTS 318" P/2 = 192" NOT GIVEll (MUST USE ACCES DOOR) EXISTING TO REMAIN 1/2" 1" X 15 ga. 3I8" F 3/8" POINT OF CONNECTION SPECIAL ANALYSIS REQUIPED ', ":HEN STRAPS ARE LAP JO INED USE B-26 BETWEEN NEW AND EXISTING THESE MINIMUM FASTENERS SINGLE HANG ER MAXIMUM ALLO'JVABILE LOAD WORK STRAP WIRE OR ROD (DIA.) 1" X '18,20,22 ga. - TWO #10 OR ONE 1/4" BOLT NOTES I. 45 °TAP -OFFS, SPLITTERS AT EACH TAP -OFF AND TEE, AND ACCESS DOORS SHALL BEE USED WHERE REQUIRED, WHETHER OR NOT INDICATED IN THE DRAWINGS, 2. IN AREAS WHERE NON- REMOVABLE CIELINGS ARE USED, PROVIDE 45 TAP -OFFS OF THE FIXED TYPE, WITH WIDTH PROPORTION TO BRANCH CFM. 3. REMOTE LIGHT AND TEST SWITCH NEXT TO AHU STARTER TYPE OF DIFFUSER A l W --DIRECTION OF FLOW 6x6�� 15 O SIZE OF DIFFUSER AMOUNT OF CFM AIR OUTLET TAG N.T.S. OUTSIDE AIR CALCULATIONS OFF AREA: 2,732 S.F. 1. NUMBER OF PEOPLE (FBMC 2004 TB- 403.3) 2,732 S.F, X 7PEOPLE = 19.1 1,000 2, MINIMUM OUTSIDE AIR REQUIRED, 20 PEOPLE X 20 C.F.M. = 400 C.F.M. PERSON 3, TOTAL OUTSIDE AIR PROVIDED = 400 C.F.M. 4, TOTAL EXHAUST AIR: 80 C.F.M. RECTANGULAR DUCT HANGERS MINIMUM SIZE 1v AXIMUN1 HALF OF PAIR AT 10 FT. SPACING PA IR AT 8 FT. SPACING PAIR AT 5 FT. SPACING PA IR AT 4 FT. SPACING DUCT PERIMETER STRAP WIRDROD STRAP WIRE/ROD STRAP WIREIROD STRAP WIRE/ROD P/2 = 30" 1" X 22 _a. �J 10 ga. (0.135) 1" X 2� ga. 10 ga. (0A35) 1" X 22 ga. 12 ga. (0.106 ) 1" X 22 ga. 12 ga. (0.106 ) P/2 = 72" 1" X '18 ga. 3/8" 1" X 20 ga. 1/4" 1" X 22 ga. 1/4" 1" X 22 ga. 1/4" P12 = 96" 1" X 16 ga. 318" 1" X 18 ga. 3/8" 1" X 20 ga. 3/8" 1" X 22 ga. 1/4" P/ = 120" '1 1/2" X 16 ga. 1/2" 1" X 16 ga. 3/8" 1" X 18 ga. 3/8" 1" X 20 ga. 1/4" P/2 = 168" 'I '1/2" X 16 ga. 1/2" 1 1/2" X 16 ga. 1/2" 1" X 16 ga. 3/8" 1" X 18 ga. 318" P/2 = 192" NOT GIVEll 1 /2" 1 1/2" X 16 ga. 1/2" 1" X 15 ga. 3I8" 1 1/2" X 16 ga. 3/8" F+2 = 193" UP SPECIAL ANALYSIS REQUIPED ', ":HEN STRAPS ARE LAP JO INED USE B-26 19 ", 20" THESE MINIMUM FASTENERS SINGLE HANG ER MAXIMUM ALLO'JVABILE LOAD G24 STRAP WIRE OR ROD (DIA.) 1" X '18,20,22 ga. - TWO #10 OR ONE 1/4" BOLT 1" X 22 ga. - 260 lbs. 0.106" - 80 lbs. 'I" X 16 ga. - TWO 1/4" DIA. BOLT 1" X 20 ga. - 320 lbs. 0.135" - 120 lbs. '1 1/2" X 16 ga. - TWO 3/8" DIA. BOLT 1 " X 18 ga. - 420 lbs. 0.162" - 160 lbs. PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE 1" X 16 ga. - 700 lbs. 1/4" - 260 lbs. C-26 1 1/2" X 16 ga. - 700 Ibs. 3/8" - 680 lbs. 120 122 1/2 "- 1250 lbs. D-26 D-26 5/8" - 2000 lbs. C-26 C-26 3/4" - 3000 lbs. NOTES 1. DlP!IENSIONS OTHER THAN GAGES ARE IN INCHES. 2 TL.BLE ALLOWS FOR DUCT WEIGHT, 1 Ib. /ft2 INSULATION WEIGHT AND NORMAL REINFORCEMENT AND TRAPEZE WEIGHT, BUT NO EXTERNAL LOADS. 3 STRAPS ARE GALVANIZED STEE_. OTHER MATERIALS ARE UNCOATED STE> L. 4. ALI-OV'vABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (`A') IS OVER 60" THAN P/2 MAXIMUM IS 1.25 In. 5. 12, 10, 8 ga. WIRE IS STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZEDTYPE. rr AIR CONDITIONING LEGEND SYMBOL DESCRIPTION AHU AIR HANDLER UNIT BD BACKDPAFT DAMPER COND. CONDENSATE CONC. CONCRETE CFM CUBIC FEET PER MINUTE EF EXHAUST FAN EA EACH E/A EXHAUST AIR FD FIRE DAMPER FLA FULL LOAD AMPS FPM FEET PER MINUTE FPS FEET PEP SECOND HP HORSEPOWER HP HOUR IN. INCH KW KILOWATT LBS. POUNDS MAX. MAXIMUM VD MANUAL VOLUME DAMPER (OPPOSED BLADE TYPE) NO. NUMBER 0/A OUTSIDE AIR RPM. REVOLUTIONS PER MINUTE P/A RETURN AIR S/A SUPPLY AIR TEMP. TEMPERATURE T THERMOSTAT V VELOCITY VAV VARIABLE VOLUME BOX PRW. No. 18056 EBOOOL),024 LOUIS_ j. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 2600 DUUCLAS RD. SUITE 605 CORAL GABLES, FLORIDA 33134 TFLE1101E: (305) 444 -1679 FAX: (305) 448 -1405 E -M.tiP_ ADDRESS: GRALMAIL @LJAAPA.COM Revisions: �2 /ro /m9 OWNEiR CHANGE GODRD INATION 0 O 0 0 a� z �00 J LO a Q w Q cry _ a v o w w w I _J U-)~ Q w w 0 � O m s = a w o w00 Q cl� 00 w �0) _ °; w a Q O J FT-) N W � � v 0 do'00a 0QO� w 00 `� 0 Q U �M 0 � �C-4 � O,Ic Q_ z d pZ Q �MmpZ< Lj E� a 0 d 8 0 0 W LL-] _I 0 = LL -� LJJ 0 W 7 PERMIT SET DRAWN: CHECKED: P.A. DATE: os -25 -Oa 3 SCALE: AS NOTED SEAL, s " fad MA �(G44 a. iaC�j78 Sheet No. M0 »00 I JOB RECTANGULAR DUCT REINFORCEMENT DUCT fvIAXIMUa1 2" W.G. STATIC POS. OR NEG. NO RENFORCEVIENT REQUIRED STP.P,P RONFORCH4vIB'dT SPACING CODE FOR DUCT GAGE NO. '12' RENFORC'Hv1FJ'•Jl- SPACING OPTIONS 1/4" DUCT DIM. 10' 8" (T 1 5' 1 4' 1 3' 2 -'I /2' 2' 10" cln. 26 ga. 460 rnrn 3.7 m NOT REQUIRED 25 4 X 0.85 rnm 19" - 24" 12' TWO '10 ga. 11 ", 12" 24 ga. B-26 B -26 B -26 8-26 1- 2 6 8-26 B-26 13 ", 14" 22 ga. 1- 24 B- 2 6 B -26 8-26 B-26 8-26 B-26 12' 20 ga. C-22 C-24 t, X24 26 C-26 C-26 B-26 B-26 17" 18" 20 ga. C-22 C-24 C 24 ('_ 26 G26 G26 C•26 B-26 19 ", 20" 18 ga. C-20 G22 G24 C-26 G26 G26 G26 C-26 21 ", 22" 16 ga. D-20 D-22 D-24 D-26 G26 G26 C-26 C-26 23 ", 24" 16 ga. 120 122 D-24 D-26 D-26 G26 C-26 C-26 25", 26 " E­20 F 18 F 18 G-16 NOT DESIGNED 122 120 F-20 Cr18 1-16 1-16 124 122 E-22 F -20 G-18 18 I-16G 1-16G D-26 124 124 F-22 G-20 R20 H-1 8G I-18G J -16H D-26 C-26 C-26 C-26 27 ", 28" D26 D-26 G26 C-26 29 ", 30" 126 D-26 D-26 C-26 31" - 36" E24 12 D-26 D-26 37" - 42" F 24 E-24 E-26 126 43" - 48" G-22 F 24 F 24 124 49" - EW 1+20G G24 F 24 F-24 5511- 601" 1-18G G-22 G-24 F 24 61" - 72" I-13G K22G H-22G 73" - 84" 118G 120E I 1I1-24 1-22G J -18H I-18H 4-20H I-22H 97" - 1088 " K -18H J -18H I-18H 109 " - 120" K -1881 J -1881 Revisions: �2 /ro /m9 OWNEiR CHANGE GODRD INATION 0 O 0 0 a� z �00 J LO a Q w Q cry _ a v o w w w I _J U-)~ Q w w 0 � O m s = a w o w00 Q cl� 00 w �0) _ °; w a Q O J FT-) N W � � v 0 do'00a 0QO� w 00 `� 0 Q U �M 0 � �C-4 � O,Ic Q_ z d pZ Q �MmpZ< Lj E� a 0 d 8 0 0 W LL-] _I 0 = LL -� LJJ 0 W 7 PERMIT SET DRAWN: CHECKED: P.A. DATE: os -25 -Oa 3 SCALE: AS NOTED SEAL, s " fad MA �(G44 a. iaC�j78 Sheet No. M0 »00 I JOB MINIMUM HANGER SIZES FOR ROUND DUCTS DUCT fvIAXIMUa1 WIRE ROD STP.P,P DIAMETER SPACING DIAfV1ETER 10 DN '12' ONE 12 ga. 1/4" "1 "x 22 ga 250 mm DN 3.7 rn ONE 2.75 rnrn. 6.4 mrn 25.4 X 0.85 rnm 1111-1811 12' TVVO '12 ga. OR ONE ga. 114" 1 "x 22 ga 460 rnrn 3.7 m ONE 4.27 rnrn. 6.4 mrn 25 4 X 0.85 rnm 19" - 24" 12' TWO '10 ga. 1/4" '1 "x 22 ga 610 mm 3.7 m TWO 3.51 rnrn. 6 4 mrn 25.4 X 0.85 rnrn 25" - 36" 12' TWO 8 ga. 318" 1" x 20 ga 900 mm 3.7 rn TvV0 2.7 mrn. 9.5 mrn 25.4 X 1.00 mm 37" - 50" 12' PNO 3/8" TWO 1 X 20 ga. 1270 mm 3.7 rn TWO 9.5 mrn TWO 25.4 X1.00 rnrn 51 " - 60" 12' TWO 318" TWIO T' X 18 ga. 1520 mm 3.7 rn pVVO 9.5 mrn 7010 25.4 X 1 31 mm 61 " - 84" 12' TWO 318" TWO 1"'X 16 ga. 2130 mm 3.7 rn T`VVO 9.5 rnrn TWO 25.4 X '1.61 mm NOTES: 1. STRAPS AREGALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL: WIRE IS BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED STFFI . ALL A.REA.LTEP.NATIVES. 2. TABLEALLOdVS FOR CONVENTIONAL WALL THICKNESS, AND .JOINT SYSTEMS PLUS ONE LB /SF INSULATION WEIGHT. IF HEAVIER DUCTS ARE TO BE INSTALLED, AD UST HANGER SE/ ES TO BEV'OTHIN THEIR LOAD LINITTS. HANGER SPACING MAY BE ADJUSTED BY SPECIAL ANALYSIS. Revisions: �2 /ro /m9 OWNEiR CHANGE GODRD INATION 0 O 0 0 a� z �00 J LO a Q w Q cry _ a v o w w w I _J U-)~ Q w w 0 � O m s = a w o w00 Q cl� 00 w �0) _ °; w a Q O J FT-) N W � � v 0 do'00a 0QO� w 00 `� 0 Q U �M 0 � �C-4 � O,Ic Q_ z d pZ Q �MmpZ< Lj E� a 0 d 8 0 0 W LL-] _I 0 = LL -� LJJ 0 W 7 PERMIT SET DRAWN: CHECKED: P.A. DATE: os -25 -Oa 3 SCALE: AS NOTED SEAL, s " fad MA �(G44 a. iaC�j78 Sheet No. M0 »00 I JOB