08-1177R-001South Miami Hospiltal Affiliate of Baptist Health Systems of South Flori GENERAL NOTES I.- CONTRACTOR IS BEING PROVIDED WITH COMPLETE SETS OF DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUBCONTRACTORS WITH COMPLETE SETS OF DRAWINGS. INTENT IS FOR ALL SYSTEMS AND EQUIPMENT TO BE PROVIDED WITH UTILITY CONNECTIONS AS REQUIRED FOR OPERATION. EXAMPLE - IF A SINK IS SHOWN IN THE ARCHITECTURAL PLANS, THE PLUMBING PLANS DO NOT SHOW A WATER OR DRAWINGS CONFECTION THE ENGINEER WILL PROVIDE THE DESIGN DETAILS IN ACCO12DANCE WITH THE DESIGN CRITERIA FOR THE REST OF THE INSTALLATIONS, CONTRACTOR IS 12ESPONSIBI E FOR PRO- VIDING THE CONNECTION AT NO ADDITIONAL COST TO THE OW- NER, 2.- CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE DURING THE BIDDING PERIOD AND VERIFY THAT THE CONDITIONS ARE AS DESCRIBED IN THE DOCUMENTS. DISCREPANCIES ARE TO BE NOTED IN WRITING, AND NOTIFY ARCHITECT / ENGINEERS. CONTRACTOR ACCEPTS CONDITIONS AS THEY ARE ON THE SITE, AND MUST PROVIDE' SYSTEMS AND WORK AS DESCRIBED IN THE CONTRACT DOCUMENTS AT NO ADDITIONAL COST TO THE OWNER. 3.- DIMENSIONS PROVIDED ARE NOMINAL, NOT ACTUAL. THEY TAKE AS A BASIS EXISTING WALLS. IF DISCREPANCIES ARE FOUND, NOTIFY ARCHITECT IMMEDIATELY FOR COORDINATION. IF CON- TRACTOR PROCEEDS, HE DOES SO AT HIS OWN RISK AND IS RESPONSIBLE FOR ALL EXPENSES INCURRED, IF AT THE DISC12E TION OF THE OWNER OR THE ARCHITECT, THE WORK WAS, TO BE RE -DONE, 4.- SHUTDOWN OF UTILITIES IF A SHUTDOWN OR ANY TYPE OF INTER- FERENCE WITH EXISTING SYSTEMS IS ANTICIPATED, THE CONTRAC TOR MUST NOTIFY THE OWNER, 72 HOURS IN ADVANCE-AND OBTA- IN APPROVAL IN WRITING PRIOR TO PROCEEDING. 5.- CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS AND USE ALL APPROPRIATE CONSTRUCTION METHODS / TECHNIQUES TO PROTECT EXISTING UTILITIES AND OTHER PROPERTY NOT NOTED FOR REMOVAL. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES INCURRED DURING CONSTRUCTION AND SHALL REPAIR ANY DAMAGES AT NO EXPENSE TO THE OWNER. 6.- IF THERE IS A DISCREPANCY BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, THE CONTRACTOR IS TO OBTAIN CLARIFICATION DURING THE BIDDING PERIOD. IF THE DISCREPANCY COMES UP DURING TI-E CONSTRUCTION, IT IS ASSLUVED THE CONTRACTOR BID THE MOST EXPENSIVE WAY AND WILL DO THE WORK AS PER THE DIRECTION OF THE OWNER /ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. T- ABBREVIATIONS THROUGHOUT THE PLANS ARE THOSE IN COM- MON USE, ARCHITECT WILL DEFINE INTENT OF ANY IN QUESTION 8.- THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY BARRIERS, LIGHTING, COVERINGS, F112E PREVENTION AND OTHER EQUIPMENT TO PROTECT THE SAFETY OF ALL PERSONS AND THE PROPERTY THROUGHOUT THE ENTIRE PERIOD OF THE CONSTRUC _ TION CONTRACT. 9.- THE CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT WITH SUBCONTRACTORS, AS WELL AS SHOP DRAWINGS AS APPROVED BY ARCHITECT, BEFORE PROCEEDING WITH THE WORK. 10.- ALL ITEMS USED IN CONSTRUCTION, BUT NOT SPECIFICALLY MENTIONED HEREIN, SHALL CONFORM TO ALL LOCAL CODES AND STATE ORDINANCES AS TO APPLICATION AND USE. II.- PROVIDE ELECTRIC INSULATION BETWEEN ALL DISSIMILAR METAL AND ALSO BETWEEN CEMENT AND METAL. 12.- THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS TO COMPLETE THE PROJECT, 13.- CONTRACTOR TO REVIEW ALL EXISTING BUILDING SYSTEMS AS TO THEIR COMPLIANCE WITH ALL LOCAL AGENCY REQUIREMENTS AND BRING ANY NON - CONFORMING ITEMS TO ARCHITECT'S AND ENGINEEP'S ATTENTION. 14 GENERAL CONTRACTOR IS TO PROTECT EXISTING ADJACENT AREAS TO WHERE WORK IS TO BE PERFORMED. ANY EXISTING MILLWORK, EQUIPMENT DAMAGED DUE TO WORK PERFORMED SHALL BE REPAIRED/ REPLACED TO MATCH EXISTING (TYPICAL UNLESS OTHERWISE NOTED). 15.- DRAWINGS ARE SCHEMATIC SHOWING RELATIVE LOCATIONS AND CONNECTIONS AND SHALL NOT BE SCALED AT ANY TIME. 16.- ALL WOOD BLOCKING WITHIN BUILDING STRUCTURE, SHALL BE FIRE - RETARDANT TREATED AS PER SPECIFICATIONS. 17.- GENERAL CONTRACTOR SHALL INSPECT ALL EXISTING RATED WALLS / PARTITIONS WITHIN SCOPE OF WORK AREA CONTRACTOR SHALL UPGRADE EXISTING PARTITIONS AS REQUIRED TO MAINTAIN THE INTEGRITY OF THE DESIGNATED RATING. 18.- ELEVATION AND LEVELS A. ALL NUMERICAL ELEVATIONS ARE TO TOP OF CONCRETE SLAB, UNLESS NOTED OTHERWISE. 19.- ALL INTERIOR GYPSUM WALL BOARD IS 5/8' TYPE X G.W.B. ON METAL STUDS OR FURRING CHANNELS UNLESS NOTED OTHERWISE, SIZES AS DIMENSIONED ON FLOOR PLANS. SEE NOTES 9 FOR LOCATION OF WATER RESISTANT G.W.B. 20.- PROVIDE WATER RESISTANT TYPE X G.W.B. IN ALL TOILETS. AND JANITOR'S CLOSETS. 21.- BEFORE PATCHING ANY FIRE - RATED C.M.U. PARTITION. FILL ANY EXPOSED CELLS SOLID WITH GROUT. 22,- PROVIDE FINISH WALL KINDER AND BEHIND ALL EQUIPMENT AND CASEWORK. 23.- LOCATION AND SIZE OF CEILING AND WALL ACCESS PANELS SHALL BE DETERMINED BY THE POSITION OF VALVES AND OTHER MECHANICAL AND ELECTRICAL ITEMS WHICH REQUIRE ACCESS. THE CONTRACTOR SHALL COORDINATE WITH ALL TRADES. THE ARCHITECT SHALL REVIEW AND APPROVE ALL FINAL LOCATIONS OF ACCESS PANELS PRIOR TO INSTALLATION. 24.- THERE SHALL BE NO BACK - TO BACK ELECTRICAL TELEPHONE OR OTHER OUTLETS. 25.- ALL VERTICAL PIPING AND COLUMNS, EXPOSED IN ROOMS SHALL BE FURRED WITH METAL STUDS AND DRY WALL AND FINISI -ED TO MATCH ADJACENT WALLS, UNLESS NOTED OTHERWISE, EXCEPTIONS; A. ELECTRIC CLOSETS C. MECHANICAL ROOMS B. TELEPHONE CLOSETS D. STAIRS 26.- WHERE HVAC OR OTHER MECHANICAL, ELECTRICAL AND PLUMBING ITEMS PENETRATE PARTITIONS, STUDS SHALL BE BRACED AND FRAMED TO STRUCTURE AS REQUIRED TO PROVIDE ADEQUATE SUPPORTS. ALL PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED TO PROVIDE FIRE, SMOKE AND / OR ACOUSTICAL ISOLATION OF SPACES WITH APPROPRIATE FIRE S.T.0 MATERIAL. 27.- SEE INTERIOR ELEVATIONS FOR FINISHES AND FINISH DETAILS FOR INTERIOR SPACES. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR ACOUSTICAL TILE FINISH. 28.- SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION OF CEILING MOUNTED MECHANICAL, ELECTRICAL FIXTURES. 29.- STAGGER JOINTS VERTICALLY AND HORIZONTALLY IN ALL G.WB. PARTITIONS EA. SIDE OF PARTITION, JOINTS STAGGERED MINIMUM 7 -O". UNLESS OTHERWISE NOTED. 30, CONTRACTOR SHALL CONFIRM THAT ALL EXISTING EXPOSED STEEL COMPLIES WITH N.F.P.A FIRE PROTECTION REQUIRE- MENTS. CONTRACTOR SHALL PROVIDE ALL NECESSARY INSULA- TION /FIRE PROTECTIVE COATINGS. 31, CONTRACTOR TO SUBMIT ALL SHOP DRAWINGS TO ARCHITECT AND THE BUILDING DF,�PARTMENT FOR APPROVAL. (ELEVATOR, TRUSSES, WINDOWS, ETC.)' 32. CONTRACTOR REQUIRED TO PULL SEPARATE DEMOLITION PERMIT. BAPTIST HEALTH BREAST CENTER - SURGICAL PRACTICE S011TH MIAMI HOSPITAL MEDICAL ,ARTS BUILDING 6200 S.W. 73 STREET SOUTH MIAMI, FLORIDA 33143 TEL: (786) 662 -4175 Fax: (786) 668 -5156 - INTERIOR REMODELING ONLY - SEPTEMBER 25, 2008 EB0000924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 2600 DOUGLAS RD. SUITE 605 CORAL GABLES, FLORIDA 33134 TELEPHONE: (305) 444 -1679 FAX: (305) 448 -1405 E-MAIL ADDRESS: GRALMAIL@L.JAAPA.COM � 'T )kKA09 a am AM AW rr o D A o architect s FLORIDA LICENSE #AA0002689 7400 N.W. 7th Street Suite 101 Miami, Florida 33126 Te6 (305)265 -7177 Fax: (305)262 -8435 LtAS E. NAYA, A.I.A Fl. AR0008063 PROJECT NUMBER: 23003 PERMIT SET ■ INDEX OF DRAWINGS LIFE SAFETY LS -1 FIRST FLOOR LIFE SAFETY P - -PHASE I LS -2 THIRD FLOOR LIFE SAFETY P -PHASE I INTERIOR RESIGN ID-1 FLOOR FINISH PLAN. ID-2 FLOOR PLAN - WALL FINISHES IAYOUT�. `� ID -3 THIRD FLOOR FINISH PLAAN AND (PALL FINISHES LAYOUT. ID-4 FINISH SCHEDULE AND TYPIVCAL ELEVATION. ^-^- ID-5 FINISH SPECIFICATION. ARCHITECTURAL SP -1 SITE PLAN. A -1 DEMOLITION PLAN, LEGEND AND NOTES. A -2 FIRST FLOOR PLAN HASE I. A -3 THIRD FLOOR PLAN PLi48F I. A -4 FIRST EQUIPMENT PLAN. PHASE I. A -5 THIRD EQUIPMENT PLAN PHASE U. A -6 FIRST REFLECTED CEEGING -PHASE I. A -7 THIRD REFLECTED CEII', NG P -PHASE H. A -8 INTERIOR ELEVATIONS. A -9 CABINET DETAILS ANN; NOTES.. A -10 FINISH SCHEDULE AND TYPICAL RESTROOM NOTES AND DETAILS. A -11 DOOR SCHEDULE, NOTT;S AND DETAILS. A -12 PARTITION TYPES, NO'T'ES AND DETAILS. A -13 CEILING DETAILS. A -14 MISCELLANEOUS DETAILS. A -15 PENETRATION AND FIRE RATING DETAILS. A -16 PENETRATION AND FIRE RATING DETAILS. A -17 PENETRATION AND FIRE RATING DETAILS. 01- -� � �, - 161W1,11 MO.00 SYMBOLS LEGEND AND GENERAL NOTES HVAC. M3.00 FIRST FLOOR PLAN -HVAC. M3.01 THIRD FLOOR PLAN -HVAC. M6.00 SCHEDULES HVAC. M7.00 DETAILS HVAC. PLUMBING PO.00 GENERAL NOTES AND DETAILS. P3.00 FIRST FLOOR PLAN - PLUMBING. P3.01 THIRD FLOOR PLAN -- PLUMBING. P5.00 ISOMETRIC DIAGRAM - PLUMBING. P7.00 DETAILS - PLUMBING. FIRE PROTECTION FPO.00 GENERAL NOTES AND DETAILS. FP3.00 FIRST FLOOR PLAN FIRE PROTECTION. FP3.00 THIRD FLOOR PLAN FIRE PROTECTION. ELECTRICAL EO.00 GENERAL NOTES AND LEGEND- ELECTRICAL. EO.01 GENERAL NOTES AND DEMOLITION NOTES - ELECTRICAL. E3.00 FIRST FLOOR DEMOLITION PLAN - LIGHTING- ELECTRICAL. E3.01 FIRST FLOOR DEMOLITION PLAN -'- POLDER- ELECTRICAL. E3.02 DEMOLITION THIRD FLOOR PLAN - LIGHTING- ELECTRICAL. E3.03 DEMOLITION THIRD FLOOR PLAN - POWER- ELECTRICAL. E3.04 FIRST FLOOR PLAN - LIGHTING - ELECTRICAL. E3,05 FIRST FLOOR PLAN - POWER- ELECTRICAL. E3.06 FIRST FLOOR PLAN - SYSTEMS - ELECTRICAL. E3.07 THIRD FLOOR PLAN - LIGHTING- ELECTRICAL. E3.08 THIRD FLOOR PLAN - POWER- ELECTRICAL. E3.09 THIRD FLOOR PLAN- SYSTEMS - ELECTRICAL. E5.00 RISER DIAGRAM - ELECTRICAL. E5.01 RISER DIAGRAM- ELECTRICAL. E6.00 PANELBOARD SCHEDULES -- ELECTRICAL. BUILDING INFORMATION ORIGINAL BmfILDING DESCRIPTION BUILDING JURISDICTION SOUTH MIAMI, MIAMI DADE COUNTY PRIMARY USE CLASS : BUSINESS NUMBER OF STORIES 6 FLOOR EXISTING BUILDING NEW PROJECT DESCRIPTION PROJECT AREA: 1ST FLOOR -2,803 SQ.FT. 3RD FLOOR -- '1,356 SQ.FT. TOTAL: 4,159 SQ.FT. INTERIOR ALTERATION: : LEVEL H SPRINKLED FULLY SPRINKLERED APPLICABLE CODES FLORIDA BUILDING CODE 2004 EDITION FLORIDA FIRE PREVENTION CODE 2004 EDITION REVISIONS COORDINATION 08 2 -6 -09 OWNER CHANGE, &,' COORDINATION. AL 0 �l 0 ,I ABERF,VIATIONS ARCHI I EC ft#"L A M&YIA4TION& WOIi JWs DRMINCsB E AND L ANGLE L a AT L LENGTH C GENTERNG LAM LAMINATE O DIAMETER LAv LAVATORY • POUND OR NUMBER LBS POUNDS 14 L551HR POUNDS PER HOUR LD LINEAR DIFFUSER A/C AIR CONDITIONING LP LOW POINT ACI AMERICAN CONCRETE INSTITUTE LT LIGHT ACP ASBESTOS CEMENT PIPE M ACSC ASPHALTIC CONCRETE SURFACE COURSE ACU AIR CONDITIONING UNIT ACT ACOUSTICAL CEILING TILE MATL MATERIAL AD AREA DRAIN MAX MAXIMUM ADJ ADJUSTABLE MC MEDICINE CABINET A/E ARCHITE MM- MM- MECHANICAL AF ACCESS FLOORING R T MANUFACTURER MEMBRANE MFR AFF ABOVE FINISHED FLOOR AGGR AGGREGATE MIS MINIMUM AHU AIR HANDLING UNIT MISG MIS MASONRY ALT ALTERNATE MQ MASOONRY OPENING, AL ALUMINUM MTD MOUNTED ANN ANNUNCIATOR MTL METAL ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MUL MULLION ANT ANTENNA MULT MULTIPLE AP ACCESS PANEL N APL ACCESS PLENUM APROX APPROXIMATE ARCH ARCHITECTURAL N NORTH A55 ASBESTOS NEC NATIONAL ELECTRIC CODE ASPH ASPHALT NIC NOT IN CONTRACT ASTM AMERICAN SOCIETY OF TESTING t MATERIALS NO NUMBER RDM NOMINAL Id NPL NAME PLATE BAT BATTERY TUTS NOT TO SCALE BD BOARD BITUM BITUMINOUS BLDG BUILDING BLKG BLOCKING OA OVERALL BM BEAM BOT BOTTOM OBS OBSCURE OC ON CENTER C OD OUTSIDE DIAMETER DIM) OF$ OVERFLOW SCUPPER CAB CABINET OPP OPPOSITE CB CATCH BASIN CEM CEMENT CER CERAMIC CFM CUBIC FEET PER MINUTE PC PRECAST CONCRETE CG CORNIER GUARD PJ PIPE JOINT CHP CRICKET HIGH POINT PL PLASTIC C1 CAST IRON P LAM PLASTIC LAMINATE CIG CAST IRON (-OVER GIP CAST IRON PIPE PLAS PLASTER cJ CONTROL JOINT P PLYWOOD CLG CEILING PNINT T PAINT CLOD CEILING DIFFUSER PTD POINT PER TOWELIDISPENCER CLKG CAULKING PTN PARTITION CLO CLOSET PTR PAPER TOWEL RECEPTACLE CLP CRICKET LOW POINT CLR CLOSER CMP CORRUGATED METAL PIPE z CMU CONCRETE MASONRY UNIT QRT QUARTER (-NTR COUNTER QT QUARRY TILE CO CLEAN OUT COL COLUMN COMM COMMUNICATION CONC CONCRETE R CONK CONNECTION CONST5 CONSTRUCTION R REAR CONT CONTINUOUS RA RETURN AIR CPT CARPET TILE RAP RADIUS CT CERAMIC TILE RB REINFORCED BEAM CTR CENTER RCPT RECEPTION CTSK COUNTERSUNK RD ROOF DRAM REEI F REINFORCED R REQ REQUIRED DBL DOUBLE RESL RESILIENT DEG DEGREE IirsTR REGISTER DEPT DEPARTMENT RM ROOM DE51G DESIGNATION RO ROUGH OPENING DET DETAIL FaLL RAIN WATER LEADER DF DRINKING FOUNTAIN DG DOOR GRILLE PIA DAMETER 8 DAG DIAGRAM DIM DIMENSION DISR DISPENSER S STUCCO DN DOWN SC SCREED CONCRETE DO DOOR OPENING $CHED SCHEDULE DSP DRY STANDPIPE SEC SECOND DS DOWN SPOUT SO SMOKE DETECTOR DWGS DRAWINGS SECT SECTION DWR DRAWER SF SUPPLY FAN SG SPANDREL GLASS SGR SYNTHETIC GRADE SHT SHEET EA EACH SIG SIGNAL EC EPDXY COATING SIM SIMILAR EHD ELECTRIC HAND DRYER 5K SINK EL ELEVATION Sm SWEET METAL EJ EXPANSION JOINT SMK SMOKE ELEC ELECTRICAL SND SOUND ELEv ELEVATOR SPEC SPECIFICATION EMER EMERGENCY SFKR SPEAKERS ENCL ENCLOSURE SQ SQUARE ENGR ENGINEER SOFT SQUARE FEET EPNL ELECTRICAL PANEL SST STAINLESS STEEL EQ EQUAL ST STREET EQPT EQUIPMENT 5TC SOUND TRANSMISSION COEFFICIENT EST ESTIMATE STD STANDARD ET EXPANSION TANK ST -D STORM DRAIN EWC ELECTRIC WATER COOLER STL STEEL EXH EXHAUST STR _ STRUCTURAL EXST EXISTING SUSP SUSPENDED EXT EXTERIOR SYM SYhIMETRICAL 5Y5 SYSTEM R T FA FIRE ALARM FABL FIRE ALARM BELL T TOILET FD FLOOR DRAIN TB TIE BEAM FG FIBERGLASS TC TIE COLUMN FCO FLOOR CLEANOUT, TEL TELEPHONE FD FIRE DAMPER TEMP TEMPERATURE FDC FIRE DEPARTMENT CONNECTOR TIG TONGUE AND GROVE FOR FRE DOOR THK THICK FDN FOUNDATIONS TOG TOP OF CURB FDV FIRE•JDEPARTMENT VALVE TOPP TOP OF PARAPET FEC FIRE EXTINGUISHER CABINET TOS TOP OF SLAB FEX FIRE EXTINGUISHER TIP TOP OF PAVEMENT FF FNISH FLOOR TRD TREAD FH FIRE HYDRANT TS TUBULAR STEEL FIN FINISH T$TAT THERMOSTAT FL FLOOR Tv TELEVISION FM FACTORY MANUAL TW TOP OF WALL FLASH FLASHING TYP TYPICAL FLG FLANGE FLOUR FLUORESCENT U FOC FACE OF CONCRETE FOF FACE OF FINISH US UNDERCUT FOM FACE OF MASONRY UL UNDERI.IIRITER'$ LABORATORIES FOS FACE OF STUD UNF UNFINISHED FPRP FIREPROOF LION UNLESS OTHERWISE NOTED FPM FEET PER MINUTE UO$ UNLESS OTHER SPECIFIED FRO FRENCH DRAIN UR URINAL FS FULL SIZE UTIL UTILITY FT FOOT OR FEET FTG FOOTING FT -LB FOOT POUNDS FURR FURRING VB VNYL BASE FUT FUTURE VCT VINYL COMPOSITION TILE VERT VERTICAL SST VERIFY IN FIELD VOL VOLUME GA GAUGE L VT VAPOR TIGHT GAL GALLON 1v1'I' 4.� b;i�t1 °� I ITId1' VTR VENT THRU ROOF GALV GALVANIZED CITY GB GRADE BEAM SUII,„DING7 DEPT. W GEN GENERATOR GL GLASS B GROUND aCTUSAI :,'ECTlON uR WND G L L LOCK W WINDOW RE W/ WITH GR GILL GRD GRILLE WG WATER CLOSET GW3 GYPSUM WALL BOARD WCO WALL CLEANOl1T GYP GYPSUM ,APPROVED BY: -- _ - I� wuALLFABRIC W/O WITHOUT �J WP WATER PROOF `t 44 1J �2 ('//�� .. UJSGT - WAINSCOT CVaTE' ... / ,.... ,, . WP WEIGHT FIB HOSE BIB WWF WELDED WIRE FABRIC HC HANDICAPPED WWI WELDED WIRE MESH HDWD HARDWOOD HOWE HARDWARE HGT HEIGHT HM HOLLOW METAL HORIZ HORIZONTAL HP HIGH POINT HR HOUR HTR HEATER WVA(- HEATING, VENTILATION, AND AIR CONDITIONING HYD HYDRANT `ID INSIDE DIAMETER ( DIAht ) IN INCHES INT INTERIOR :1 OF (�✓n° .T r. A JAN JANITOR JB JUNCTION BOX :1 ` JCT JUNCTION JSK JANITORS SINK A � JT JOINT G' K �� �a KO KNOCK OUT