08-1177-033SECTION A -A A
INSULATION (IF REQUIRED
BY SPECIFICATION
RESILIENT TYPE
PIPE
I" THICK X 12' LONG SLEEVE
NEOPRENE FOAM (RUBATEX
OR ARMFLEX)
PIPE RING 1" GREATER THAN
PIPE O.D.
Ed
A
INSULATION STEEL -
SHIELD (SEE SPECS.
FOR SHIELD CAGE)
16 GAUGE X 12" LONG GALVANIZED
STEEL PIPE SHIELD
I 1 A A I/l Crl r'I^M
ADJUSTABLE TRAPEZE
CHANNEL OR ANGLE
TRAPEZE TYPE PIPE HANGER
N.T.S.
PIPE HANGER DETAILS
N.T.S.
"ONCRETE ANCHOR SELF DRILLING
J.L. LISTED THRU 4" PIPE SIZE
ROAD COUPLING, U.L. /F.M. GRINNELL
136 OR APPROVED EQUAL
ALL THREAD ROAD
RING
METAL PIPE OR CONDUIT
3M FIRE CARRIER CP 25 C
SCE OF WALL
MAI I
STAINLESS STEEL COVER
SCREWED TO THREADED
C.O. PLUG.
TYPICAL CLEANOUT DETAIL
N.T.S.
nnIA IT
METAL PIPE OR CONDUIT
3M FIRE CARRIER CP 25 CAUI
FIRE RATED CONC.
FLOOR SLAB
NOTES:
I- FLOOR OR WALL ASSEMBLY - MIN. 2 -1/2 IN. THICK REINFORCED LIGHTWEIGHT OR
A NORMAL WEIGHT (100 -150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED
OF ANY UL CLASSIFIED CONCRETE BLOCKS. MAX DIAM OF OPENING IS 30 -7/8 IN,
IA- STEEL FLOOR UNIT /FLOOR ASSEMBLY - AS AN ALTERNATE TO ITEM I, THE FLOOR
ASSEMBLY MAY CONSIST OF A FLUTED STEEL FLOOR UNIT / CONCRETE FLOOR
ASSEMBLY. THE FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS
AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL FLOOR- CEILING DESIGN THE
THE FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
CONSTRUCTION FEATURES:
I�.
SECTION A -A
A. CONCRETE - MIN 2-1/2 IN, THICK REINFORCED LIGHTWEIGHT ON NORMAL
WEIGHT (100 -150 PCF) CONCRETE, AS MEASURED FROM THE TOP PLANE
THE FLOOR UNITS.
B. STEEL FLOOR AND FORM UNITS - COMPOSITE OR NON - COMPOSITE 1 -1/2" TO
3 IN. DEEP FLUTED GALV STEEL UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR -
CEILING DESIGN. MAX DIAM OF OPENING IS 30 -7/8 IN.
2- THROUGH- PENETRANT- ONE METALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR
3M FIRE CARRIER SPACE BETWEEN PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN.
CP 25 CAULK TO MAX 7/8 IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES
OR CONDUITS MAY BE USED:
UL APPROVED PIPING SAFING ASSEMBLIES EQUAL
TO UL SYSTEM ttCAJ -1175 FOR INSULATED PIPE AND
SYSTEM nC -AJ -1291 FOR NON INSULATED PIPE
A. STEEL PIPE - NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER)
STEEL PIPE.
B. IRON PIPE - NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER)
COPPER PIPE.
D. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER)
COPPER TUBING.
E. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.
F. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
TUBING (EMT).
3- FILL, VOID, OR CAVITY MATERIAL - SEALANT - MIN 1/2 IN. THICKNESS OF FILL
MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR
WITH BOTH SURFACES OF WALL. -AT THE POINT CONTACT LOCATION BETWEEN
PIPE AND CONCRETE, A MIN 114 IN. DIAM BEAD OF FILL MATERIAL SHALL BE
APPLIED AT THE CONCRETE / PIPE INTERFACE ON THE TOP SURFACE OF FLOOR
AND ON BOTH SURFACES OF WALL.
PIPE PENETRATION FIRESTOP DETAIL
N.T.S.
PROJ. No. 18056 EB0000924
LOUIS J. AGUIRRE ASSOCIATES-. Rk �
CONSULTING ENGINEERS
2600 DOUGLAS RD. SUITE 605
CORAL GABLE.a; 7LORIDA -, _ 331 4
TELEPHONE: csobj -444 -1679
FAX: =, --
E -MAIL ADDRESS: GRALMAILOLJAAPA.COM
i
Revisions:
0
0
0
A
0
V rn N
a
Z o
F
cme a
a
v O
� N
W
V
V) N
cmd =
an
W
F
:�
LLJ
O n �uapi
1
A,
�o
p_"
C�
c�
1j •0
O
m
Q
V f
�U�I
1�
O k
�
z
LLJ
a
PERMIT SET
DRA H
CHECKED:
P.A.
DATE:
09-25-05
SCALE:
AS NOTED
SEAL
tip' M�,C,H/�NIC'AL: T
?NESFO N;FA.NA P.E.,
LICEAISi`' ' 6 88- 1 ;
Sheet No.
P7.00
JOB f 28003
+. r
�s