08-1177-025AIR DISTRIBUTION SCHEDULE
SYMBOL
SIZE
DESIGN CFM
DESIGNATION
A
B
V / PH I HZ
MANUF.
MODEL
NUMBER
30 % EFFICIENCY
MANUFACTURER
TITUS
TITUS
280
2000
-
277/1 /60
MODEL NO. AND / OR
PASS
PAR
1090
2000
CATALOG NO.
TITUS
VAV -111
1310
24 X24
24 X 24
TITUS
VAV -112
FRAME TYPE
1210
2000
TITUS
LAY -IN
LAY -IN
1360
2000
DEVICE TYPE
PERFORATED
PERFORATED
FUNCTION
SUPPLY
RETURN
VAV -308
PATTERN
SEE DRAWING
SEE DRAWING
TITUS
OPPOSED BLADE DAMPERS
YES
YES
NOTES:
1. ALTERNATE MANUFACTURERS CARNES, METALAIRE MAY BE SUBMITTED FOR APPROVAL.
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED, ALL AIR DEVICES FINISH SHALL BE BAKED OFF- WHITE.
4. SUPPLY, RETURN OR EXHAUST OUTLETS SERVED BY AN INDIVIDUAL DUCT BRANCH PROVIDED WITH AN ACCESSIBLE MANUAL VOLUME DAMPER
SHALL BE SUPPLIED WITHPOUT INTEGRAL O.B.D.
5. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, PROVIDE THE REQUIRED INSULATED SQUARE TO ROUND TRANSITION.
EXISTING VAV TERMINAL UNIT SCHEDULE
SYMBOL
SIZE
DESIGN CFM
CFM MIN
MAX BOX
CFM
EH KW &
STAGES
V / PH I HZ
MANUF.
MODEL
NUMBER
30 % EFFICIENCY
VAV -113
95% EFFICIENCY
880
280
2000
-
277/1 /60
TITUS
DESV 10
VAV -116
1090
2000
TITUS
VAV -111
1310
2000
TITUS
VAV -112
1210
2000
TITUS
VAV -114
1360
2000
TITUS
VAV -308
1200
2000
TITUS
REMARKS: 1. ALL UNITS TO BE PRESSURE INDEPENDENT NORMAL OPEN WITH ELECTRONIC
CONTROL OPERATOR.
2. ALL VARIABLE VOLUME BOXES SHALL BE DOUBLE WALL CONSTRUCTION WITH
INSTALLED R -VALUE OF 3.5 MIN. INSULATION BETWEEN WALLS.
3. MAXIMUM NOISE CRITERIA (25 NC).
N E W V A V T E R M I N A L U N I T S C H E D U L E
SYMBOL
SIZE
DESIGN CFM
CFM MIN
MAX BOX
CFM
EH KW &
STAGES
V I PH I HZ
MANUF.
MODEI_
NUMBER
30 % EFFICIENCY
VAV 308B
95% EFFICIENCY
700
280
1400
-
277/1 /60
TITUS
DESV 10
REMARKS: 1. ALL UNITS TO BE PRESSURE INDEPENDENT NORMAL OPEN WITH ELECTRONIC
CONTROL OPERATOR.
2. ALL VARIABLE VOLUME BOXES SHALL BE DOUBLE WALL CONSTRUCTION WITH
INSTALLED R VALUE OF 3.5 MIN. INSULATION BETWEEN WALLS.
3. MAXIMUM NOISE CRITERIA (25 NC).
EXISTING AHU # 1 DATA (BEFORE DEMOLITION)
AREA SERVED
FIRST FLOOR
LOCATION
MECHANICAL ROOM 107
AIR FLOW - CFM
15,680
OUTSIDE AIR - CFM
2,825
PRE - FILTER (PF)
30 % EFFICIENCY
FINAL FILTER (FF)
95% EFFICIENCY
SMOKE DETECTOR
YES ON SUPPLY AND RETURN DUCT (EXISTING)
EXISTING AHU # 1 DATA (AFTER NEW CONSTRUCTION)
AREA SERVED
FIRST FLOOR
LOCATION
MECHANICAL ROOM 107
AIR FLOW - CFM
15,680
OUTSIDE AIR - CFM
3,265
PRE - FILTER (PF)
30 % EFFICIENCY
FINAL FILTER (FF)
95 % EFFICIENCY
SMOKE DETECTOR
YES ON SUPPLY AND RETURN DUCT (EXISTING)
NOTE: THE O/A MUST BE ADJUSTED TO OBTAIN 3,265 CFM AS SHOWN ON SCHEDULE
AFTER NEW CONSTRUCTION IS FINISHED.
EXISTING EF -G (BEFORE DEMOLITION) DATA
AREA SERVED
FIRST FLOOR
LOCATION
CEILING
CFM
2,300
EXISTING EF-G
AREA SERVED
FIRST FLOOR
LOCATION
CEILING
CFM
2,740
NOTE: THE EXHAUSTAIR MUST BE ADJUSTED TO OBTAIN 2,740 CFM AS SHOWN ON
SCHEDULE AFTER THE NEW CONSTRUCTION IS FINISHED.
PROJ. No. 18056 E60000924
LOUIS J. AGWRE I A$�QCJ RTES P.A.
CONSULTING ENGINEERS
2600 DOUGLAS RD. SUITE 605
CORAL GABI_e , LORIDA --- - 33134' -
TELEPHONE: '305r 444 -16,79
FAX: ' 305) 418--14C6, -
E -MAIL ADDRESS: GRALMAILQLJAAPA.COM
Revisions:
0
0
0
0
w c
V 1 N
H � �
a
Q Z a�
H
� a �
� a �
u O
$ fA
w
Kai 2
Z
w
Lai V
F-� H
vi N
O
m
w
LLA
F
O �n
N
91"
O
��
O
m
V
Q 4
J
O � �
V)
LLj
V
Q >
xx
V
t�
PERMIT SET
DRAWL+
CHECKED.
P.A.
DATE:
09 -25 -08
SCALE:
A5 NOTED
SEAL
MECHANICAL: J
ERNE .DTO,�$MTAN,', P.E. I
LICENSE. 6086
A t I
Sheep
M6.00
JOB f _)aoo