08-1140-004I
DEMOL1110N LEGEND
1110"M DESCRIPTION
SPRINKLER HEADS TO BE RELOCATED
EXISTING TO REMAIN
EXISTING TO BE REMOVED
OEM Impliumem 1:11-malellam
TAMPER SWITCH 0. S. &Y.
GATE VALVE
ELECTRIC Nl-
FLOW SWITCH
PRESSURE GAUGE
& COCK
................
-------------------
PARTIAL C� S_ll
..............
0' 11' 2' 4' 8'
CONCRETE INSERT
SIC-DAL).- ------ -- -- - - - ----------------------- ---- ------- --- -------- ------ ---- - N 0 IN E NG HANGER DETAIL
SCPIPIE O
AL- -------------------- ------------------------------ ---------------------- ------------------------ NNE
NEW CONSTRUCTI-ON LEGEND
m I •
-b-E SCRIPTI6N__
K—FACT
PIPE NEW SPRINKLER HEADS FROM EXIS11NG LOCATION
LOCATION
EXISTING SPRINKLER HEADS TO REMAIN
5.6
EXISTING • REMAIN
AS NOTED
NEW CONSTRUCTION
CONNECT TO EXIST. AT THIS POINT
CONTRACTOR SHALL REFER TO ARCHITECTS REFLECTED CEILING PLAN FOR EXACT HEAD LOCATIONS.
0 CASE CASE SHALL SPRINKLER HEADS BE LOCATED MORE THAN 14'-0n ON CENTER.
'Z
. ...........................
ti
-------------------
1.
ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPUANCE W`TWTHE
------------ ....... ......
cc::,
- ,_
LOCAL FIRE CODES AND ORDINANCES AND INSTALLED IN ACCOMCE
WITH THE LATEST CODES AND STANDARDS.
zw
iz x Q
A. NFPA-13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS. (2002).
�E C'q
�i 0 0
B. NFPA-101 LIFE SAFETY CODE. (2003)
C)
Eli Lo
Q:
--- ------------- x (Typ)
LC40 co
D. FLORIDA BUILDING CODES (2004)
c"q
x
2.
-D
EXiS,-,'N-G -�NKLE-
N
3.
CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (6)
SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEINGNSTALLED.
4.
ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENT A NEAT AND
U.
BALANCED CEILING PATTERN UNLESS SHOWN OTHERWISE.
X
----------------
x
5.
CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES
x i
bc
6.
ry
(Typ)
------- --
7.
SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE
.'30R I I I
C
A*
�30z S, OPE
8.
ALL PRODUCTS ASSOCIATED WITH THE SPRINKLER SYSTEM SHALL BE
,a
: 10 0 \NNZ z; ""R \N: m
: w
UNDERWRITERS LABORATORIES (UL) LISTED AND FACTORY (FM) APPROVED.
FIRE PROTECTION SPECIFICATIONS
.4
Q)
r - -
S RA';'
C \',jl_A` l"DNS V�
CAL-`,
4
Ni:m; a m w; w
ALL PRODUCTS ASSOCIATED WITH THE SPRINKLER SYSTEM SHALL BE
""`;RTI,
L FIF\"--']- P N
D M0 L TI 0 Fl R E PIROTECTION
t
---------- -----------
ITT!] I
2'
PIPE
I
DEMOL1110N LEGEND
1110"M DESCRIPTION
SPRINKLER HEADS TO BE RELOCATED
EXISTING TO REMAIN
EXISTING TO BE REMOVED
OEM Impliumem 1:11-malellam
TAMPER SWITCH 0. S. &Y.
GATE VALVE
ELECTRIC Nl-
FLOW SWITCH
PRESSURE GAUGE
& COCK
................
-------------------
PARTIAL C� S_ll
..............
0' 11' 2' 4' 8'
CONCRETE INSERT
SIC-DAL).- ------ -- -- - - - ----------------------- ---- ------- --- -------- ------ ---- - N 0 IN E NG HANGER DETAIL
SCPIPIE O
AL- -------------------- ------------------------------ ---------------------- ------------------------ NNE
NEW CONSTRUCTI-ON LEGEND
m I •
-b-E SCRIPTI6N__
K—FACT
PIPE NEW SPRINKLER HEADS FROM EXIS11NG LOCATION
LOCATION
EXISTING SPRINKLER HEADS TO REMAIN
5.6
EXISTING • REMAIN
AS NOTED
NEW CONSTRUCTION
CONNECT TO EXIST. AT THIS POINT
lz
N
`71
E L E VA 0 N
+
aY
0
SPRINKLER HEADS:
ACCEPTABLE MANUFACTURERS: RELIABLE, AUTOMATIC, GEM, GRINNELL,
VIKING & CENTRAL CONCEALED AND UPRIGHT TYPE ?" ORIFICE, QUICK RESPONSE.
PIPE. INS7ALL.ATION-
PROVIDE HANGERS ON ALL ARM OUTS OF 12m OR MORE.
SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE
WITH UL FIRE RESISTANCE INDEX FOR THROUGH— PENETRATION FIRESTOP
SYSTEMS. COORDINATE REQUIREMENTS WITH DIVISION 7.
PROVIDE TRAPEZE TYPE HANGERS WHERE NECESSARY TO SUPPORT PIPE
WHEN STRUCTURAL STEEL IS NOT DIRECTLY ABOVE FOR SUPPORT.
SPRINKLER
HEAD LEGEND
TYPE
K—FACT
TEMP
LOCATION
11. CONCEALD CHROME PENDANT (QRS)
- Co I
5.6
165"
AS NOTED
SPRINKLER NOTES
CONTRACTOR SHALL REFER TO ARCHITECTS REFLECTED CEILING PLAN FOR EXACT HEAD LOCATIONS.
0 CASE CASE SHALL SPRINKLER HEADS BE LOCATED MORE THAN 14'-0n ON CENTER.
1.
ALL FIRE PROTECTION SYSTEM SHALL BE IN COMPUANCE W`TWTHE
cc::,
- ,_
LOCAL FIRE CODES AND ORDINANCES AND INSTALLED IN ACCOMCE
WITH THE LATEST CODES AND STANDARDS.
zw
iz x Q
A. NFPA-13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS. (2002).
�E C'q
�i 0 0
B. NFPA-101 LIFE SAFETY CODE. (2003)
C)
Eli Lo
Q:
C. CHAPTER 69A-3.012 STATE OF FLORIDA FIRE PREVEN11ON CODE. (2004)
LC40 co
D. FLORIDA BUILDING CODES (2004)
c"q
x
2.
MAKE ALL OFFSETS REQUIRED AS PER JOB CONDITIONS.
3.
CONTRACTOR TO PROVIDE AND TURN OVER TO THE OWNER AT LEAST (6)
SPARE SPRINKLERS OF SAME TYPE AND TEMPERATURE RATING BEINGNSTALLED.
4.
ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENT A NEAT AND
BALANCED CEILING PATTERN UNLESS SHOWN OTHERWISE.
5.
CONTRACTOR SHALL COORDINATE WITH STRUCTURE AND OTHER TRADES
BEFORE INSTALLING SPRINKLER WORK.
6.
INSTALL PIPING TIGHT TO STRUCTURE WHERE POSSIBLE,
7.
SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE
PROTECTION CONTRACTOR.
8.
ALL PRODUCTS ASSOCIATED WITH THE SPRINKLER SYSTEM SHALL BE
UNDERWRITERS LABORATORIES (UL) LISTED AND FACTORY (FM) APPROVED.
FIRE PROTECTION SPECIFICATIONS
Q)
r - -
S RA';'
C \',jl_A` l"DNS V�
CAL-`,
4
ALL PRODUCTS ASSOCIATED WITH THE SPRINKLER SYSTEM SHALL BE
4-4
UNDERWRITERS LABORATORIES (UL) LISTED AND .FACTORY (FM) APPROVED.
PIPE
(D
INTERIOR PIPE AND FITTINGS:
k
4J".pc4
U2,
1. SCHEDULE 40 ASTM-135, ELECTRIC—RESISTANCE WELDED STEEL PIPE.
2. THREADABLE THINWALL, ASTM-135, ELECTRIC RESISTANCE WELDED BY
BERGER, AWED, OR BULL MOOSE.
FITTINGS:
A. MECHANICAL COUPLINGS: ROLL OR CUT GROOVE-RIGID TYPE BY
VICTAULIC, SPRINK OR GRINNELL.
B. CLASS 125 OR CLASS 250 CAST IRON SPRINKLER FITTINGS
MM
SCREWED, FLANGED, OR GROOVED—END.
C. ALL FITTINGS SHALL BE BY THE SAME MANUFACTURER.
SPRINKLER HEADS:
ACCEPTABLE MANUFACTURERS: RELIABLE, AUTOMATIC, GEM, GRINNELL,
VIKING & CENTRAL CONCEALED AND UPRIGHT TYPE ?" ORIFICE, QUICK RESPONSE.
PIPE. INS7ALL.ATION-
PROVIDE HANGERS ON ALL ARM OUTS OF 12m OR MORE.
SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE
WITH UL FIRE RESISTANCE INDEX FOR THROUGH— PENETRATION FIRESTOP
SYSTEMS. COORDINATE REQUIREMENTS WITH DIVISION 7.
PROVIDE TRAPEZE TYPE HANGERS WHERE NECESSARY TO SUPPORT PIPE
WHEN STRUCTURAL STEEL IS NOT DIRECTLY ABOVE FOR SUPPORT.
SPRINKLER
HEAD LEGEND
TYPE
K—FACT
TEMP
LOCATION
11. CONCEALD CHROME PENDANT (QRS)
- Co I
5.6
165"
AS NOTED
CONTRACTOR SHALL REFER TO ARCHITECTS REFLECTED CEILING PLAN FOR EXACT HEAD LOCATIONS.
0 CASE CASE SHALL SPRINKLER HEADS BE LOCATED MORE THAN 14'-0n ON CENTER.
FIRE PROTECTION LEGEND
E-4 pq
Ix
i II
cl!
I—
z
0
V
DATE:
00/00/00
DRAWN BY:
S. Kovacs
NICET IV
Cart. #074567
210 4 8
SCALE:
W=I'—Cr, Unlm Naiad
FP 2. 1