LEGEND
SYMBOL DESCRIPTION MOUNTING
HEIGHT
LIGHTING
�K?
LIMOUNTINGHT GRRE - 'X` DENOTES FIXTURE TYPE -
ABOVE FINISHED CEILING
AFF
TaPEADETERM NES
AFG
Q
CRITICAL OR EQUIPMENT BRANCH LIGHT - `X` DENOTES
BREAKER
X e
FIXTURE TYPE - TYPE DETERMINES MOUNTINGRE
cd
MEG
SAFETY BRANCH LIGHT
CIRCUIT
�
- ERMINES MOUNTING
CLG
CEILING MOUNTED DEVICE
DISC
NORMAL BRANCH LIGHT FIXTURE - 'X' DENOTES FIXTURE TYPE
DIV
EX
®
TYPE DETERMINES MOUNTING
F
FRAME
F/A
CRITICAL OR EQUIPMENT BRANCH LIGHT FIXTURE - 'X' DENOTES
FBO
®X®
FLA
FIXTURE TYPE - TYPE DETERMINES MOUNTING
FU
®X®
LIFE SAFETY BRANCH LIGHT FIXTURE - `X' DENOTES
GROUND
HP
FIXTURE TYPE - TYPE DETERMINES MOUNTING
K
ej
EXIT LIGHT, PROVIDE DIRECTIONAL ARROWS AS INDICATED
MAIN CIRCUIT BREAKER
MLO
ON PLANS
NEC
NATIONAL ELECTRIC CODE
a+
EXIT LIGHT, PROVIDE DIRECTIONAL ARROWS AS INDICATED
OC
OVER CURRENT
OCP
ON PLANS
P
SWITCHES
S
SINGLE POLE SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
SPECIAL MOUNTING HEIGHT
TV
SINGLE POLE SWITCH - RED TOGGLE
AFF' 108 CL
S3
THREE WAY SWITCH - IVORY TOGGLE
3' -10'
AFF TO CL
S4
FOUR WAY SWITCH - IVORY TOGGLE
31-10'
AFF TO CL
SD
DIMMER SWITCH
3` -10®
AFF TO CL
SP
SINGLE POLE SWITCH WITH PILOT LIGHT
3' -i0'
AFF TO CL
ST
MOTOR RATED SWITCH WITH THERMAL OVERLOAD
WEATHERPROOF DEVICE, NEMA 313
XFMR
TRANSFORMER
PUSH BUTTON SWITCH (MUSHROOM BUTTON)
AFF P A
TO CL
POWER - RECEPTACLES
120V. DUPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
1' -6'
ABBREVIATIONS FOR EXCEPTIONS)
AFF TO CL.
120V. DUPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
AS NOTED OR
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
SEE SPECS
120V. QUADPLEX RECEPTACLE - IVORY (REFER TO RECEPTACLE
1' -6'
ABBREVIATIONS FOR EXCEPTIONS)
AFF TO CL.
120V. QUADPLEX RECEPTACLE - IVORY - SPECIAL MOUNTING HEIGHT
AS NOTED OR
(REFER TO RECEPTACLE ABBREVIATIONS FOR EXCEPTIONS)
SEE SPECS
/}-
120V. GFI RECEPTACLE (SPECIAL MOUNTING HEIGHT)
AS NOTED OR
SEE SPECS
t-
120V. GFI RECEPTACLE
AFF TO CL.
®
WIREMOLD - LENGTH AS REQUIRED - EMERGENCY POWER
ABOVE
COUNTER
®
WIREMOLD - LENGTH AS REQUIRED - NORMAL POWER
ABOVE
COUNTER
TELEPHONE /DATA/TV
.�
TELEPHONE OUTLET WITH PLATE
AFFV-6 CL.
,W
WALL TELEPHONE OUTLET WITH PLATE
AS NOTED OR
SEE SPECS
,--
TELEPHONE OUTLET WITH PLATE (SPECIAL MOUNTING HEIGHT)
AS NOTED OR
SEE SPECS
q
COMBINATION DATA /TELEPHONE OUTLET WITH PLATE
V -6'
AFF TO CL.
COMBINATION DATA /TELEPHONE OUTLET WITH PLATE
AS NOTED OR
(SPECIAL MOUNTING HEIGHT)
SEE SPECS
®
TV OUTLET FOR WALL OR CEILING
AS NOTED OR
SEE SPECS
PAGING /INTERCOM
PS
HOSPITAL PAGING SPEAKER
CEILING
QM
MONITOR DESK MOUNTED
Iw
INTERCOM WALL MODEL
IF
INTERCOM WALL MODEL (FLUSH MOUNTED)
DS
DOOR SWITCH MOUNTED IN DOOR JAMB
®
DOOR RELEASE PUSH BUTTON
NON - FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING /POLES)
MOTOR CONNECTION
Q
JUNCTION BOX
PANELBOARD - FLUSH MOUNTED
PANELBOARD - SURFACE MOUNTED
CONCEALED CONDUIT
CONDUIT CONCEALED IN FLOOR OR BELOW GRADE
HOMERUN TO PANELBOARD - NUMBER OF PHASE CONDUCTORS IN MINIMUM 314
CONDUIT UNLESS NOTED OTHERWISE
NOTES:
1. ONE NEUTRAL CONDUCTOR, ALTHOUGH NOT INDICATED, SHALL BE INCLUDED
-
IN EACH RACEWAY UNLESS OTHERWISE NOTED.
2. ONE INSULATED GREEN GROUNDING CONDUCTOR, ALTHOUGH NOT INDICATED, SHALL
BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE
CONDUCTORS (ONE PER PHASE)PLUS NEUTRAL AND GROUND CONDUCTORS IN
EACH CONDUIT.
4. ALL CONDUCTORS SHALL BE #12 AWG UNLESS OTHERWISE NOTED.
E
F
ABBREVIATIONS
SYMBOL DESCRIPTION
ABC
ABOVE COUNTER
ACLG
ABOVE FINISHED CEILING
AFF
ABOVE FINISHED FLOOR
AFG
ABOVE FINISHED GRADE
BKR
BREAKER
CB
CIRCUIT BREAKER
cd
CANDELA
CKT
CIRCUIT
CL
CENTER LINE
CLG
CEILING MOUNTED DEVICE
DISC
DISCONNECT
DIV
DIVISION
EX
EXISTING
F
FRAME
F/A
FIRE ALARM
FBO
FURNISHED BY OTHERS
FLA
FULL LOAD AMPS
FU
FUSE
G
GROUND
HP
HORSE POWER
K
KILO
MCB
MAIN CIRCUIT BREAKER
MLO
MAIN LUGS ONLY
NEC
NATIONAL ELECTRIC CODE
NIC
NOT IN CONTRACT
OC
OVER CURRENT
OCP
OVER CURRENT PROTECTION
P
POLE
PH
PHASE
SMH
SPECIAL MOUNTING HEIGHT
TV
TELEVISION
TYP
TYPICAL
UH
UNIT HEATER
UG
UNDER GROUND ELECTRICAL
UON
UNLESS OTHERWISE NOTED
V
VOLT(S)
VA
VOLT - AMPS)
W
WATT(S), WIRE, WALL TELEPHONE OUTLET
WP
WEATHERPROOF DEVICE, NEMA 313
XFMR
TRANSFORMER
4
A. REFER TO VENDOR DRAWINGS FOR ELECTRICAL REQUIREMENTS FOR
ONBOARD IMAGING (OBI) EQUIPMENT INSTALLATION. PROVIDE ALL CIRCUIT
BREAKERS, SWITCHES, PUSHBUTTONS, WIRE WAYS, LOAD CENTERS,
ELECTRICAL DUCTS, CONDUIT, WIRING, BACK BOXES, ELECTRICAL DEVICES,
AND GROUNDING AS REQUIRED BY THE VENDOR. COORDINATE ALL WORK
WITH VENDOR. PROVIDE ALL FINAL TERMINATIONS AS DIRECTED BY VENDOR.
PERFORM ALL WORK IN ACCORDANCE WITH NEC AND NFPA 99.
B. CONTRACTOR TO OBTAIN A LISTING FROM THE MANUFACTURER OF ALL
INTERCONNECTING CABLES IDENTIFYING THE USE, TYPE OF CABLE, AND
CLASS OF THE SYSTEM (I.E., POWER, COMMUNICATION, CLASS 1, CLASS 2,
ETC.) FOR FIELD VERIFICATION ON THE SEPARATION OF THE DIFFERENT
WIRING SYSTEMS.
C. CONTRACTOR IS RESPONSIBLE FOR ALL REQUIREMENTS AND DETAILS
IN THE VENDOR DRAWINGS.
D. ALL EQUIPMENT MUST BE BONDED TO THE RACEWAY SYSTEM. WHERE
FLEXIBILITY IS REQUIRED, FLEXIBLE METAL CONDUIT SHALL BE USED AS
PERMITTED BY THE NEC. WHERE THE DEGREE OF FLEXIBILITY DOES NOT
ALLOW THE USE OF FLEXIBLE METAL CONDUIT, A MULTISTRANDED
INSULATED COPPER CONDUCTOR MAY BE UTILIZEDTO PROVIDE RACEWAY
CONTINUITY FROM THE BEGINNING TO THE END.
E. CONTRACTOR SHALL COORDINATE WITH VENDOR AND PURCHASE ELECTRICAL
DUCT WITH SHEET METAL DIVIDERS TO PROVIDE SEPARATION FOR THE
FOLLOWING CABLE TYPES:
(1) 24 VOLT
(2) 300 VOLTS AND LESS
(3) 301 -600 VOLTS
(4) HIGH TENSION X -RAY CABLES
(5) VIDEO CABLES
F. ALL SECTIONS OF RACEWAY AND CONDUIT SHALL BE GROUNDED WITH AN
INDEPENDENT #6 AWG GREEN WIRE THAT IS TO BE ATTACHED USING
SOLDERLESS LUGS. ALL CEILING MOUNTED STRUCTURAL SUPPORT MEMBERS
AND CEILING PLATES SHALL ALSO BE GROUNDED. ALL GROUNDING CONNECTIONS,
TERMINALS, ETC. SHALL BE INSTALLED IN A MANNER TO PROVIDE ACCESSIBILITY
FOR INSPECTION, MAINTENANCE, REPAIRS, ETC. REFER TO VENDOR DRAWINGS
FOR ADDITIONAL GROUNDING REQUIREMENTS.
G. COORDINATE WITH ARCHITECT AND VENDOR, THE EXACT LOCATIONS OF ALL
ELECTRICAL EQUIPMENT FOR THE SPECIAL PROCEDURES ROOM, EQUIPMENT
ROOM AND CONTROL ROOM. COORDINATE ALL MOUNTING HEIGHTS PRIOR
TO INSTALLATION.
H. TEST THE EFFECTIVENESS OF THE GROUNDING SYSTEM BY VOLTAGE AND
IMPEDANCE MEASUREMENTS AS REQUIRED BY NFPA 99, SECTION 4.3.3.
RECORD THE RESULTS AND MAKE THEM AVAILABLE TO THE AUTHORITY
HAVING JURISDICTION AT THE TIME OF FINAL INSPECTION BY THESE
AUTHORITIES. METER USED SHOULD HAVE BEEN CALIBRATED WITHIN THE
LAST 12 MONTHS AND THIS METER SHALL BE AVAILABLE AT TIME OF
FINAL AHCA INSPECTION.
I. CONTRACTOR SHALL OBTAIN VENDOR INSTALLATION DRAWING PRIOR TO
THE START OF ANY WORK.
PROVIDE SURGE PROTECTION FOR ALL LOW VOLTAGE AND POWER CONNECTIONS TO
ALL ELECTRONIC EQUIPMENT IN CRITICAL CARE AREAS AND LIFE SAFETY SYSTEMS
AND EQUIPMENT SUCH AS FIRE ALARM, NURSE CALL AND OTHER CRITICAL SYSTEMS.
PROTECTION SHALL BE IN ACCORDANCE WITH APPROPRIATE IEEE STANDARDS FOR THE
TYPE OF EQUIPMENT PROTECTED.
3 4
5
0151 ... 111''i...
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS
REQUIRED TO ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED-.--- THE
CONTRACTOR
CONTRACTOR SHALL REFER TO THE NEW ARCHI TECTURAL, PLUMBI NG, FI RE P ; a CTI ONP
MECHANI CAL AND ELECTRI CAL WORK SHOWN ON THE OTHER DRAWI NGS OF THI S. -SET TQ_ _
DETERMINE THE EXTENT OF DEMOLITION REQUIRED.
WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN
TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE
INSTALLATION OF ANY STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.
THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR
REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING
CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR
SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS REQUIRED TO PREVENT
DAMAGE.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND
CONSTRUCTION DEBRIS GENERATED FROM WORK ON ALL FLOORS. TAKING CARE TO PREVENT
EXCESSIVE LOADING OF FLOOR ASSEMBLIES.
THE CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITS WHERE EXISTING EQUIPMENT IS
TO BE REMOVED AND DOWN STREAM DEVICES MAY BE EFFECTED.
THE CONTRACTOR SHALL COORDINATE ALL POWER INTERRUPTIONS WITH OWNER. SEE
SPECIFICATIONS.
WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, ALL
REMAI NI NG OPENI NGS I N THE SLAB AND WALLS SHALL BE FI LLED I N BY THE CONTRACTOR.
REMOVE ALL MISCELLANEOUS FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED
FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER.
THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND
CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY AND
EMERGENCY EGRESS EQUIPMENT.
THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND
CONSTRUCTION TO MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOORWAYS AND
STAIRS.
THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND
CONSTRUCTION TO PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST
EXTENT POSSIBLE. THIS EFFORT SHALL INCLUDE SCHEDULED COORDINATION WITH OWNER OF
ELECTRICAL SHUTDOWNS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL FLUORESCENT AND HID
TYPE LAMPS AND PROPER DISPOSAL OF SAID LAMPS AND SHALL PROVIDE VERIFICATION
OF LAMP DISPOSAL TO THE OWNER UPON REQUEST.
REMOVE ALL LIGHTING FIXTURES, RECEPTACLES AND DEVICES IN THE AREA OF DEMOLITION
AND PULL ALL CIRCUITS BACK TO NEXT ACTIVE DEVICE OR SOURCE OF POWER
PROVIDE PANEL SCHEDULES, TO THE ENGINEER, INDICATING THE CIRCUITS MADE SPARE BY DEMOLITION
AND THE EXISTING CIRCUITS THAT REMAIN ACTIVE.
IT SHALL BE THE RESPONSIBILITY OF THE CONSTRUCTION MANAGER (CM), GENERAL CONTRACTOR (GC), AND
THE SUB- CONTRACTORS (SC) TO STUDY ALL THE DRAWINGS AND DETAILS SO THAT THE INSTALLATION OF
ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC, AND SC SHALL VISIT THE SITE, INCLUDING DOING
AN ABOVE CEILING INSPECTION, DURING BIDDING TO SATISFY HIM /HER SELF THAT ALL PROVISIONS HAVE
BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES EXIST BETWEEN DRAWINGS AND /OR
SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE GENERAL CONTRACTOR IN WRITING PRIOR TO
BID DUE DATE. FAILURE TO DO SO WILL NOT BE ALLOWED ON A BASIS FOR ADDITIONAL COMPENSATION
TO CORRECT A DIFFICULTY OF DIFFERENCE FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS.
F1
ELECTRICAL DRAWING INDEX
NO. SHEET TITLE
EO.1
LEGEND, ABBREVIATIONS & DRAWING INDEX
SYSTEMS RESPONSIBILTY
SCHEDULE
SYSTEM
PARTIAL FLOOR PLAN - NEW WORK - ELECTRICAL
INTERIOR CABLE
INTERIOR CABLE
E4.1
EXTENT OF
E5.1
EQUIPMENT
EQUIPMENT
FURNISHED BY:
INSTALLED BY:
CONDUIT:
FURNISHED BY:
INSTALLED BY:
NOTES:
TELEPHONE /DATA
VENDOR
VENDOR
0
VENDOR
VENDOR
NOTES:
EC= ELECTRICAL CONTRACTOR
VENDOR =
OWNER /OWNER'S VENDOR
ALL OPEN
WIRING ABOVE CEILING SHALL
BE PLENUM RATED
O
TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR, TERMINATE WITH PLASTIC
BUSHING.
iD
VENDOR
CONTRACTED DIRECTLY BY OWNER.
F1
ELECTRICAL DRAWING INDEX
NO. SHEET TITLE
EO.1
LEGEND, ABBREVIATIONS & DRAWING INDEX
E1.1
PARTIAL FLOOR PLAN - LOCATION REFERENCE PLAN
E2.1
PARTIAL FLOOR PLAN - NEW WORK - ELECTRICAL
E3.1
ELECTRICAL RISER DIAGRAM
E4.1
ELECTRICAL STUDIES
E5.1
ELECTRICAL SPECIFICATIONS
no
E
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
SOUTH MIAMI
HOSPITAL
6200 SW 73 STREET, MIAMI, FLORIDA 33143
MEP ENGINEER:
Smith
SR Seckman
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm Certification - EB- 0000857
Alfred Esquivel PE - 45863
Bruce W. Peek PE - 35901
Donald Netinho PE - 48454
Erik S. Walter PE -63929
John E. Moulder PE - 33200
Michael A. Steward PE - 65701
Usman A.Tariq PE - 66485
SSR JOB # 0732091.0
PROJECT
SOUTH •
ACCELERATOR LINEAR
ORI UPGRADE
PROJECT ,rr.
6200 SW 73 STREET
Florida
KEY PLAN
COMM. •
O,
DATE: 00
DRAWN:
CHECKED:
Arr
DRAWING
ABBREVIATIONS
DRAWING
SHEET •
1
..
C,-
Fllilt d u
PROJECT
SOUTH •
ACCELERATOR LINEAR
ORI UPGRADE
PROJECT ,rr.
6200 SW 73 STREET
Florida
KEY PLAN
COMM. •
O,
DATE: 00
DRAWN:
CHECKED:
Arr
DRAWING
ABBREVIATIONS
DRAWING
SHEET •
1