Loading...
08-1048-012FBI C 1 A A IN 0 15010 - BASIC MECHANICAL REQUIREMENTS A. CODES & REFERENCES 1. FLORIDA STATE BUILDING CODE 2004 (WITH 2006 AMENDMENTS). 2. SMACNA 3. NFPA 101 (2003) 4. NFPA 90A (2002) 5. NFPA 99 (2002) 6.2006 GUIDELINES FOR DESIGN & CONSTRUCTION OF HEALTHCARE FACILITIES. B. SCOPE OF WORK 1. PROVIDE ALL REQUIRED PERMITS, LABOR, MATERIAL AND EQUIPMENT REQUIRED TO COMPLETE THE SCOPE OF THE PROJECT SHOWN ON THE DRAWINGS COMPLETE AND READY FOR OCCUPANCY AND USE BY OWNER.THE WORK SHALL INCLUDE BUT IS NOT LIMITED TO: a. REMOVAL, RELOCATION AND RE- INSTALLATION OF EXISTING EQUIPMENT AND SYSTEM. b. CONNECTIONS TO EXISTING OR NEW EQUIPMENT AND SYSTEMS. c. MODIFICATION OF EXISTING CHILLED OR HOT WATER SYSTEMS, STEAM SYSTEMS, CONDENSATE DRAINAGE, DUCTWORK, TEMPERATURE CONTROLS AND LIFE- SAFETY SYSTEMS. d. CUTTING AND PATCHING TO REMOVE EXISTING OR INSTALL NEW WORK. e. CLEANING AND TESTING. f. INSTRUCTION TO OWNER'S PERSONNEL. 2, PROVIDE ALL BUILDING PENETRATIONS REQUIRED TO COMPLETE PROJECT. ALL PENETRATIONS TO BE PATCHED AND SEALED TO BE WATERTIGHT. MAINTAIN FIRE RATINGS OF EXISTING STRUCTURE. 3. PROVIDE ALL NECESSARY DUCT AND EQUIPMENT SUPPORTS AND MATERIALS REQUIRED FOR INSTALLATION. PER THE REQUIREMENTS OF LOCAL, STATE OR FEDERAL CODES. C. REQUIRED SHOP DRAWINGS 1. INSULATION. 2. AIR DEVICES. 3. DUCTWORK COORDINATION DRAWINGS. D. MAINTENANCE MANUALS 1. PROVIDE MAINTENANCE MANUALS FOR ALL NEW EQUIPMENT CONTAINING ALL OPERATING AND MAINTENANCE DATA, SUBMITTALS. WARRANTEES. DIAGRAMS, INSPECTION REPORTS AND VALVE LISTS IN A 3 RING BINDER WITH POCKETS FOR DRAWINGS. PROVIDE OWNER WITH MINIMUM OF 2 COPIES. E. AS -BUILT DRAWINGS 1. THE CONTRACTOR SHALL MAINTAIN AN ACCURATE RECORD OF ALL CHANGES MADE TO THE CONTRACT DOCUMENTS (AS- BUILT). 2.THE CONTRACTOR SHALL PROVIDE THE ENGINEER 2 SETS OF COMPLETED AS -BUILT DRAWINGS. 3.THE PROJECT WILL NOT BE CONSIDERED COMPLETE UNTIL ACCURATE AS- BUILTS ARE DELIVERED. F. SUBSTITUTIONS I. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE SPECIFICATIONS SHALL BE CONSIDERED AS 'SPECIFIED STANDARD' OF QUALITY. NO SUBSTITUTIONS SHALL BE MADE WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER 10 DAYS PRIOR TO BID DATE. 2.ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECTS THE ELECTRICAL REQUIREMENTS SHALL BE COORDINATED BY THE MECHANICAL CONTRACTOR AND EQUIPMENT VENDOR WITH THE ELECTRICAL CONTRACTOR PRIOR TO SUBMITTING BIDS. 15050 - BASIC MATERIALS AND METHODS A. ACCESS PANELS - FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY GENERAL CONTRACTOR. 1. PROVIDE FOR ACCESS TO ALL SERVICEABLE EQUIPMENT IN WALLS AND CEILINGS. 2. MICOR STYLE M FOR DRYWALL. 3. MICOR STYLE K FOR PLASTER. 4. MINIMUM SIZE 161x16' . 5. NYSTROM, KARP, J.L. INDUSTRIES OR WILLIAMS PAINT. B. MECHANICAL SYSTEMS CLEANING 1. CLEAN AND TOUCH UP ALL FACTORY FINISHES. 2. FLUSH ALL HVAC SYSTEMS BEFORE CONNECTION TO EQUIPMENT. 3.CLEAN ALL CLOSED HVAC SYSTEMS WITH ALKALINE CLEANER CIRCULATED FOR 72 HOURS. C. CLEANING TESTING AND ADJUSTING I. THE MECHANICAL CONTRACTOR, AT HIS EXPENSE, SHALL CLEAN, REPAIR, ADJUST, CHECK, BALANCE AND PLACE IN SERVICE THE VARIOUS SYSTEMS HEREIN SPECIFIED WITH THEIR RESPECTIVE EQUIPMENT, ACCESSORIES AND PIPING. HE /SHE SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS REQUIRED TO PERFORM TESTS REQUIRED BY THESE SPECIFICATIONS AND BY THE GOVERNING AUTHORITIES. 2.N0 WORK SHALL BE COVERED OR CONCEALED UNTIL PROPERLY INSPECTED AND TESTED. D. HANGERS AND SUPPORTS 1. PROVIDE ALL NECESSARY DUCTWORK, HANGERS, RODS, CLAMPS AND ATTACHMENTS TO PROPERLY INSTALL AND SUPPORT DUCTWORK, AND EQUIPMENT FROM THE BUILDING STRUCTURE. 2. PROVIDE ANY ANGLE IRON OR UNISTRUT AND SUSPENSION RODS REQUIRED TO INSTALL EQUIPMENT AND DUCTWORK. 3. ALL SUPPORTS EXPOSED TO OUTDOORS SHALL BE CLEANED, PRIMED AND PAINTED TO PREVENT RUSTING. FINISH COLOR AS SELECTED BY OWNER. 4. THE USE OF BAILING WIRE OR PERFORATED METAL STRAPPING IS NOT PERMITTED FOR SUPPORTS. E. WARRANTY /GUARANTEE 1. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION OF THE PERIOD OF ONE YEAR. 2. DEFECTS OF ANY KIND DUE TO THE FAULTY WORK OR MATERIALS APPEARING DURING THE ABOVE MENTIONED PERIOD MUST BE IMMEDIATELY MADE GOOD BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE OWNER AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE ORIGINAL DEFECT OR REPAIR THERETO. 4 15250 - INSULATION A. INSULATION, ADHESIVES, COATINGS, SEALERS, TAPES, ETC. SHALL HAVE A FLAME SPREAD OF 25 OR LESS AND SMOKE DEVELOPMENT OF 50 OR LESS IN ACCORDANCE WITH ASTM E-84, NFPA 225. UL 723 AND MEET THE REQUIREMENTS OF NFPA 90A. ALL INSULATING R- VALUES TO MEET THE REQUIREMENTS OF THE FLORIDA ENERGY CODE. B. BLANKET TYPE DUCT INSULATION, JOHNS MANVILLE, CERTAINTEED, KNAUF, OWENS CORNING, MINIMUM R =6.0, FOIL FACED KRAFT VAPOR BARRIER : GLASS FABRIC & MASTIC ALL JOINTS. 1. ALL SUPPLY, OUTSIDE AIR AND RETURN WHERE CONCEALED FROM VIEW, R -6 . C. SEMIRIGID BOARD TYPE DUCT INSULATION I.51b DENSITY, CERTAINTEED IB -300, JOHNS MANVILLE, KNAUF, OWENS CORNING: GLASS FAB & MASTIC ALL JOINTS. 1. ALL SUPPLY, RETURN AND OUTSIDE AIR WHERE EXPOSED AND IN MECHANICAL ROOMS. 2. MINIMUM DUCT INSULATION THICKNESS AND R VALUES ARE AS FOLLOWS: a. SUPPLY AND RETURN AIR IN UNCONDITIONED SPACE: 2'(R-6 MINA.) b. SUPPLY AND RETURN AIR IN CONDITIONED INTERIOR SPACE: 1.5'(R-4.2 MINA.) c. OUTSIDE AIR: 2' (R -6 MINA.) d. SUPPLY AIR IN CEILING RETURN AIR PLENUM: 1.5' (R -4.2 MINA.) e. RETURN AIR IN CEILING RETURN AIR PLENUM: NOT REQUIRED. D. OUTSIDE INSTALLATION: 1. PIPE INSULATION COVER WITH 18 ga. STAINLESS STEEL COVER. SUBSTITUTE CELLULAR GLASS OF EQUIVALENT R VALUE FOR FIBERGLASS. 2. DUCT INSULATION CLOSED FOAM POLYISOCYANURATE 2' OR FOAM GLASS 3' THICK (R -8 MIN) COVER WITH GLASS CLOTH AND SEALER AND COVERED WITH LAMINATED ALUMINUM POLYESTER FIRM OR ALUMINUM METAL JACKET. 15890 - SHEET METAL DUCTWORK A. ALL DUCT TO BE INSTALLED ACCORDING TO 1990 EDITION OF SMACNA STANDARDS. B. ALL DUCT EXCEPT THAT SPECIFICALLY SHOWN IS TO BE GALVANIZED. RETURN, EXHAUST AND DUCT DOWNSTREAM OF CV BOXES TO BE 0 -2' PRESSURE CLASS. SUPPLY DUCT FROM FAN TO CV OR VAV BOX TO BE 4' CLASS. C. ALL SYSTEMS TO BE LEAKAGE TESTED. D. DUCTWORK ROUTED PARALLEL TO A WALL, RATED OR CORRIDOR SHALL BE INSTALLED WITH MINIMUM 6" CLEARANCE TO ALLOW FOR INSPECTION OF WALL PENETRATIONS. CONTRACTOR SHALL PROVIDE 12" CLEARANCE WHERE POSSIBLE, COORDINATE. E. BUTTON SNAPLOCK JOINTS OR SEAMS ARE NOT PERMITTED. 15910 - SHEET METAL ACCESSORIES A. AIR INLETS AND OUTLET. 1. REFER TO SCHEDULE. 2. ALL ALUMINUM CONSTRUCTION. 3. ACCEPTABLE MANUFACTURERS: TITUS, PRICE, METAL -AIRE, CARNES, ANEMOSTAT, NAILOR, POTTORFF. C. FLEXIBLE DUCTWORK (HOSPITALS) 1. TO BE OMNIAiR 1800 FLEXMASTER, OR WIREMOLD. 2. FLEXIBLE DUCTWORK SHALL BE ACOUSTICAL LOW PRESSURE TYPE WITH FLEXIBLE METAL INTERIOR. FIBERGLASS INSULATION WITH AN R VALUE OF 6.0 OR GREATER AND COPOLYMER SEAMLESS OUTSIDE SLEEVE. THE ENTIRE FLEXIBLE DUCT ASSEMBLY SHALL BE LISTED IN ACCORDANCE WITH UL -181 CLASS I AIR DUCT MATERIAL. THE MAXIMUM LENGTH OF ANY FLEX DUCT SHALL BE 4' -0'. FLEXIBLE DUCTWORK SHALL MEET THE FLORIDA MODEL ENERGY EFFICIENCY CODE. ALL JOINTS AT CONNECTIONS TO DIFFUSERS AND DUCTWORK SHALL BE SEALED WITH GLASS. FABRIC AND MASTIC. D. TERMINAL CONNECTORS 1. GENERAL - CONNECTORS SHALL BE RATED FOR 12' W.G., AND MEET NFPA 90A REQUIREMENTS. DUCT SHALL BE FABRICATED OR ALUMINUM SPIRAL HELIX AND REINFORCED RIP STOP ALUMINUM POLYESTER. PRESSURE DROP SHALL NOT EXCEED .6' /100' -O' AT 1000 FPM. WHERE INSULATION IS REQUIRED, FURNISH FACTORY APPLIED FIBERGLASS WITH REINFORCED VAPOR - BARRIER JACKET. INSULATION CONDUCTANCE VALUE SHALL NOT EXCEED 0.23 . NON - INSULATED DUCT SHALL BE EQUAL TO FLEXMASTER TYPE 3. INSULATED DUCT SHALL BE EQUAL TO FLEXMASTER 3M. 2. HIGH VELOCITY - MAXIMUM DEVELOPED LENGTH OF CONNECTOR SHALL BE 6' -O'. USE METAL DUCTS AND FITTINGS TO REACH WITHIN 6' -0' WHERE CONNECTORS ARE ATTACHED TO INSULATED DUCT, FURNISH INSULATED FLEXIBLE DUCT. E. BALANCING DAMPERS (RUSKIN MD -35 SERIES) 1. GENERAL -IN ALL DUCTWORK SYSTEMS, PROVIDE DAMPERS FOR PROPER CONTROL AND BALANCING OF AIR QUANTITIES. CONCEALED DAMPERS TO HAVE CONCEALED DAMPER REGULATOR. ALL COMPONENTS FOR PROPER OPERATION; Me. GEARS, LINKAGES, CABLE, ETC.) SHALL BE INCLUDED. 2. TYPE: FACTORY MANUFACTURED ONLY, OPPOSED BLADE FOR 12' AND LARGER AND SINGLE BLADE UP TO 11' IN HEIGHT. 3. MATERIAL: STEEL, 3V TYPE BLADES MOUNTED IN STEEL CHANNEL FRAME. 4. SHAFT: 3/9 SQUARE ROD OPERATOR WITH END BEARINGS AND GASKET SEAL AT DUCT PENETRATIONS. TERMINATE SHAFT IN DAMPER FRAME WITH BUSHINGS. 5. OPERATOR: LOCKING QUADRANT HANDLE WITH DAMPER POSITION INDICATOR AND INSULATION STAND OFF MOUNTING BRACKET FOR EXTERNALLY INSULATED DUCTWORK. 6. MANUFACTURER: RUSKIN MODEL MD -35 SERIES OR EQUAL BY AIR BALANCE, INC. OR GREENHECK. F. ACCESS DOORS I. ACCEPTABLE MANUFACTURERS: a. RUSKIN MODEL ADH22. b. VENCO CAD -10. c. GREENHECK HAD -10. 2. SIZE ACCESS DOOR AS FOLLOWS: a. DUCT SIZES UNDER 12': DOOR SIZED SUFFICIENT TO EQUIPMENT OR REPLACE FUSIBLE LINK. b. DUCT SIZES 12' TO 20': 12 'x12' DOOR. c. DUCT SIZES 20' TO 36': 18'x!8' DOOR. d. DUCT SIZES 36' AND ABOVE: 241x24' DOOR. 3. USE DOUBLE PANEL CONSTRUCTION, TWO SHEETS OF AT LEAST 24 GAUGE GALVANIZED STEEL WITH V THICK INSULATION BETWEEN PANELS. 4. MOUNT DOORS IN A RIGID FRAME OF AT LEAST 22 GAUGE FORMED GALVANIZED STEEL OR ALUMINUM. 5. PROVIDE LATCHES THAT PERMIT EASY REMOVAL OF ACCESS DOOR WHILE MAINTAINING POSITIVE CLOSING AND MINIMUM LEAKAGE. 6. PROVIDE SPONGE RUBBER GASKETS FOR ALL DOORS. 7. IN ACCORDANCE WITH NFPA 90A. IDENTIFY EACH ACCESS DOOR WITH s/¢ HIGH STENCILED LETTERS AS 'FIRE DAMPER'. 'SMOKE DAMPER', OR 'COMBINATION FIRE /SMOKE DAMPER'. G. BRANCH CONNECTIONS- CLINCH LOCK TYPE NOT PERMITTED. 3 4 0 m 15990 - TEST AND BALANCE A. PROVIDE COMPLETE TEST AND BALANCE OF ALL WATER AND AZR "SYSTEMS = IN ., ACCORDANCE WITH NEBB (NATIONAL ENVIRONMENTAL BALANCING DURi =AU) OR- -AAB4 (ASSOCIATED AIR BALANCE COUNCIL) STANDARDS. B. TEST AND BALANCE FIRM SHALL BE: 1. TOTAL DYNAMIC BALANCE - (954) 425 -0764. - 2. EARL HAYGOOD, INC. - (305) 266 -7070. 3. GFS CONSULTING - (305) 992 -4348. C. CONTRACTOR SHALL: 1. VISIT SITE AT START OF PROJECT AND COORDINATE REQUIRED BALANCING EQUIPMENT AND DAMPERS WITH MECHANICAL CONTRACTOR. 2. AIR SYSTEMS: a. MAKE CHANGES TO BELTS, PULLEYS, DAMPERS, VOLUME BOXES, ETC. TO OBTAIN DESIGN CONDITIONS AS REQUIRED BY TAB PROCEDURES. b. BALANCE SUPPLY" RETURN AND EXHAUST AIR OUTLETS WITHIN 10% OF DESIGN WHILE MAINTAINING REQUIRED PRESSURE RELATIONSHIPS. RECORD DESIGN AND ACTUAL TOTALS. c. MEASURE AND REPORT FAN RPM, FAN SUCTION PRESSURE, FAN DISCHARGE PRESSURE, FAN TOTAL PRESSURE AND PRESSURE DROP ACROSS COMPONENTS. DESIGN AND ACTUAL SUPPLY, RETURN, OUTSIDE AND EXHAUST AIR. d. ACTUAL AND DESIGN NAMEPLATE AMPERAGE ON FAN MOTORS. e. PRESSURE DIFFERENTIAL ACROSS DUCT SMOKE DETECTORS. f. ADJUST FANS FOR LOWEST STATIC PRESSURE REQUIRED TO DELIVER TO OUTLETS AS NOTED IN NEBB OR AABC PROCEDURES. 3. WATER SYSTEMS: a. ADJUST AND RECORD ACTUAL GPM AND SYSTEM SUCTION AND DISCHARGE PRESSURES (STATIC AND OPERATING). B. MOTOR DESIGN AND ACTUAL AMPERAGE AT PUMPS. c. DESIGN AND ACTUAL GPM AND TEMPERATURE DIFFERENCE ACROSS COILS, CONVERTERS, CHILLER AND TOWERS. d. ADJUST AND RECORD SYSTEM MAKEUP PRESSURE, RELIEF PRESSURE SETTING AND EXPANSION TANK PRESSURE. 4. CONFIRM OPERATION OF ALL CONTROLS, MANOMETERS AND SENSING DEVICES. 5. ON AHCA REVIEWABLE PROJECTS PROVIDE WRITTEN REPORT AT LEAST ONE WEEK BEFORE FINAL INSPECTION AND PROVIDE A TECHNICIAN DURING FINAL INSPECTION OF PROJECT. 6. CONTRACTOR SHALL PROVIDE FINAL SHEAVE CHANGE OUT AND ADJUSTMENT FOR MAXIMUM AMPRAGE TO INCLUDE DIRTY FILTER ALLOWANCE LOADING ALLOWING TH VFD TO RAMP UP IN RESPONSE TO FILTER LOADING. BERMELLO AJAMIL & PARTNERS, INC. Architecture Engineering Planning Interior Design Landscape Architecture 2601 South Bayshore Drive 10th Floor Miami, Florida 33133 E (305) 859 -2050 Fax (305) 860 -3700 SOUTH MIAMI HOSPITAL 6200 SW 73 STREET, MIAMI, FLORIDA 33143 1_7 IC rRIMMMM: Smith Ss�t S eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 Alfred Esquivet PE - 45863 Bruce W. Peek PE - 35901 Donald Netinho PE -48454 Erik S. Walter PE - 63929 John E. Moulder PE - 33200 Michael A. Steward PE - 65701 Usman A Tariq PE - 66485 SSR JOB # 0732092.0 $�y Y NO.- REVISIONS: PROJECT SOUTH MIAMI HOSPITAL LINEAR O. OBI UPGRADE PROJECT ADDRESS: 6200 SW 73 STREET Florida 331434989 KEY PLAN COMM. NO. SCALE: AS SHOWN DATE: 12 -20 -2007 DRAWN: CHECKED: A CADD FILE: DRAWING TITLE: SHEET SPECIFICATION - H VAC SHEET NO. M0.2