05-1614-001TI WIRE TYPES LISTED IN THE WIRE LEGEND ARE THE MANUFACTURER'S MINIMUM WIRING REQUIREMENTS. CONTRACTOR SHALL CHOOSE WIRE TYPES AND RATING TO MEET THESE REQUIREMENTS AND ALL OF THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE ANL NFPA FOR THE APPLICATI ❑NS AND LOCATIONS OF USE. WIRE LEGEND A = INITIATING DEVICE CIRCUIT - IDC 14/2 FPL MINIMUM. C = AUXILIARY CONTROL CIRCUIT - ACC 14/2 FPL MINIMUM. L = NOTIFICATI ❑N APPLIANCE CIRCUIT - NAC 14/2 FPL MINIMUM. P = POWER CIRCUIT 14/2 FPL MINIMUM. N = DATA COMMUNICATIONS 18/2 TWISTED /SHIELDED PAIR FPL MN = MULTI - ADDRESSABLE PERIPHERAL NETWORK 18/2 TWISTED /SHIELDED PAIR FPL MP = MAPNET POWER CIRCUIT - APC 14/2 FPL MINIMUM. - MAPNET SYMBOL LEGEND SYMBOL SIMPLEX MODEL # DESCRIPTION FRCP 4100 -9111 FACP 250 PT 6 NAC 4A 120VAC, WITH VOICE NAC 4009 -9201 NAC EXTENDER PANEL, IDNET, (IN MAIN BLDG. ONLY) NO PS- 12/24 -8 NAC EXTENDER PANEL- WHEEL❑CK (IN GARAGE ONLY) FAAP 4603 -9101 FIRE ALARM ANNUNICATOR PANEL T/C 4 F.B.O. FIRE ALARM TERMINAL CABINET E5 M 51 (FURNISHED BY ELECTRICAL CONTRACTOR) X Z1 4090 -9001 MONIT ❑R INDIVIDUAL ADDRESS MODULE Systems costing more than $5,000 are sealed or approved by a Fla Registered Engineer. X WNO Z Ln CONNECT TO N/❑ CONTACTS ONLY Z2 4090 -9002 CONTROL RELAY INDIVIDUAL ADDRESS MODULE Z3 4090 -9118 RELAY IAM WITH T -SENSE INPUT - ADDRESSABLE MODULE ❑ 4099 -9001 SINGLE ACTION ADDRESSABLE STATION M� � 2099 -9138 SINGLE ACTION STATI ❑N Ff1WP 2975 -9211 W.P. BACK BOX �0)rn 4090 -9051 ENCAPSULATED ADDRESSABLE MONITOR IAM 0 4098 -9792 SSD SENSOR BASE C) � aiL 4098 -9733 SSD HEAT SENSOR O 4098 -9714 SSD PHOTO SENSOR z 4098 -9792 SSD SENSOR BASE 12 4098 -9756 SSD SENSOR DUCT H ❑USING 4 WIRES 2098 -9799 SAMPLING TUBE 97' ® 2098 -9806 REMOTE TEST STATION RED LED KEY SWITCH ® 2088 -9007 MR101 RELAY, SPDT WITH LED 14 FS X F.B.O. FLOW DETECTOR SWITCH FN•- o_ _ 16 All devices in areas in which the voltage, temperature, and humidity variations exceed those conditions stated in NFPA 72, are listed for conditions and all such areas are identified. to_J FURNISHED BY DIVISION 15 X No weatherproof devices on this project 18 A specific sequence of operation including all alarm, supervisory, trouble and control functions such as fire suppression, door release, smoke control, etc., are specified on the plan. TAMPER (GATE VALVE) SWITCH TS See sequence F.B.O. FURNISHED BY DIVISI ❑N 15 -- EOLR END OF LINE RESIST ❑R See note 1 2081 -9028 ISOLATED LOOP PROTECTOR FOR MAPNET LINE X 4906 -9127 A/V MULTI- CANDELA RED SYNC (IN MAIN BLDG, ONLY) 75CD /110CD X a R NS- 241575W -FR A/V MULTI- CANDELA RED SYNC <IN GARAGE ONLY) 1801CD X RWP ASWP- 2475W -FR WEATHRPROOF HORN /STROBE, 180CD 180CD WPBB WEATHERPROOF BACKBOX FOR HORN /STROBE U U) W 22 Manufacturer's documentation of device compatibility has been provided. 7512!) D 4906 -9101 V/0 MULTI - CANDELA RED SYNC (IN MAIN BLDG. ONLY) 23 Each device and com onent model number is specified in the legend. X 180C RSS- 241575W -FR V/❑ MULTI - CANDELA RED SYNC (IN GARAGE ONLY) ® RSSWP- 241575W WEATHERPROOF V/0 MULTI - CANDELA RED SYNC 180CD (IN GARAGE ONLY) FE-W-0 LED EL -1 SS EL -1 SS ELEVATOR WARNING SIGN FSD F.B.O. FIRE SMOKE DAMPER (FURNISHED BY OTHERS) q M F.B.O. DAMPER FAN (FURNISHED BY OTHERS) J_ CONNECTION TO AN APPROVED, DEDICATED = F.B.O. EARTHGROUND, NFPA 70. COMPLY WITH NEC. 120VAC SOURCE DEDICATED BREAKER -- F.B.O. COMPLY WITH NFPA 70, --4 F.B.O. TELEPHONE LINE SPECIFICATIONS: 1. -THE NEW PROPIETARY FIRE ALARM SYSTEM IS DESIGNED FOR SMH- MEDICAL ARTS BLDG & PARKING 1HE MEDICAL BUILDING IS LOCATED AT 6200 SW 73RD. STREET SOUTH MIAMI, FLORIDA 33143 2.- ALL EQUIPMENT PROVIDED SHALL BE NEW AND UL LISTED, AND COMPATIBLE. 3.- THE INSTALLATION OF THE PRORIETARY FIRE ALARM SYSTEM ALSO COMPLY WITH THE NFPA -70 NATIONAL ELECTRIC CODE (N.E.C.) 1999 EDITION AND THE FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION 1997 EDITION THE INSTALLATION SHALL ALSO COMPLY WITH NFPA -101 AND NFPA -72. 4.- ALL PROPIETARY FIRE ALARM EQUIPMENT FOR THIS PROJECT SHALL BE RATED POWER LIMITED. 5.- THE PROPIETARY FIRE ALARM SYSTEM SHALL HAVE STANDBY BATTERY BACKUP PER NFPA -72, 1999, ARTICLE 1 -5.2.6 PROVIDING BATTERY POWER CAPACITY FOR THE ENTIRE SYSTEM TO OPERATE FOR 24 HRS. IN NORMAL MODE AND THEN, AT THE END OF THE PERIOD, FOR 5 MIN. IN THE EMERGENCY MODE. 6.- CABLE SIZE SHALL COMPLY WITH ARTICLE 760 -71 AND THE CABLE INSTALLATION SHALL COMPLY WITH THE SEPARATION AND USE OF CONDUCTORS AND CABLES AS SPECIFIED IN ARTICLES 760 -54 AND 760 -61 OF THE NATIONAL ELECTRICAL CODE 7.- SYSTEM WIRING SHALL SPECIFICALY CONFORM WITH THE NATIONAL ELECTRICAL CODE ARTICLE 760 PART C FOR POWER LIMITED FIRE PROTECTION SIGNAL WITH EMPHASIS ON ARTICLE 760 -52(b) ON POWER LIMITED WIRING METHODS AND MATERIALS. WIRING SHALL BE SELECTED ACCORDING TO THE NEC (1999) ARTICLE 725 -27(b) CLASS 1 CIRCUIT CONDUCTORS AND 760 -71 8.- MINIMUM CABLE SIZE: A.- #18 AWG. COPPER (2 -# 18 FPL SHIELDED, OF FPLP IF PLENUM) FOR SLC LOOP B.- #14 AWG. COPPER (2 -# 14 FPL OR FPLP IF PLENUM) FOR NOTIFICATION DEVICES C.- #16 AWG. COPPER (2 -# 16 FPL OR FPLP IF PLENUM) AUXILIARY POWER 24VDC 9.- WHERE CABLE IS OPEN TO DAMAGE SHALL BE RUN IN APROVED METALIC RACEWAY CONDUIT FILL SHALL BE NO MORE THAN 40% 10.- ALL ALARM NOTIFICATION DEVICES SHALL BE AUDIBLE AND VISUAL, VISUAL SHALL SHALL BE CLEAR XENON TYPE , WITH A MINIMUM INTENSITY OF 75 CANDELAS AS PER ARTICLE (5) OF THE ADA GUIDELINES OF JULY 26, 1992 AND AS PER ARTICLE 4.28.2. & CODE FOR BUILDING CONSTRUCTION 1997 EDITION 11.- HORN STROBE DEVICE SHALL BE PLACED 80" (6'8 ") ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACE OR 6" BELOW THE CEILING WHICHEVER IS LOWER AS PER ADA GUIDELINES AND ARTICLE 4.28 (6) OF THE FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION 97 EDITION. 12.- MANUAL STATIONS SHALL BE PLACED 48" ABOVE THE HIGHEST FLOOR LEVEL AS PER ADA GUIDELINES AND ARTICLE 4.28 (6) OF THE FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION 97 EDITION. 13.- ALL CIRCUITS SHALL BE CLASS "B" 14.- POWER SOURCE FOR A POWER LIMITED FIRE ALARM SYSTEM SHALL BE TYPE "C" PER NEC(1999) 760 -41 15.- THE FIRE ALARM CONTROL PANEL IS LOCATED AT THE MAIN BLDG. 1ST. FLOOR ELECTRICAL ROOM 106 AND IS PROTECTED BY SMOKE DETECTOR _ 16.- PROPIETARY FIRE ALARM SYSTEM IS NOT OFF SITE MONITORED 17.- PROPIETARY FIRE ALARM SYSTEM WILL REPORT ALARM, TROUBLE, AND SUPERVISORY TO THE FIRE ALARM PANEL IN A 24 HR. MANNED SECURITY STATION SCOPE OF WORK, Dr, Gatbut, 1. PROVIDE & INSTALL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. 2, SIGNALING LINE CIRCUIT WIRING SHALL BE STYLE 4 (CLASS B). 3. NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL BE STYLE Y (CLASS B). 4. THE NEW ADDITION OF THIS TENANT INCLUDES, 10 SMOKE DETECTOR, 2 PULL STATIONS, 5 HORN /STROBES, 9 STROBES ONLY, 1 ANNUNCIATOR. DOCS 1111 � 1. FIRE ALARM SYSTEM SHALL BE POWER LIMITED, 2. WIRING SHALL BE #12 THHN, #14 THHN OR 18/2 TWISTED SHIELDED PAIR FPL TYPE CABLE. 3. INSTALLATION SHALL COMPLY WITH NFPA 1, 2000, APPLICABLE CHAPTERS. 4. INSTALLATION SHALL COMPLY WITH NFPA 72, 1999, APPLICABLE CHAPTERS. 5. INSTALLATION SHALL COMPLY WITH NFPA 101, 2000, APPLICABLE CHAPTERS. 6. INSTALLATION SHALL COMPLY WITH NEC 2002 7, CONDUIT, AS APPLICABLE SHALL BE 1/2' MINIMUM WITH A MAXIMUM FILL OF 40%. COMPLY WITH NEC. 8. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS. 9. ALL DEVICES SHALL BE COMPATIBLE & SHALL BE UL LISTED FOR FIRE SERVICE USE. 10. ALL SPACES SHALL MEET THE AUDIBLE CHARACTRISTICS OF NFPA 72 AND NFPA 101. 11. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS. 12. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' +/- ON SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED. 13. SIGNALLING LINE CIRCUITS SHALL HAVE A MAXIMUM OF 250 POINTS PER CHANNEL. SEE FLOOR PLANS FOR QUANTITIES & TYPES OF DEVICES. 14, FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 15. ALL INTERCONNECTED FIRE ALARM PANELS SHALL BE ARRANGED TO FUNCTION AS A SINGLE', SYSTEM AND SHALL BE M ❑NIT ❑RED FOR INTEGRITY PER NFPA 72, 16. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. 17. THE DESIGN INSTALLATI ❑N COMPLIES WITH F.D.C. 11- 4,287.3 18, THE BUILDING HAS A BACK UP GENERATOR 19. PREMISES HAS A 24 HOURS MANNED CENTRAL CONTROL STATI ❑N 20, THIS SYSTEM SHALL BE A LOCAL FIRE ALARM SIGNALING SYSTEM. 1.�5ie111s1►[y��I��IZ�3�i� UPON ACTIVATION OF ANY MANUAL STATION THE FOLL ❑WING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIAT ❑R. 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT. UPON ACTIVATI ❑N OF ANY AUTOMATIC DEVICE THE FOLLOWING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR, 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT. 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE. UPON ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTORS (WITH THE EXCEPTION OF THE ELEVATOR LOBBY DETECTOR AT THE PRIMARY LEVEL OF EGRESS), THE F ❑LL ❑WING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATI ❑N VIA DACT. 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE. 6. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS. 7. FIREHAT IN ELEVATOR CAB SHALL ILLUMINATE. UPON ACTIVATI ❑N OF THE ELEVATOR LOBBY SMOKE DETECTOR AT THE PRIMARY LEVEL OF EGRESS, THE FOLLOWING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET, 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT. 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE. 6. ELEVATORS SHALL RECALL TO THE ALTERNATE LEVEL OF EGRESS. 7. FIREHAT IN ELEVATOR CAB SHALL ILLUMINATE. UPON ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR, THE F ❑LL ❑WING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET, 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT, 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE, 6, ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS, 7. FIREHAT IN ELEVATOR CAB SHALL BLINK. UPON ACTIVATION OF THE ELEVATOR TOP OF SHAFT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR, 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR, 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT, 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE. 6. ELEVATORS SHALL RECALL TO THE PRIMARY LEVEL OF EGRESS, 7. FIREHAT IN ELEVATOR CAB SHALL BLINK. UPON ACTIVATION OF A WATERFL ❑W SWITCH, THE FOLLOWING SHALL OCCUR. 1. ALL HORNS WILL SOUND UNTIL SYSTEM IS SILENCED. 2. ALL STROBES WILL FLASH UNTIL SYSTEM IS RESET. 3. AN ALARM SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 4. A SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATI ❑N VIA DACT. 5. ALL AIR HANDLER UNITS SHALL SHUT DOWN AND FIRE SMOKE DAMPERS SHALL ACTIVATE. UPON ACTIVATION OF A TAMPER SWITCH, THE F ❑LL ❑WING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT. UPON ACTIVATI ❑N OF A DUCT SMOKE DETECTOR, THE FOLLOWING SHALL OCCUR. 1. A SUPERVISORY SIGNAL SHALL BE SENT TO THE FACP & REMOTE ANNUNCIATOR. 2. A SUPERVISORY SIGNAL SHALL BE SENT TO THE OWNERS SUPERVISING STATION VIA DACT. 3. THE AIR HANDLER UNIT ASSOCIATED WITH THAT DUCT DETECTOR SHALL SHUT DOWN. 4. ALL AIR HANDLER UNITS SHALL SHUT DOWN, -AND THE ASSOCIATED FIRE SMOKE DAMPERS SHALL ACTIVATE, NOTES SCALE: NTS AND LEGENDS MIAMI DADE FIRE RESCUE FIRE ALARM PRE - SUBMITTAL CHECKLIST Designer to fill in and answer all items and provide location comments as appropriate. Process Permit A Date: ^ 2 Fire Department Application # - - - - vF- - NO r `L LOCA1°CN COMMENTS 3 Project Name: South Miami Hospital - Medical Arts Building, 6th Dr. Galbut. X^ ; 4 Address: 6200 SW 73rd Street. Miami, Florida. 33143 X E5 M 51 A copy of the contract is provided showing the total cost of the equipment and installation. Cost 4.677.07 X 6 Systems costing more than $5,000 are sealed or approved by a Fla Registered Engineer. X WNO Z Ln 7 A coov of alarm ualifier's license is attached. X ) M LLI e This fire alarm: _)C_ is required under NFPA 72, or is not required by any code or authority. X M� � See notes 3, 4, 5, S. 9 For non - required systems or components, a statement is included indicating which code or AHJ (See def. AHJ in NFPA 72) is requiring the system or component and the parameters of the requirement. �0)rn X to A copy of the Notice of Violation from Miami -Dade County Fire Rescue, or a copy of the relevant sections of the approved Life Safety Plan, is attached. '� C) � aiL X .` i Q 11 A complete statement of the scope of work is stated o th 1 X z See scope of work 12 The total number of devices and components being installed is 21 X W W 13 A description of the building and /or section of the building is provided including, fire suppression systems, number of stories s uare footage, and elevation of the last occupied floor if over 5 stories. X O Ow 14 A location key is provided showing the area of proposed work within the building. X FN•- o_ _ 16 All devices in areas in which the voltage, temperature, and humidity variations exceed those conditions stated in NFPA 72, are listed for conditions and all such areas are identified. to_J a X No weatherproof devices on this project 18 A specific sequence of operation including all alarm, supervisory, trouble and control functions such as fire suppression, door release, smoke control, etc., are specified on the plan. X See sequence 17 A specification of power-limited or [non-power limitedl is included on the plan. X See note 1 18 Emergency forces notification or sprinkler supervision _7I:_ is required or - is provided, but is not required. X Existing to remain 191011-site monitoring __ is provided _X_ is not provided. X a Existing to remain. remns with 24 hour manned location 20 The method of communication to the monitoring station is included on the plan. X �0 see sequence 21 Complete specifications sheets are provided for all devices, control units, and components. X U U) W 22 Manufacturer's documentation of device compatibility has been provided. X 0 23 Each device and com onent model number is specified in the legend. X 24 Floor plans are drawn to 1/8" scale or, if using another scale, all device coverage is diagramed on the plan and all room dimensions are included. X 25 Each device, appliance and component is identified with it's own unique number and indicated on the floor plan and riser? X 28 All new, existing, replaced or relocated devices are indicated on the floor plan. X U) 27 All rooms & spaces are labeled indicating their use, and the occupant load has been provided for all assembly use rooms with an occupant load of 50 or greater.. X 28 Ceiling condition and height is provided for all ceiling mounted devices. X W W 29 A riser diagram is provided showing each floor and building with all zones and circuits labeled. X 3o The wire size, type, and number is provided for each circuit. X 31 The FACP or remote annunciator is located near the main entrance /lobby when required or in the Central Control Station. X 32 YES NO N/A LOCATION COMMENTS 33 The FACP and all sub panels in unoccupied rooms are protected with a smoke detector. X a Existing 34 If a complete automatically activated system, there is at least 1 pull station each floor or 2 for large buildings. X W 0 Existing 35 If a manually activated system, the travel distance to reach a pull station is less than 200' and near all exits. X Existing 36 All automatic initiating devices are shown and are located in accord with NFPA 72, the manufacturer's specifications, and accepted enizineerinq practices. X o 37 All visible devices are placed per the tables in NFPA 72 and each strobe has it's candela rating listed on the floor plan and riser. X 38 _ Ali corridors aced strobes are placed a maximum of 100' apart and wl'.rin 15' from ends of the corridor. X 39 All spaces meet the audible characteristics of NFPA 72 and NFPA 101. X See note 10 4o Racks, shelves and equipment which may block devices are shown with their height indicated. X U See note 16 41 Duct detectors or relays for duct detectors are shown on the floor plan and riser for all systems over 2000 cfm. X Existing 42 The fire pump is monitored for run, phase reversal & phase loss to _, a continuously manned location, or the supervised fire alarm system. X N w Existing to remain - Not in the scope of this contract 43 Elevator recall is connected to the fire alarms stem. X Existing 44 All interconnected fire alarm control panels are arranged to function as a single system and monitored for integrity per NFPA 72. X See note 16 45 All relays for automatic extinguishing systems are shown on the floor plem and riser. hood sprinkler, FM200 etc. X Existing 461 The class and /or style is shown for all initiating device circuits, signal line circuits and notification appliance circuits. X Urn See Scopes Notes 2 & 3 47 The maximum number of each device type is provided for each IDC or SLC, based on class and style, per NFPA 72 and the manufacturer's specifications. X See note 13 48 The power supply model number and capacity is specified for each power supply in each fire alarm control panel. X See Schedules 49 The total device load, including voltage drop calculations, are provided for each notification appliance circuit for each power supply. X See Schedules 5o The wattage tap is indicated for all speakers. o a� (d rn a X Not a Voice System 51 The wattage capacity and load is provided.for each amplifier. M UE X Not a Voice System 52 All load and draw calculations correlate with the provided spec sheets and the device draw or available power is highlighted on the specification sheets. X U 0 LL 53 This system is a Local Fire Alarm System or a Proprietary Supervising Station Fire Alarm System and is stated as such on the plan. 24 hours secondary power) X O z Ed 64 This system will be certificated as a Central Station Fire Alarm System and is stated as such on the plans. (24 X 65 This system is a Remote Supervising Station Fire Alarm System as stated on the plan and will be provided with 60 hours of secondary power supply. U) z X 58 This system includes Emergency Voice Evacuation and is provided with 15 minutes of secondary alarm power. z � in X 67 This system is being provided back up power by an emergency generator and will provide 4 hours of standby power plus the appropriate secondary alarm power. X 0 F_ U F- 58 Battery calculations, detailed in chart form, are provided for each back-up power supply. X W H See Battery Cale 59 Desi ned b (� Im LL X= W a a eo Signature: Q F- 5 F+ w 0 LL Refer to the instructions for a line by line clarification of the above items. �i X C) W F- FTREE ALARM SYSTEM TIO BE INSTALLED IN ACCORDANCE WITH NFPA 72; 70;101- APPROVED MIAMI -DARE COUNTY FIRE DEPARTMENT BLDG. PEAVIT �^ FIRE ALARM FIRE SUPPRESSIION WATER AWN EXT. DATE: '11111A -5- BY: ��"/ MM11 -DARE CO. FIRE DEPARTMENT APPLICATION #- 2 `x=36 9P?.3 L. TRIANA AND ASSOCIATES, INC. CONSULTING ENGINEERS 5151 S.W. 98TH AVENUE ROAD MIAMI, FL. 33165 PHONE: (305) 595 -9765 (305) 596 -9421 FAX: (305)596 -1814 E-MAIL LTENGINEERING @BELLSOUTH.NET . Henry VidaliP.E. Discipline: Electrical Engineer License No: PE.56204 ��41k''' SIGNATURE AND SEAL: ". C CIL 04, ST,zTI- ri Sir W C CO 1� z Q E5 W E5 M MI u. Q W N WNO Z Ln =aM o N a °�° ) M LLI M� � OQIvLr) z0 Z �0)rn L°n X � = w[L [L '� C) � aiL m .` i Q W J U) nW z + m J W W z� zw O Ow X C� J FN•- o_ _ to_J a O J oQ 0 0 0 a �0 U U) W 0 0 0 z O U J U) W W LL w a. a W 0 o d z U N w U F Urn Q) W w z o a� (d rn a w z Q . ads 00 M UE U) Y A x w W U 0 LL � M O z Ed X U) z J M CJF z � in Z Q J H Q 0 F_ U F- I-� U W H M w W Im LL X= W a a Q F- 5 F+ w 0 LL �i X C) W F- n. 5 I4 ¢ a D ¢ Un F-� Q w 0 PEI = ZO 0 W WZ n� F-+ zJ z F J 0 0 Z a� z W ° F- J O LL z F4 0 (7 W z co Sc rn 0 D Cr 0 �i C) 9 0 J a. M CO 0. F- °z a O a 0 O I�i a 0 o z 5 zoo ?o z a°r� Q +' 9 � 0-- 0 c°�t O wU) CD m ch 0< 0 DRAWN BY: DATE: RC 9 -20 -05 DESIGNED BY: DATE: APPROVED BY: DATE: PROJECT NUMBER: 263-400861/912735718 SHEV TITLE/ PATH: .200ASOUTHM IAM I HOSP /MOB &PARK 7MASTERSITE3BU I LDOUTS 13VEET NUMBER: = ;1 OF 9 SIZE 0(24'X38';