R13-122-006TYPE: LOAD CENTER / NEMA 1 MAIN 51,15: 200 A
SERVICE: IPH, 3W / S/N PANEL "A" NEUTRAL: 200 A
VOLTAGE: 120/240 V, IF, 3W MAIN: M.L.O
MOUNTING: FLUSH (EXIST. FOR REFERENCE) AIC: 10,000 AIC
TRIP
POLE
CON
TOTAL
V.A.
WIRE
51ZE
DESCRIPTION
REMARKS
CKT
«
REMARKS
DESCRIPTION
WIRE
SIZE
TOTAL
VA.
GOND
TRIP
POLE
60/2
RMX
10,570
6
NEW A.N.U. "1
lm KW + b-1 FAN (NC)
(EXIST)
1
2
(EXIST)
CU. "1 (N.C.)
6
9,000
RMX
60/2
3
4
50/2
RMX
12,000
6
RANCxE /OVE N
(EXIST)
5
6
(EXIST)
DRYER
10
5,000
RMX
30/2
1
S
20/1
RMX
1,200
12
REFRIGERATOR
9
10
(EXIST)
WATER NEATER
6
5,500
RMX
5O/2
20/1
X
1,500
12
SMALL APPLIANCE5
GFI (NEW)
11
12
20/1
RMX
1,500
12
SMALL APPLIANCES
GFI (NEW)
13
14
(EXIST)
WASHER
12
1,200
RMX
20/1
20/1
RMX
1,500
12
SMALL APPLIANCES
GFI (NEW)
15
16
(EXIST)
MICROWAVE /HOOD
12
1,200
RMX
20/1
20/1
RMX
O
12
BATH RECEPTACLE
GPI (NEW)
11
IS
(EXIST)
DISHWASHER
12
1,200
RMX
20/1
15/1
RMX
O
14
GEN. LIGHTING 4 RECEPT.
(EXIST)
19
2
(EX15T)
GARBAGE DISPOSAL
12
SOO
RMX
20/1
15/1
RMX
O
14
GEN. LIGI -ITING 4 RECEPT.
(EXIST)
21
22
(EXIST)
GEN. LIGHTING 4 RECEPT.
14
Q
RMX
15 /I
15/1
RMX
O
14
GEN. LIGHTING 4 RECEPT.
(EXIST)
23
24
(EXIST)
GEN. LIGHTING 4 RECEPT.
14
1
RMX
15/I
15/1
RMX
O
14
GEN. LIGHTING 4 RECEPT_
(EXIST)
25
26
(EXIST)
GEN. LIGHTING 4 RECEPT.
14
O
RMX
15/1
15/1
RMX
G
14
GEN. LIGHTING 4 RECEPT.
(EXIST)
21
28
(EXIST)
GEN. LIGHTING 4 RECEPT.
14
RMX
15/1
15/1
RMX
14
GEN. LIGHTING 4 RECEPT.
NEW
29
3
(NEW)
GEN. LIGHTING 4 RECEPT.
14
lO
RMX
15 /i
SPACE
31
32
SPACE
SPACE
33
34
SPACE
35
36
31
35
39
4
41
42
11,100
TOTAL
TOTAL
14,1300
NC - - - -- -NOT COUNTED LOAD
VERIFY MANUFACTURE SPECIFICATIONS
SUB TOTAL LOAD: 32,600
(D FLOOR AREA= 2,151 SRw 3 WATTS = 6,453
NEW TOTAL LOAD (WITH ADDITION) 39,053
ELECTRICAL SYMBOL LEGEND
O JUNCTION BOX
HIGH HATS LIGHTING
OO MINI HIGH HATS LIGHTING
VP VAPOR PROOF
O CEILING MOUNTED FIXTURE
KEYLESS FIXTURE
O CEILING MOUNTED FIXTURE
F/L
W /SUPPORT FOR FAN 8 LIGHT
10 WALL MOUNTED FIXTURE
0 1'X4' FLUORESCENT FIXTURE
CxFI RECEPTACLE
GF I
SINGLE RECEPTACLE
® 2 POLE OUTLET
RECEPTACLE
SWITCHABLE DUPLEX RECEPTACLE
GARBAGE DISPOSAL
ELECTRIC PANEL
z EXHAUST FAN
WP WEATHER PROOF
SWITCH
$F FAN SWITCH
$3 3WA1' SWITCH
TELEPHONE
Tv TELEVISION CABLE OUTLET
DISCONNECT SWITCH
NEW SMOKE /CARBON MONOXIDE DETECTOR
SD COMBO (INTERCONNECTED)
l\TC)TFq-
NC
ELECTRICAL LOAD CALCULATIONS
(MAIN HOUSE PANEL - EXIST. TO REMAIN)
I- SUBTOTAL 39.05
2- FIRST 10.00 KW e 100` 0 100 KW
3- REMAINDER 21305 KW 'a 40% 11.62 KW
4- 1 AIR CONDITIONING "I HEATER
AMPS 240 SINGLE PHASE 3 WIRE
32,190 W /240 V = TOTAL LOAD
SCOPE OF WORK:
SUBTOTAL = 21-(o2 KW
10,5 -10 10.5 -1 <W
GRAND TOTAL = 32.19 KW
134 AMPS
ALL INTERIOR WIRING, LIGHT FIXTURES, OUTLETS, SWITCHES,
BOXES AND ELECTRICAL PANEL TO REMAIN UNLESS
OTHERWISE NOTED.
NEW ELECTRICAL AS PER PLAN.
EXIST. METER AND DISCONNECT BOX ARE EXISTING AT
EXISTING STORAGE TO REMAIN.
EXISTING PANEL IS SUFFICIENT FOR NEW ELECTRICAL WORK
(SEE EXISTING PANEL ABOVE).
EXISTING A.H.U. AND C.U. TO BE REMOVED AND REPLACED
WITH NEW.
1- PROVIDE ARC -FAULT CIRCUIT INTERRUPTER PROTECTION
FOR ALL BEDROOM BRANCH CIRCUIT RECEPTACLE OUTLETS.
2 -ALL AREAS SPECIFIED IN 210.52 ALL 125 -VOLT 15 AND 20
AMPERS RECEPTACLES SHALL BE LISTED TAMPER RESISTANT
RECEPTACLES, NEC 2008
3 -NEW SMOKE DETECTOR SHALL BE HARDWIRED (110 VOLT TYPE)
TO A NON- SWITCHABI_E BEDROOM LIGHTING CIRCUIT,
WITH BATTERY BACK -UP. SMOKE DETECTORS TO BE
CARBON MONOXIDE DETECTORS.
4 -BOXE6 IN OUTLETS IN CENTER OF:
BEDROOMS, FAMILY, GYM AND DEN SHALL BE ABLE TO
SUPPORT LAMP HOLDER5 AND FANS AS N.E.0 314.21 a 4 d
5 -ALL EXIST. KITCHEN RECEPTACLES SHALL BE REPLACED WITH
NEW 204 G71 OUTLET AS PER N.E.G.
ELECTRICAL NOTES
1) CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT
FOR COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE
DRAWINGS.
2) COMPLY WITH THE N.E.C. AND STANDARD BUILDING CODE,
3) PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM.
4) OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT.
5) PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER
TRADES.
(o) PROVIDE ALL REQUIRED CONNECTIONS FOR OTHER TRADES.
�) COORDINATE ALL OUTLET LOCATIONS WITH BUILDING ARCHITECTURAL
FEATURES.
8) CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH
ALL EXISTING CONDITIONS.
(EI) ALL GABLE SHALL BE COPPER_
10) ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR.
11) OUTDOOR UNDERGROUND CONDUITS SHALL BE SCHEDULE 40 PVC.
UNDER PAVED AREAS IT SHALL BE ENCASED IN CONCRETE. MINIMUM
COVER SHALL BE 24 INCHES.
4RE,4 OF CONSTRUCT ION
I
ELECTRICAL PLAN
SCALE: 1/4" =1' -0"
&H
ARCHITECT
ORESTES LOPEZ -RECTO
AR0009350
5895
S.W. 32 STREET
MIAMI, FLORIDA 33155
TELEPHONE (" 608-8887
OWNER-
W
0
z
W
0
®
w
Il
®1
w
w
Q
co
< �(y)
z
:E
_0
Lu
F—
z
O
Co
1J_ lid 2E
z
N.
1..1�
75
REVLSTONS:
0 5.1$.13 REVISION
BY OWNER
SEAL;)
,
.,
Z
,k; • ,. �a
DATE
JANUARY 18, 20B
SCALE =
AS SHOWN
DRAWN
WAC.
JOB NO. B -2000
E -1
SHEET NO. OF