Loading...
08-801-0010FFlC&*-,p =0 M I ■ SCALE 1/4' =1' -0' Hanger Location Ntel PIPE SIZE A 8' C 1" 3' -0" MAX. 12' -0" MAX. 3" MIN. 1 -1/4" 4' -0" MAX. 12' -0" MAX. 3" MIN. 1- 1 /2"TH 8" 5' -0" MAX. 15' -0" MAX. 3" MIN. A E1' C SPRINKLER HEAD STEELE—PIPE HANGER MAXIMUM HANGER SPACING FOR THREADED UGHTWALL STEEL PIPE IS 12' -0" FOR ALL PIPE SIZES ' POWDER ACTUATED PIN a . i 3/8" ALL THREAD ROD (ATR) ATTACHED TO CONCRETE WITH do 3 E 1 /8" DCPLG. (F01 USE WITH 4' PIPE & SMALLE GALVANIZED HANGER #45 Hanger Detail NO SCALE fwwR EIRE PROTECTION CRITEhA ^ ^ ^ n- ^A ALL MATERIAL& INSTALLATION SHALL BE PROVIDED IN ACCORDANCE QITH NFPA -13 (2002) REQUIREMENTS, a t SPRINKLERS SHALL BE 5.6K, 155 DEGREE FAHRENHEIT, SEMI — RECESS PENDENTS DESGN CRITERIA IS IN ACCORDANCE r. WITH NFPA -13 FOR LIGHT I HAZARD OCCUPANCY FOR OFFICES (225FT/2) INTERIOR PIPE TO BE XL OR BLACK STEEL SCHEDULE 10. ALL HANGER MATERIAL .AND 'SPACING SHALL COMPLY WITH NFPA -.13 SCOPE OF WORK THIS IS AN EXISTING OFFICE BEING _ REMODELED FOR NEW TENANT OFFICE USE WITH AN EXISTING FIRE SPRINKLER SYSTEM.' WORK TO BE DONE THROUGHOUT OFFICE::. SCOPE IS TO ADD /RELOCATE (24) FIRE — SPRINKLERS FOR PROPER OFFICES PROTECTION COVERAGE, (SEE LEGEND FOR EXISTING AND NEW SPRINKLERS) EIRE PROTECTION LEGEND NEW FIRE SPRK PIPE -- -- EXISTING FIRE SPRK PIPE �o NEW PENDENT FIRE SPRINKLER HEAD EXISTING UPRIGHT SPRINK TO RELOCATE " 0--- • RELOCATION TYPE (EXST TO NEW LOCATION)''° �9P SCHEDULE . #�� 1. 1' ARM❑VE:R. 2. EXISITNG BRANCH LINE MECHANICAL TEE OUTLET. 3. 1' DROP. 4. NEW PENDENT FIRE SPRINKLER HEAD WITH STANDARD RECESSED ESCUTCHEON, X *ARMOVERS GREATER THAN 24' IN LENGTH SHALL BE SUPPORTED BY A HANGER.