14-715-005TO 'FPL'
iARTIAL FIRST FLOOR
REFLECTED CEILING FLAN
SCALE: 1/4" = 1'-0"
fAf;RT I AL FIRST FL CCU
EQUIFMENT FLAN
SCALE: 1/4" = 1' -0"
EXISTING
EXISTING
PANEL 'IA'
PANEL '1B'
120/240V
120/240V
225A, 10
225A, 10
20 POS.
20 POS.
EXISTING
3 #4/0 THWN IN 2•C
EXISTING
MAIN BREAKER
225A 10
120/240V
6" X6•X2' GUTTER
O
EXISTING
METER
120/240V
EXISTING
3#4/0 THWN IN 2 -C
1 FLOOR
PARKING GARAGE
PARTIAL ELECTRICAL RISER
-
Ws
_Z
0
ELECTRICAL SPECFCA nm
PART 1– GENERAL
A.– Overall Installation: The installation shall comply with the Latest
edition of Electrical Code (NEC), the Florida Building Code (FBC), and
any other applicable Federal, State and Local codes.
B.– Conductor Calculations: Conductor calculations are based on 75 'C.
1. General: The General and Special Conditions and Requirements of
the Contract and Specifications as well as plans and specifications
of other disciplines and trades shall be a part of the work hereby
specified. These specifications and accompanying plans are intended
to provide for the complete furnishing and installation of the elec-
trical systems. To provide means to furnish and install.
2. Compliance: Workmanship, materials and installation shall be in strict
accordance with the applicable edition of the NEC,NFPA,NEMA,ASTM,
OSHA, HRS health agencies, and other applicable national, state, and
local codes and pertaining regulations established by the ruling
authority having jurisdiction.
Contractors shall also meet the requirements of other standards
where such requirements are more strict than those standards
cited above.
3. Workmanship: All work shall be performed by contractors licensed
in their respective discipline. Work shall be done in a first class
manner, fully operative, and to the acceptance of the Architect and
the Engineers. Contractor shall provide for all necessary labor and
material required for the completion of the work including but not
limited to related work such as connection of existing systems, exca-
vations and back filling.
4. Materials: Contractor shall provide all new materials of American ma-
nufacture, bearing the Underwriters Laboratory (UL) label as appli-
cable. Materials shall be new, suitable for the application and above
standard quality normally used for the purpose as called for on plans.
Supplemental materials, products and components necessary to comply
with the intent of the Contract drawings and /or specifications, but
not noted or specified on these sections, shall be provided by the
Contractor as required for the completion of the work at no additio-
nal cost to the Owner. Contractor shall be responsible for provisions
and coordination of delivery of materials.
Equipment marred during shipment or installation shall be touched up
and refinished to factory finish, replaced where not acceptable.
5.– Permits and Insurance: Contractor shall secure and pay for all
permits, fees, taxes, inspections, tests, fines and other items as
required for the installation of the complete electrical systems as
outlined herein and shown on plans.
Contractor shall provide all required insurance for protection against
public liability and property damage for the duration of the work
6.– Existing conditions: Before bidding, the contractor shall visit the job
site and ascertain all existing conditions which will affect his work.
Failure to do so will not be accepted as a reason for requesting
extra pay where the existing conditions result in extra materials or labor
Any existing conditions found by the Contractor which will adversely
affect the work shall be immediately be brought to the attention of
the Architect /Engineer. Correction of any defects shall be completely
without additional charge and shall include replacements or repair of
any other phase of the installation which may have been damaged thereby.
7.– Plans: Drawings are basically diagrams intended to depict approximately
equipment locations and arrangements, not to show every minor detail.
Plans shall not be scaled to determine exact location and dimensions.
8.– Interference: The Contractor shall coordinate his work with other
trades so that interference with existing conditions, conduits, piping,
equipment, architectural and structural members be avoided.
9.– Substitutions: Products and materials called out by trade name and /or
catalog numbers establish a standard of quality, appearance, perfor-
mance and dimension. Contractors shall base his proposal on those
items as they shall be considered as a standard basis of bidding.
Requests for substitution shall be submitted in writing to the Archi-
tect /Engineer, demonstrating that product is of comparable and basic
design, construction, standards and warranties, dimensions to fit wi-
thout change, and does not cause extra work to other trades.
Contractor shall be responsible for providing equality of substitution:
Architect /Engineer will, under no circumstances, be required to prove
such item is or is not of equal quality to the specified item. Archi-
tect /Engineer expenses incurred due to Contractors requested revi-
sions or substitutions shall be paid by the Contractor.
10.– Record Drawings: Maintain a complete set of prints for indicating
all changes. Use colored pens to mark changes at the time of exe-
cution and deliver the set to the Architect /Engineer upon completion.
Contractor shall stamp As Built' on prints and plans, date and sign
in ink
11. –The Contractor shall, and hereby does, warrant all labor and material
free from defects for a period of one (1) year from the date of
acceptance or beneficial use by the owner, whichever is earlier and
shall, upon notification during this period promptly repair or replace
any defective items or material or equipment at no cost to the owner.
i-LCEM
@-- DUPLEX RECEPTACLE A 12• AFF, U.O.N.
& GF1 DUPLEX RECEPTACLE
Ny PHONE /DATA OUTLET. PROVIDE MUD RING
AND 1/2-C STUBBED ABOVE CEILING.
LIGHTING SWITCH ® 48' AFF.
M$ MOTOR RATE SWITCH
EXHAUST FAN
I UNDER CABINET LIGHT
120V. 4OW SELECTED
BY ARCH /OWNER.
'E' EXISTING TO REMAIN
'N' NEW DEVICE
SERVICE: 1PH, 60HZ
VOLTAGE: 1201240 V.
1PK 60HZ
120124OV.
CHECKED:
DG
DATE:
EXISTING SUB PANEL "1 A"
EXISTING SUB PANEL "1 Be'
AS SI-IOM
TYPE
MOD:
MAIN BUS:
MAINS:
EXISTING - -
225 AM?
LUGS ONLY
DEMAND
LOAD VA
NO DEM.
LOAD VA
CONDW
WIRE
SIZE
TRIP
AMP
POLES
LOAD DESCRIPTION
AND RK3MARKS
CKT
NO.
PHASE
I I
CKT
NO.
LOAD DESCRIPTION
AND REMARKS
POLES
TRIP
AMP
WIRE
SIZE
CONDUIT
NO DEM.
LOAD VA
DEMAND
LOAD VA
720
12
12
20
1-
EXISTING GEN RIEC
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19
-21
-23
-25
-27
-29
-31
-l—
—I-
-l—
—l-
-l—
—I-
-I—
—l-
-I—
—l-
-I—
—I-
-l—
—I-
-I—
—l-
2-
4-
6-
8-
10-
12-
14-
16-
18-
20-
22-
24-
26-
28-
30-
32-1
NEW CRYOSTAT
-1
20
12
12
1,440
360
12
12
20
1-
SPACE
NEW FUMEABSORVE
-1
20
12
12
240
360
2,250
314
8
40
2-
EXISTING WH
NEW RE= LIGHT
-1
20
12
1R
80
180
720
2,250
12
12
20
1-
IXISTNG GEN RIM
NEW REC
-1
20
12
12
360
540
12
12
20
1-
EXISTING GM REC
NEW REDIC LIGHT
-1
20
12
12
80
360
540
800
112
12
20
1-
EXISTING GEN RIB✓
NEW D(AHUST FAN
-1
20
12
12
120
540
800
1R
12
20
1-
EXISTNG GI3N FEC
EXISTNG GEN REC
-1
20
12
12
540
360
800
12
12
20
1-
EXISTING GEN R130
EXISTING GEN REr,
-1
20
12
12
800
540
360
800
12
12
20
1-
EXISTING GEN REC
D(ISTNG GEN REC
-1
20
12
12
540
360
2,250
12
12
20
1-
EXISTING GEN REC
EXISTING GEN REC
-1
20
12
12
360
360
2,250
12
12
20
1-
IXISTING GEN REC
DXISING GEN REC
-1
20
12
12
360
720
12
12
20
1-
EXISTING GEN REC
EXISTING GEN REC
-1
20
12
12
_
360
540
1R
12
20
1-
EXISTING GEN REC
EXISTING GEN REC
-1
20
12
12
540
720
4,500
1R
12
20
1-
EXISTING GEN REC
EXISTING GEN REC
-1
20
12
1 12
4,500
540
720
4,500
12
12
20
1-
DUSTING GEN RIB;
EOSTNG GEN REr_
-1
20
1 12
1 1R
4,500
1 540
2,800
16,700
12
12
20
1-
PANEL'2B LOAD
PANEL '2B' LOAD
-1
20
1 12
12
10,600
4,480
9,280
21,200
=SUB-TOTALS
D.F. = 0.50
27300 VA : TOTAL NO DEMAND LOAD
SUB-TOTALS=
10,880
11,380
15330
VA: TOTAL
DEMAND LOAD (2)
TOTAL PANEL AMPS = VA ! VOLT =
1. PROVIDEGROUNDING BARKIT
2. APPLYING DEMAND AS PER NEC TABLE 220 -44.
204
AMP
32080 VA :TOTAL NO DEMAND LOAD
1200 VA : 25%CONTINOUS LIGHT
300 VA: 25% LARGEST MOTOR
48910 TOTAL LOAD
SERVICE:
VOLTAGE:
1PK 60HZ
120124OV.
CHECKED:
DG
DATE:
05 -23 -2014
EXISTING SUB PANEL "1 Be'
AS SI-IOM
TYPE
MOD:
MAIN BUS:
MAINS:
EXISTING
225 AMP
LUGS ONLY
DEMAND
LOAD VA
NO DEM.
LOAD VA
CONDUIT
WIRE
SIZE
TRIP
AMP
POLES
LOAD DESCRIPTION
AND REMARKS
CKT
NO.
PHASE
I I
CKT LOAD DESCRIPTION
NO. AND FE MARKS
POLES
TRIP
AMP
WIRE
SIZE
CONDUT
NO DEM.
LOAD VA
DEMAND
LOAD VA
720
12
12
20
1-
EXISTING GEN REC
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19
-21
-23
-25
-27
-29
-I—
—l-
-I—
—l-
-I—
—l-
-I—
—l-
-I—
—l-
-I—
—I-
-l—
—I-
-I—
2-
4-
6-
8-
10-
12-
14-
16-
18-
20-
22-
24-
26-
28-
30-
EXISTING GEN RIB✓
-1
20
12
12
540
360
12
12
20
1-
E ISTI4G GEN RIB✓
EXISTING GEN REC
-1
20
12
12
540
360
12
12
20
1-
EXISTING GEN REC
EXISTING GEN REC
-1
20
12
12
540
720
12
12
20
1-
IXISTNG GEN RIM
EXISTING GEN REC
-1
20
12
12
540
720
12
12
20
1-
1 EXISTING GEN REr_
EXISTING GEN REC
-1
1 20
12
12
720
800
12
12
20
1-
EXISTNG GEN LIGHT
EXISTING GEN LIGHT
-1
20
12
12
800
800
1R
12
20
1-
E XIST14G GEN LIGHT
SPACE
-1
800
12
12
20
1-
E ISTNG GEN LIGHT
EXISTING GEN LIGHT
-1
20
12
12
800
800
12
12
20
1-
EXISTING V*i
SPACE
-1
2,250
12
12
20
2-
EXISTING WH
EXISTING COOLER
-2
20
12
1R
800
2,250
800
12
10
30
2-
EXISTING GU # 1 (NCL)
EXISTING GU # 2 (NCL)
-2
30
10
1R
4,500
1
6
60
2-
EXISTING ARJ #1
EXISTING AFKJ # 2
-2
60
6
1 1
4,500
4,500
1
4,500
2,880
16,700
=SUB-TOTALS
D.F. = 0.50
SUB-TOTALS=
10,600
4,480
7360
VA : TOTAL
DEMAND LOAD (2)
(NCL) NOT CONCURI EN117 LOAD
1. PANEL F® THROUGH FROM PANEL 2A, SEE 2A LOAD CALCULATION
2. APPLYING DEMAND AS PER NEC TABLE 220 -44.
27300 VA : TOTAL NO DEMAND LOAD
NOTES:
1– THE SCOPE OF WORK IS A RENOVATION OF EXISTING EXAM ROOM 100 AND 101.
2– LIGHTING WILL REAMING SAME AND CONNECTED TO EXISTING CIRCUIT.
3– NEW POWER HAVE BEEN ADDED TO COVER NEW EQUIPMENTS AND NEW COUNTER
DISTRIBUTION.
4– ELECTRICAL CONTRACTOR SHALL VERIFY RECEPTACLES LOCATION AS PER
ARCHITECTURAL ELEVATIONS.
PANEL 1A & 1B
LOCATION
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
P.E. No 57468
David Guirola
Electrical Engineer
1150 NW 72nd AVE, S -451
MIAMI, FLORIDA 33126
P.H: (305) 513 -9665
CA 00009112 EMAIL: GUIRO 5(MAOLCOM
SCOPE OF WORK
Revisions:
A
■
Z_\
n
0
F
Q
ra^
�l
O
x
H
z
0
U
in in
m
M
F4
N
J" _z � g in
0 ^
�'+ 3 0
h v
O
-p a
.. F
w
rq
a O
�x
»
-ICJ
++ g
Q
a
z
a
V
V
W
I.1a
PERMIT SET
DRAWN:
IA
CHECKED:
DG
DATE:
05 -23 -2014
SCALE:
AS SI-IOM
SEAL,_ -.����.i
.� O U •
w
a
;the �►.
r
OF y
1 1
l Li x.. _ _ �:ia�➢h� — �I JOB # 2014►(.
Now
d� PIP
aL 7,0iw
if
1111111110n.«e
•
!k �
�i
3k.–Av>M
41111111111
+ate re
w
�w
•
_,. � Yo��l"•�sas
j
1
•
4l9wft
�aas�
O