09-305-010AIR CONDITIONING NOTES
�1 PROVIDE (FURNISH AND INSTALL) ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND
VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS. AND HEREIN
SPECIFIED. INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
ASHRAE, SMACNA, NFPA, AND LOCAL ORDINANCES.
O DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR THE EXACT
LOCATION OF EQUIPMENT. PIPING, DUCTWORK, ETC.
O3 DUCTWORK IN UNCONDITIONED SPACE SHALL BE R =6.0
QTHESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL,
BUT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED
FOR A COMPLETE ACCEPTABLE WORKING INSTALLATION.
ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A
FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE
FULLY OPERATIVE AND ACCEPTANCE BY THE ARCHITECT AND / OR
ENGINEER MUST BE CONDITION OF THE CONTRACT.
® CONTRACTOR WILL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS.
n THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
WITH EXISTING CONDITIONS.
®PRIOR TO INSTALLING EQUIPMENT AND /OR FABRICATING DUCTWORK, A.C.
CONTRACTOR SHALL CHECK THAT THERE IS SUFFICIENT CLEARANCES FOR
EQUIPMENT , DUCTWORK, ETC. AND ALSO TO AVOID ANY INTERFERENCE
WITH THE PROCESS OF CONSTRUCTION.
IF THERE ARE ANY CHANGES IN ENGINEER'S DRAWINGS, IN DESIGN OR IN
EQUIPMENT, WITHOUT ENGINEER'S CONSENT, THE A.C. CONTRACTOR SHALL
ASSUME ALL RESPONSIBILITIES FOR THE PROJECT.
EXISTING SPLIT SYSTEM SCHEDULE
MT.
UNIT No i
TONS
5.0-TONS
TOTAL CAPACITY BTU/HR
55 500
,ENS CAPACITY 8TUA4R
38 300
CFM SUPPLY
I 80m
HEATER KW
10�
VOLTAGE
1 -60 -240
DESIGN MANUFACTURER
GE
A14.U. MODEL NO.
61335V- 06OK -C
G.U. MODEL NO.
5KCP355FV493S
SEER
13�J0
REFRIG. LIQUID /SUCTION
3/811- l /8"
3'0 EXHAUST DUCT (METAL PIPE 30GA)
STEEL HANGER WIRE
TYPICAL CEILING CABINET
EXHAUST FAN WITH BACKDRAFT
DAMPER -LOW NOISE LEVEL
AND Nd VIBRATION.
FRONT FACE GRILLE WITH
FASTENING SCREENS
EXHAUST FAN HANGING
BRACKET (ADJUSTABLE)
CEILING MOUNTED CA5INET
EXHAUST FAN DETAIL
N.T_5_
e
REvISED OUTSIDE AIR CALCULATIONS
AS PER F8C1M 4033
1165 OF / 100 S.F. PER PERSON ■ 12 PERSONS
O/A CFM REQUIRED 25 CFM / PERSON
12 x 25 ■ 300 CFM REQUIRED
CFM PROVIDED 300 CFM
UNIT TO BE SECURED
(4) KWIK BOLT 3/8'X3
2 -1/2' MIN EMBEDMENT
R MIAMI —DADE COUNTY
LANCE 8C -5.
CONDENSING UNIT INSTALLATION DETAIL
NTS
06" FRESH AIR INTAKE FLEXIBLE DUCT
THROUGH SCREENED -VENT WITH �►�
MANUAL DAMPER SET AT 300 CFM.
AIR DISCHARGE
PLENUM SHALL BE
RECHANICALLY
ATTACHED TO AHU.
FBC MEC 603.7
WALL L
REFRIG. LINES
PRINCIPAL
DRAIN LINE
TO OUTSIDE
AHU INSTALLATION DETAIL
NTS
T SWITCH 2
NDARY DRAIN LINE
AL STAND
EXISTING
THRJOGH
FAN SCHEDULE
ITEM
EXISTING EF -1
NEW EF -2
MANUFAC.
NUTONE
NUTONE
TYPE
CEILING
CEILING
CFM
80
210
SONES
2.5
6.5
REFERENCE MODEL
684NT
8210
REMARKS
4' p( DUCT
7' I( DUCT
THERMOFIN DUCT VENT THRU WALL
WALL CAP WITH INSECT SCREEM.
CONECT TO INDEPENT SWITCH
EXISTING
=VIATtW IN Pvr_ rOWn nIPAthl
HVAC DESIGN REQUIRES=
YES
NO
DUCT SMOKE DETECTOR
x
FIRE DAMPER (S)
x
SMOKE DAMPER(S)
x
FIRE RATED ENCLOSURE
x
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
x
FIRE STOPPING
x
SMOKE CONTROL
x
LEGEND
l" EF -2
THRJ WALL CAP
( Exwwa TwERf toSTAT
4 " =1' -0'
�o
�o
•
Imm •
-jog i
zz
NJ ot
•
mi• i
•
e.
MEN , i
lu W co
•
MEN •
ME
on"
0 to
f PA M 0
5
IL•
Revision
Down is R. G.
cwdma M. LOPEZ
Dow 04/01/09
Project # 08-40
Sheet