09-305-009AIR CONDITIONING NOTES
�1 PROVIDE (FURNISH AND INSTALL) ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND
VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS. AND HEREIN
SPECIFIED. INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
ASHRAE, SMACNA, NFPA, AND LOCAL ORDINANCES.
O DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR THE EXACT
LOCATION OF EQUIPMENT. PIPING, DUCTWORK, ETC.
�3 DUCTWORK IN UNCONDITIONED SPACE SHALL BE R =6.0
® THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL,
BUT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED
FOR A COMPLETE ACCEPTABLE WORKING INSTALLATION.
ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A
FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE
FULLY OPERATIVE AND ACCEPTANCE BY THE ARCHITECT AND / OR
ENGINEER MUST BE CONDITION OF THE CONTRACT.
�6 CONTRACTOR WILL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS.
r1 THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
WITH EXISTING CONDITIONS.
®PRIOR TO INSTALLING EQUIPMENT AND /OR FABRICATING DUCTWORK, A.C.
CONTRACTOR SHALL CHECK THAT THERE IS SUFFICIENT CLEARANCES FOR
EQUIPMENT , DUCTWORK, ETC. AND ALSO TO AVOID ANY INTERFERENCE
WITH THE PROCESS OF CONSTRUCTION.
IF THERE ARE ANY CHANGES IN ENGINEER'S DRAWINGS, IN DESIGN OR IN
EQUIPMENT, WITHOUT ENGINEER'S CONSENT, THE A.C. CONTRACTOR SHALL
ASSUME ALL RESPONSIBILITIES FOR THE PROJECT.
EXISTINCz SPLIT SYSTEM SCHEDULE
UNIT .
UNIT No I
TONS
5D -TONS
TOTAL CAPACITY 5TU/HR
55 500
SENS CAPACITY 5TUA4R
38 300
CFM SUPPLY
1 800
HEATER KW
10.0
VOLTAGE
1 -60 -240
DESIGN MANUFACTURER
GE
A.H.U. MODEL NO.
6535Y- 060K -C
G.U. MODEL NO.
5KCP39GFV4938
SEER
13.00
REFRIG. LIQUID /SUCTION
3/811- 7/8"
3'0 EXHAUST DUCT (METAL PIPE 30GA)
STEEL HANGER WIRE
TYPICAL CEILING CABINET
EXHAUST FAN WITH BACKDRAFT
DAMPER, 'LOW NOISE LEVEL'
AND NO VIBRATION.
FRONT FACE GRILLE WITH
FASTENING SCREENS
EXHAUST FAN HANGING
BRACKET (ADJUSTABLE)
CEILING MOUNTED CA51NET______
EXHAUST FAN DETAIL
N.T.S.
REVISED OUTSIDE AIR CALCULATIONS
AS PER FSC/M 4033
1165 SF / 100 S.F. PER PERSON - 12 PERSONS
O/A CFM REQUIRED 15 CFM / PERSON
12 x 15 - 180 CFM REQUIRED
CFM PROVIDED 200 CFM
SCOPE OF WORK
MECHANICAL WORKS:
PLAN TO REMAIN (ADD TWO
NEW EXHAUST FAN AND FRESH AIR
TO AHU CLOSET.
UNIT TO BE SECURED
(4) KWIK BOLT 3/8'X3
2 -1/2' MIN EMBEDMENT
R MIAMI —DADE COUNTY
ONCE 8C -5,
CONDENSING UNIT INSTALLATION DETAIL
NTS
08" FRESH AIR INTAKE FLEXIBLE DUCT
THROUGH SCREENED VENT WITH
MANUAL DAMPER SET AT 200 CFM.
AIR DISCHARGE
LENUM SHALL BE
MECHANICALLY
U L NU ATTACHED TO AHU.
Z FBC MEC 603.7
x 4 I
WALL ¢ A U
� A
REFRIG. LINES ` I A.H.U.
AT SWITCH C
ONDARY DRAIN LINE
PRINCIPAL
DRAIN LINE
TO OUTSIDE METAL STAND
AHU INSTALLATION DETAIL
NTS
EXISTNG
T14RUOGH
FAN SCHEDULE
ITEM
YES
EXISTING EF -1
NEW EF -2
MANUFAC.
x
NUTONE
NUT ❑NE
TYPE
SMOKE DAMPER(S)
CEILING
CEILING
CFM
80
210
SONES
.x
2.5
6.5
REFERENCE MODEL
SMOKE CONTROL
684NT
8210
REMARKS
4' 9( DUCT
7' 1( DUCT
THERM ❑FIN DUCT
VENT THRU WALL
WALL CAP WITH
INSECT SCREEM.
CONECT TO INDEPENT SWITCH
i
i
FXI4tWr 2' PVr_ Mhlo_ DRAN
EXISTING MECHANICAL PLAN
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
x
FIRE DAMPER (S)
x
SMOKE DAMPER(S)
x
FIRE RATED ENCLOSURE
x
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
.x
FIRE STOPPING
x
SMOKE CONTROL
x
LEGEND
l" EF -2
THRU WALL CAP
( ) EXISTING THERMOSTAT
1/477=1' -071.
•
• Cq
• Z Mv�
pm 4C LLI n
cbmlw� I
• xmJ
.902
•
4C Cl mi in
Cl
•
NOR
•
so z
•
am•
•
ME
•
Revision
om, ex R. G.
rl , * M. LOPEZ
owm 04/01/09
Sheet:
Project # 08-40
M -1