09-305-009AIR CONDITIONING NOTES �1 PROVIDE (FURNISH AND INSTALL) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS. AND HEREIN SPECIFIED. INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE, SMACNA, NFPA, AND LOCAL ORDINANCES. O DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR THE EXACT LOCATION OF EQUIPMENT. PIPING, DUCTWORK, ETC. �3 DUCTWORK IN UNCONDITIONED SPACE SHALL BE R =6.0 ® THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL, BUT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE ACCEPTABLE WORKING INSTALLATION. ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTANCE BY THE ARCHITECT AND / OR ENGINEER MUST BE CONDITION OF THE CONTRACT. �6 CONTRACTOR WILL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS. r1 THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE WITH EXISTING CONDITIONS. ®PRIOR TO INSTALLING EQUIPMENT AND /OR FABRICATING DUCTWORK, A.C. CONTRACTOR SHALL CHECK THAT THERE IS SUFFICIENT CLEARANCES FOR EQUIPMENT , DUCTWORK, ETC. AND ALSO TO AVOID ANY INTERFERENCE WITH THE PROCESS OF CONSTRUCTION. IF THERE ARE ANY CHANGES IN ENGINEER'S DRAWINGS, IN DESIGN OR IN EQUIPMENT, WITHOUT ENGINEER'S CONSENT, THE A.C. CONTRACTOR SHALL ASSUME ALL RESPONSIBILITIES FOR THE PROJECT. EXISTINCz SPLIT SYSTEM SCHEDULE UNIT . UNIT No I TONS 5D -TONS TOTAL CAPACITY 5TU/HR 55 500 SENS CAPACITY 5TUA4R 38 300 CFM SUPPLY 1 800 HEATER KW 10.0 VOLTAGE 1 -60 -240 DESIGN MANUFACTURER GE A.H.U. MODEL NO. 6535Y- 060K -C G.U. MODEL NO. 5KCP39GFV4938 SEER 13.00 REFRIG. LIQUID /SUCTION 3/811- 7/8" 3'0 EXHAUST DUCT (METAL PIPE 30GA) STEEL HANGER WIRE TYPICAL CEILING CABINET EXHAUST FAN WITH BACKDRAFT DAMPER, 'LOW NOISE LEVEL' AND NO VIBRATION. FRONT FACE GRILLE WITH FASTENING SCREENS EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CEILING MOUNTED CA51NET______ EXHAUST FAN DETAIL N.T.S. REVISED OUTSIDE AIR CALCULATIONS AS PER FSC/M 4033 1165 SF / 100 S.F. PER PERSON - 12 PERSONS O/A CFM REQUIRED 15 CFM / PERSON 12 x 15 - 180 CFM REQUIRED CFM PROVIDED 200 CFM SCOPE OF WORK MECHANICAL WORKS: PLAN TO REMAIN (ADD TWO NEW EXHAUST FAN AND FRESH AIR TO AHU CLOSET. UNIT TO BE SECURED (4) KWIK BOLT 3/8'X3 2 -1/2' MIN EMBEDMENT R MIAMI —DADE COUNTY ONCE 8C -5, CONDENSING UNIT INSTALLATION DETAIL NTS 08" FRESH AIR INTAKE FLEXIBLE DUCT THROUGH SCREENED VENT WITH MANUAL DAMPER SET AT 200 CFM. AIR DISCHARGE LENUM SHALL BE MECHANICALLY U L NU ATTACHED TO AHU. Z FBC MEC 603.7 x 4 I WALL ¢ A U � A REFRIG. LINES ` I A.H.U. AT SWITCH C ONDARY DRAIN LINE PRINCIPAL DRAIN LINE TO OUTSIDE METAL STAND AHU INSTALLATION DETAIL NTS EXISTNG T14RUOGH FAN SCHEDULE ITEM YES EXISTING EF -1 NEW EF -2 MANUFAC. x NUTONE NUT ❑NE TYPE SMOKE DAMPER(S) CEILING CEILING CFM 80 210 SONES .x 2.5 6.5 REFERENCE MODEL SMOKE CONTROL 684NT 8210 REMARKS 4' 9( DUCT 7' 1( DUCT THERM ❑FIN DUCT VENT THRU WALL WALL CAP WITH INSECT SCREEM. CONECT TO INDEPENT SWITCH i i FXI4tWr 2' PVr_ Mhlo_ DRAN EXISTING MECHANICAL PLAN HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR x FIRE DAMPER (S) x SMOKE DAMPER(S) x FIRE RATED ENCLOSURE x FIRE RATED ROOF /FLOOR CEILING ASSEMBLY .x FIRE STOPPING x SMOKE CONTROL x LEGEND l" EF -2 THRU WALL CAP ( ) EXISTING THERMOSTAT 1/477=1' -071. • • Cq • Z Mv� pm 4C LLI n cbmlw� I • xmJ .902 • 4C Cl mi in Cl • NOR • so z • am• • ME • Revision om, ex R. G. rl , * M. LOPEZ owm 04/01/09 Sheet: Project # 08-40 M -1 m