Loading...
11-1013-00619 Scope Of Work 1. The fire alarm should be UL certificated. 2. The Fire Alarm System is design for Larkin Community Hospital at 6129 5W 70th Street 5outh Miami FL 33143. 3. All equipment shall be new and U.L. Listed. 4. This Design is based on the budding having a 10096 5prinkler Fire Protection System. 5. Knox box rs provided by others. G. Visual devices in rooms MRI 123, Gamma room 109, PET Cr 118, are not required based on been covered in control rooms. 7. The installation of the Fire Alarm System shall also comply with the NFPA -70 National Electrical Code (NEC) 2005 edition and the Florida Accessibility Code For Budding Construction. The installation shall also comply with NFPA -101, 2006 and NFPA -72, 2002. 8. The fire Alarm System shall consist of a Manual fire Detection and Notification System. The fire Alarm System Is a new 105000D Addressable fire Alain Control Panel. 9. All Fire Alarm equipment for this project shall be rated' POWER LIMITED' 10. The Fire Alain Control Panel shall have a standby battery backup as per NFPA 72, 2002, Article 4.4.1 .5.3.1 providing battery power capacity for the entire system to operate for 24 hours in normal mode and then, at the end of the period, for 5 minutes in the emergency mode. General Notes 1. Cable size shall comply with article 760-71 and the cable installation shall comply with the separation and use of conductors and cables as specified in articles and 760-6 I of the National Electrical Code. 2. Budding wiring shall specifically confirm with the National Electrical Code article 760 part III for Power - Limited Fire Protection Signal Circuits with emphasis on article 760 -52(b) on Power Limited Wrong Method and Materials. 3. MINIMUM CABLE 51ZE: A. # 16 AWG Copper (2 # 16 FPLP) for: 5moke Detectors, Duct Detectors, Pull Stations, Water and Tamper 5witche5. B. # 14 AWG Copper (2 # 14 FPLP) for: Horns, Strobes and Horn/Strobes notification devices. 4. All new wiring installed in ducts, plenums and other spaces used for environmental air shall be type FPLP, as per NEC (National Electrical Code) article 760 -61. 5. The Design installation complies with FBC 11-4-28.3. G. All Alarm notification devices shall be audible and visual and shall be done via Hornl5trobe combination devices. Strobes shall be clear xenon type, with Intensity of 75 candelas as per Article 4.28 (1) through (5) of the ADA guidelines of July 2G, 1992 and as per article 4.28 4 4.28.3 of the Florida Accessibility Code for Budding Construction. 7. Hornl5trobe and Strobe devices shall be placed 80' (9-81 to the bottom of lens above the highest floor level within the space or G' below the ceding whichever is lower as per ADA guidelines and article 4.28 (6) of the Florida Accessibility Code for Budding Construction. 8. The distance from any place to a notification device shall not exceed 50' as per article 4.28 (7) and (8) of the Florida Accessibility Code for Budding Construction. 9. Pull Stations and zone number shall be Installed at 48' AFF to lever as per article 4.2.5 of the Florida Accessibility Code for Budding Construction. 10. The location of the audible devices has been designed as to be effectively heard 15 dB above ambient noise level obtained under normal condition of occupancy as per Article 7.4.2.1 of the NFPA 72 2002 edition., the NFPA 101 article 9.6.3 and the Florida Accessibility Code for Budding Construction and the Florida Building Code. 11. This design was based on calculations over a set of plans provided to the design engineer. If the post installation on site tests conducted by the authority having jurisdiction determines that, because unforeseen conditions or changes in field parameters, the audible alarm level falls below the required level In specific areas, the number of audible Hornistrobes shall be increased to comply with the requirements and to the satisfaction of the authority having ,jurisdiction. 12. 5moke. Detectors shall be Installed as per article 5.7.3.2 of NFPA 72, 2002 edition. 13. Heat Detectors shall be Installed as per article 5.6.3.1 of NFPA 72, 2002 edition. 14. Fire wall penetrations shall have steel sleeves 15. This system will be Certificated or Placarded as a Central Station Service Fire Alarm System and is stated as such on the Plans (24 hours of secondary power supply). 16. Conduit fill shall not exceed 40% as per NEC (National Electrical Code) edition 2005. 17. Conduit most meet a minimum of V4. 18. Visible 51gnals Shall not be required in Exit 9talr Enclosures as per Article 9.6.3.5.5 of NFPA 101 2006 Edition. 19. Visible Notification Appliances 5hall be Located not more than 4.75 m (15 ft) from the and of the corridor with a separation not greater than 30.4 m (100 ft) between appliances as per article 7.5.4.2.5 of NFPA 72 2002 Edition. 20. The room containing the FACP and/or Power Supply (NAC) Is Mechanically ventilated. 22. The FA logbook will be stored within 5 feet of the FACP. Deficient free record of completion paper work will be provided at time of Fire Division Alarm inspection. 23. All Strobes shall be synchronized when more than two are in any field of vision unless they are separated by 55 feet. 24. Knox Box provided by others. 25. No Access Control or Maglocks to be part of the Scope of Work. Fire Alarm 5y5tem 5eauence Of Operation General Alarm System No. W -L -3060 F Rating - 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Asse * -Min 5 in. thick reinforced lightweight or normal weight (100 -150 pct) cancrets. Wall may also be constricted of any u Classified Canaete Blocks'. Max dian of opening is 4 in. See Concrete Bolcks (CAi'.1) cotegory in the Fire Resistance Directory for names or manufaturom 2. Steel Sleeve - Nom 4 h dam (or smaller) steel electrical metallic busing MM or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 MSG) golly steel skrere friction fit or cat into wd flesh with wall surfaces. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. b"Id the wall wrfaees, 3. Cables Aggregate am - sectional area of cables to be max 45 percent of the sou- sectiond area of the opening. Cables installed either Oax:entric* or scceritric* within the fire stop sy stem. The annular space between the cables and the periphery of the opening shall be min 1/4 in. to mac 3/4 in. Cables to be rigidly supported on both sides of the wall asenbly. The following types of cabs: may be wed: A. 7/C No. 12 AWG with polyvinyl dhlakfe (PVC) knubtion and out or jaaksL & Max 25 pair Na 24 AWG telephone cable with PVC insulation and outer jodA C. Max RG 59 (or smaller) comdal cable with polye *w (PE) insulation and PVC WA D. Multiple 24 fiber optical comma nicotion cable with PVC jacket, lave a max OD d 5/8 h E. liwough Penebatiig Products• - Max three capper conductor No. 8 AWG . Metal -Clad Cable +. AFC CABLE SYSTEMS INC 4. Fit, Void or Cc* MaterW - Sealant Min 5/8 in. thickness of Fill material applied within annulus, flush with both safaces of wall o sift. M WS" 1/2 in, fan bead of fill materiel :hall be applied orand the perknelm of sleeve on both side of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DN OF Han INC -- CP601S, CP606 or FS-One Sealant *Betrkg the UL Classiraotion Mork +Bearing the UL L" Mark ��0• ��sslF�Fo u,errrwnb �laeon�lte. � FlRESroP SYSTEMS JWa 24 2003 C us E. TAMPER 5WITCHE5 Activation of the Tamper Switches shall Initiate the following functions: 1. Generate an Audible Supervisory 51gnal at the Fire Alarm Control Panel. 2. Indicate the location of the Tamper Switch by displaying, in English, the Supervisory device and Its location on the FACP alphanumeric display. 3. Transmit a supervisory signal to the designated third party Listed Central station by way of DACT. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. F. TROUBLE Activation of the Trouble shall Initiate the following functions: 1. Generate an audible Trouble 51gnal at the fire Alarrn control Panel. 2. Indicate the location of the Trouble by displaying. In English, the troubled device and Its location on the FACP alphanumeric display. 3. Generate an audible Trouble Condition Signal at the fire Alarm control Panel. 4. Indicate the location of the Trouble Condition by displaying, in English, the device and its location on the FACP alphanumeric display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. G. ELEVATOR LOBBY 5MOKE DETECTORS (elevator lobby # machine room) Activation of the Smoke Detectors (elevator lobby i machine room only) shall Initiate the following functions of all the elevators associated with the corresponding Elevator Lobby or Machine Room: 1. Generate an Audible alarm signal at the fire Alarm Control Panel and at the Remote Annunciator Panel, 2. Generate an audible alarm signal simultaneously on all areas of the building by means of a Horns Devices. Generate a visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horr4trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, In English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. H. 5MOKE DAMPERS CONTROL RELAY5 Activation of the Smoke Damper Control Relays shall Initiate the following functions: I. Based on Smoke Control 5quence of Operation (by others), in the event of a fire alarm activation Control Relay will open or close the corresponding fire smoke damper. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. ALL 51GNALING LINE CIRCUiT5 SHALL BE CLA55 B, 5TYLE 4 ALL NOTIFICATION APPLIANCE CIRCUn 5HALL BE CLA55 A. STYLE Z ALL INITIATING DEVICE CiRCUIT5 SHALL BE CLA55 B, STYLE A �I System No. W -L -3065 F Ratings - 1 and 2 Hr ( See Item 1) T Rating - 0 Hr SECTION A -A 1. Wd Ann* -- The 1 or 2 fine -voted gypsum wabowd /stud wall assem* shall be constructed! of the mote Is and in the marxr specified in the kndlVAW U30D or U400 Series Wall and Partition Design in the UL Fn Resistance DkedM and shop include the fdowkg construction features: A. Studs -- Wall framing may con 313 of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. umber spaced 16 h OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 h OC. B. Gypsum Board' -- Nom 5/8 in. thick gypsum wdlb= d. with square or tapered edges. The gypa n wallboard type, thickness, number of layers, fastener type and sheet aientalion shah be as specified in the individual U300 or U40D Series Designs in the UL Fn Reststornoe Muiory. Max dam of opening is 4 h The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optkxal) - Nan 4 h diam (or smaller) steel electrical metallic tkibkg ( EMT) or Schedule 5 (or heavies) steel pipe or min 0.016 kn. thick (28 MSG) gale :Gel sleeve out into wall assono Mth font compand and installed flush with wall wrfoces. When Sdnedi 5 steel pipe or EMT is wed, sleeve may extend up to 18 in. beyond the wall surfaces. L.rLJ��• Iled.ewNwe� �lt0oe bei�Mrc. d n1rjmw sYsfENs Jke n 2e, 2003 C ) US ._J. ELEVATOR RECALL FOR FIRE FIGHTERS 5ERVICE. (NFPA 72 6.15.3_) 1. 6.15.3.1 System -type smoke detectors. or other automatic fire detection as permitted by by 6.15.3.7, located in elevator lobbies, elevator holstways, and elevator machine rooms Including machine space, control room, and control space used to Initiate fire fighter's service recall, shall be connected to the e fire alarm system._ - -_ •_ -_- . ._ -__ -- .- _- .---- _- __ -_..__ -- -._ - -_ _ - . -- _ - -- - - r2: 6. f 5.3.2• In facilities without a building fire alarm system, these smoke detectors, or other automatic fire detection as permitted by 6.15.3.7. shall be connected to a a dedicated function fire alarm control unit that shall be desgnated as 'elevator recall control and supervisory control unit'. ermane identified on_the.dedc*,ed function fire alarm control unit and on the record drawn 3. 6.15.3.3 Unless otherwise required by the authority having jurisdiction, only the elevator lobby. �---- elevator hoistway, and the elevator machine room smoke detectors, or other automatic fire detection " as permitted by 6.15.3.7, shall be used to recall elevators for fire fighter's service. 4. 6.15.3.4 Each elevator lobby, elevator hoistway, and elevator machine room smoke detector, or other automatic fire detection as permitted by 6.15.3.7. shall be capable of initiating elevator recall when all other devices on the same initiaiting device circuit have been manually or automatically placed In the alarm condition. 5. 6.15.3.5' A lobby smoke detector shall be located on the ceding within 6.4 m (21 ft) of the centerline of each elevator door within the elevator bank under control of the detector. J. ELEVATOR SHUTDOWN I. 6.15.4.1' Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. 2.6.15.4.2 If heat detectors are used to shut down elevator power prior to spirnkkler operation, they shall be placed within 610 mm (2 ft) of each sprinkler head and be installed in accordance with the requirements of chapter 5. Alternatively, engineering methods, such as specified in Annex B. shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. 3. 6.15.4.3• If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers. the use of devices with time -delay switches or time -delay capability shall not be permitted. 4. 6.15.4.4' Control circuits to shut down elevator power shall be montored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. 5.6.15.4.5 The Initiating devices described in 6.15.4.2 and 6.15.4.3 shall be monitored for Integrity by the fire alarm control unit required in 6.15.3.1 and 6.15.3.2. K. FLOW BELL Activation of the Flow Bell shall initiate the following functions: I . Flow Bell shall activate upon water flow. 2. Flow Bell shall sound as long as water Is flowing. 3. Flow Bell shall not be silenceable from FACP. �I System No. W -L -3065 F Ratings - 1 and 2 Hr (See Rem 1) = T Rating - 0 Hr 3. Cables - Aggregate cross - sectional area of cable in opening to be max 45 percent of the cross- sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 1/4 in. to max 3/4 in. Cables to be rigidly supported on both aides of the wall msentbllr. Any eanbination of the following typo and saes of copper conductor cabin may be used: A. Max 7/C No. 12 AWG with potyvirryl chloride (PVC) insulation and jacket. B. Max 25 pair Na 24 AWG telephone cable with PVC insulation and WAsL C. Type RG/U coandal cable with polyethyl nne ('PE) insulation and PVC jacket having a max outside diameter of X in. D. Multiple flea optical communication cable jacketed with PVC and having a max 00 of 5/8 in. E Through Penetrating Products • -- Max three copper conductor Na 8 AWG . Metal -Clad Cable +. AFC CABLE SYSTEMS INC F. Max 3/C (with groundxor smaller) No. 8 AWG copper conductor cable with PVC insulation 4. Fell, Veld or Ca* Matelot -- SeWont Fill material applied within the ovx* s, flush with each end of the steel sleeve or wall surface. Fill moterial Installed synmetricaily on both sides of the wall. A min 5/8 h thickness of sealant is required for the 1 or 2 hr F Rating . M additional 1/2 in. dam bead of fill material stall be applied wound the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HIL11 CONSTRUCTION CHEMICALS, DN OF HILTI INC -- CP601S, CP606 or FS-One Seakwnt *Bewinng the UL Classification Mark `S1gFo utaw.w..le �nl�o Im `i �sroP sYsi on Jinn 2116 sow C US STROBE OR Horn /Strobe 80" A.F.F. OR 6' BELOW CEILING fMOM OF LENS) (WHICHEV1ER IS LOWER) PULL STATION 48" A.F.F. ADA HEIGHT REQUIREMENTS NO SCALE HSHA" M 2 d, d� f to D21 YEL [tOW40ttor oena r. 2 It 2 R R R R m ®mr9 FACP ELEVATOR 1SL_ L€VEL MACH. RM. T TO SHUNT t TRIP DEVICE m SHAFT THIS DIAGRAM IS AN APPROXIMATION. PLEASE CONSULT YOUR ELECTRICAL ENGINEER FOR THE SPECIFIC REQUIREMENTS OF YOUR PROJECT. NIO ES: 1. DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO PRIMARY FLOOR RELAY. I SMOKE DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO SECONDARY FLOOR RELAY. & SMOKE DETECTOR ACTIVATION SHALL ACTIVATE ELEVATOR WARNING LIGHT. 4. HEAT DETECTOR SHALL BE LOCATED WITH IN 18' OF SPRINKLER AND SHALL ACTIVATE SHUNT TRIP BREAKER. ELEVATOR FIRE SAFETY STANDARD NOT TO Sc#a CUSTOMER APPROVAL I have reviewed these plans and they conform to our requirements. I understand that ary modifications to these plans will be an additional service. Print Name 1 Accepted as is O Accepted as noted 0 , Unaccepted Date 5 Ali: r.. --.........I FIALLO'S NIEP DESIGN, INC. CA #28637 9301 SW 92nd Ave. A213 Miami, FL 33176 Phone (305) 877 -1845 Fax (305) 595 -6334 REGISTRATION des E -MAIL: JORGE FIALLO: 65527 fiall o2004`®ynhoo. com N' MO. rY. •` t iY.ro Z) iAT'• ,- � n _A U� Automatic response functions shall be Initiated only by the first fire alarm received. Additional alarms shall be received, annunciated and shall Initiate functions associated i exclusively with subsequent alarm. Common alarm function shall not be Initiated unless the first alarm is returned to normal. The actuation of the fire alarm Initiating device shall automatically Initiate the function detailed below: A. MANUAL FlRE ALARM PULL 5TATION Activation of the Manual Fire Alarm Pull Station shall Initiate the following functions: I. Generate an audible alarm signal at the Fire Alarm Control 2. Generate an audible alarm signal simultaneously on all areas of the budding by means of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the building by the use of strobe devices or combination Horml5trobe notification devices. 3. Indicate the location of the Pull Station by displaying, in English, the alarmed device and Its location on the FACP alphanumeric display 4. Transmit a fire alarm signal to the designated third party Listed Central 5tation by way of DACT. B. 5MOKE AND HEAT DETECTOR5 A Activation of 5moke and heat Detectors shall initiate the following functions: 1. Generate an Audible alarm signal at the Fire Alarm Control Panel. 2. Generate an audible alarm signal simultaneously on all areas of the building by means of Horn devices. Generate a visual alarm signal simultaneously on all areas of the building by the use of strobe devices or combination Hornl5trobe notification devices. 3. indicate the location of the Smoke Detector by displaying, in English, the alarmed device and Its location on the FACP alphanumeric display. 4. Indicate the location of the Heat Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display. 5. Transmit a fire alarm signal to the designated third party Listed Central Station by way of DACT. C. DUCT DETECTORS Activation of Duct Detectors shall Instate the following functions: d I. Generate a Supervisory signal at the Fire Alarm Control Panel and at the T.j Remote Annunciator Panel. . o 2. Indicate the location of the Duct Detector by displaying. In English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator �r alphanumeric display. J 3. Transmit a Supervisory signal to the designated third party Listed Central Station by way of DACE. 4. Activation of a Duct Detector shall cause its associated air handler to shutdown inmedlately, without delay. 5. Duct Smoke Detector shall set fire alarm Into supervisory mode, and the remote test switch shall be provided with an audioAnsual LED Indicator. located In a normally occupied area 48' AFF'. NFPA 90A 6- 4.4.3(1), and (2) 2002 Edition. D. WATER FLOW DETECTORS Activation of the Water Flow Detectors shall Initiate the following functions: O O 0 1. Generate an Audible alarm signal at the Fire Alarm Control Panel. 0= BY. 2. Generate an audible alarm signal simultaneously on all areas of the budding by ins 08.22.1 1 means of a Horn Devices. Generate a visual alarm signal simultaneously on all areas of CC the budding by the use of strobe devices or combination Homl5trobe notification devices. I 3. Indicate the location of the Water Flow Detector by displaying, In English, the alarmed device and its location on the FACP alphanumeric display. 4. Transmit a Waterflow Alarm signal to the designated third party Listed Central 5tation by way of DACT. ..� Integrated Security Systems ...r.... 1876 NW 7th Street VoiceFlorida 324.8 Vice :305.324.8800 Fox 305.324.0008 E-mol hfoeTeomlSS.com URL w .T"mISS.com PROPRIETARY TO INTEGRATED SECURITY SYSTEMS COPYRIGHT O 2011 System No. W -L -3060 F Rating - 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Asse * -Min 5 in. thick reinforced lightweight or normal weight (100 -150 pct) cancrets. Wall may also be constricted of any u Classified Canaete Blocks'. Max dian of opening is 4 in. See Concrete Bolcks (CAi'.1) cotegory in the Fire Resistance Directory for names or manufaturom 2. Steel Sleeve - Nom 4 h dam (or smaller) steel electrical metallic busing MM or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 MSG) golly steel skrere friction fit or cat into wd flesh with wall surfaces. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. b"Id the wall wrfaees, 3. Cables Aggregate am - sectional area of cables to be max 45 percent of the sou- sectiond area of the opening. Cables installed either Oax:entric* or scceritric* within the fire stop sy stem. The annular space between the cables and the periphery of the opening shall be min 1/4 in. to mac 3/4 in. Cables to be rigidly supported on both sides of the wall asenbly. The following types of cabs: may be wed: A. 7/C No. 12 AWG with polyvinyl dhlakfe (PVC) knubtion and out or jaaksL & Max 25 pair Na 24 AWG telephone cable with PVC insulation and outer jodA C. Max RG 59 (or smaller) comdal cable with polye *w (PE) insulation and PVC WA D. Multiple 24 fiber optical comma nicotion cable with PVC jacket, lave a max OD d 5/8 h E. liwough Penebatiig Products• - Max three capper conductor No. 8 AWG . Metal -Clad Cable +. AFC CABLE SYSTEMS INC 4. Fit, Void or Cc* MaterW - Sealant Min 5/8 in. thickness of Fill material applied within annulus, flush with both safaces of wall o sift. M WS" 1/2 in, fan bead of fill materiel :hall be applied orand the perknelm of sleeve on both side of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DN OF Han INC -- CP601S, CP606 or FS-One Sealant *Betrkg the UL Classiraotion Mork +Bearing the UL L" Mark ��0• ��sslF�Fo u,errrwnb �laeon�lte. � FlRESroP SYSTEMS JWa 24 2003 C us E. TAMPER 5WITCHE5 Activation of the Tamper Switches shall Initiate the following functions: 1. Generate an Audible Supervisory 51gnal at the Fire Alarm Control Panel. 2. Indicate the location of the Tamper Switch by displaying, in English, the Supervisory device and Its location on the FACP alphanumeric display. 3. Transmit a supervisory signal to the designated third party Listed Central station by way of DACT. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. F. TROUBLE Activation of the Trouble shall Initiate the following functions: 1. Generate an audible Trouble 51gnal at the fire Alarrn control Panel. 2. Indicate the location of the Trouble by displaying. In English, the troubled device and Its location on the FACP alphanumeric display. 3. Generate an audible Trouble Condition Signal at the fire Alarm control Panel. 4. Indicate the location of the Trouble Condition by displaying, in English, the device and its location on the FACP alphanumeric display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. G. ELEVATOR LOBBY 5MOKE DETECTORS (elevator lobby # machine room) Activation of the Smoke Detectors (elevator lobby i machine room only) shall Initiate the following functions of all the elevators associated with the corresponding Elevator Lobby or Machine Room: 1. Generate an Audible alarm signal at the fire Alarm Control Panel and at the Remote Annunciator Panel, 2. Generate an audible alarm signal simultaneously on all areas of the building by means of a Horns Devices. Generate a visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horr4trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, In English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. H. 5MOKE DAMPERS CONTROL RELAY5 Activation of the Smoke Damper Control Relays shall Initiate the following functions: I. Based on Smoke Control 5quence of Operation (by others), in the event of a fire alarm activation Control Relay will open or close the corresponding fire smoke damper. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. ALL 51GNALING LINE CIRCUiT5 SHALL BE CLA55 B, 5TYLE 4 ALL NOTIFICATION APPLIANCE CIRCUn 5HALL BE CLA55 A. STYLE Z ALL INITIATING DEVICE CiRCUIT5 SHALL BE CLA55 B, STYLE A �I System No. W -L -3065 F Ratings - 1 and 2 Hr ( See Item 1) T Rating - 0 Hr SECTION A -A 1. Wd Ann* -- The 1 or 2 fine -voted gypsum wabowd /stud wall assem* shall be constructed! of the mote Is and in the marxr specified in the kndlVAW U30D or U400 Series Wall and Partition Design in the UL Fn Resistance DkedM and shop include the fdowkg construction features: A. Studs -- Wall framing may con 313 of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. umber spaced 16 h OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 h OC. B. Gypsum Board' -- Nom 5/8 in. thick gypsum wdlb= d. with square or tapered edges. The gypa n wallboard type, thickness, number of layers, fastener type and sheet aientalion shah be as specified in the individual U300 or U40D Series Designs in the UL Fn Reststornoe Muiory. Max dam of opening is 4 h The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optkxal) - Nan 4 h diam (or smaller) steel electrical metallic tkibkg ( EMT) or Schedule 5 (or heavies) steel pipe or min 0.016 kn. thick (28 MSG) gale :Gel sleeve out into wall assono Mth font compand and installed flush with wall wrfoces. When Sdnedi 5 steel pipe or EMT is wed, sleeve may extend up to 18 in. beyond the wall surfaces. L.rLJ��• Iled.ewNwe� �lt0oe bei�Mrc. d n1rjmw sYsfENs Jke n 2e, 2003 C ) US ._J. ELEVATOR RECALL FOR FIRE FIGHTERS 5ERVICE. (NFPA 72 6.15.3_) 1. 6.15.3.1 System -type smoke detectors. or other automatic fire detection as permitted by by 6.15.3.7, located in elevator lobbies, elevator holstways, and elevator machine rooms Including machine space, control room, and control space used to Initiate fire fighter's service recall, shall be connected to the e fire alarm system._ - -_ •_ -_- . ._ -__ -- .- _- .---- _- __ -_..__ -- -._ - -_ _ - . -- _ - -- - - r2: 6. f 5.3.2• In facilities without a building fire alarm system, these smoke detectors, or other automatic fire detection as permitted by 6.15.3.7. shall be connected to a a dedicated function fire alarm control unit that shall be desgnated as 'elevator recall control and supervisory control unit'. ermane identified on_the.dedc*,ed function fire alarm control unit and on the record drawn 3. 6.15.3.3 Unless otherwise required by the authority having jurisdiction, only the elevator lobby. �---- elevator hoistway, and the elevator machine room smoke detectors, or other automatic fire detection " as permitted by 6.15.3.7, shall be used to recall elevators for fire fighter's service. 4. 6.15.3.4 Each elevator lobby, elevator hoistway, and elevator machine room smoke detector, or other automatic fire detection as permitted by 6.15.3.7. shall be capable of initiating elevator recall when all other devices on the same initiaiting device circuit have been manually or automatically placed In the alarm condition. 5. 6.15.3.5' A lobby smoke detector shall be located on the ceding within 6.4 m (21 ft) of the centerline of each elevator door within the elevator bank under control of the detector. J. ELEVATOR SHUTDOWN I. 6.15.4.1' Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. 2.6.15.4.2 If heat detectors are used to shut down elevator power prior to spirnkkler operation, they shall be placed within 610 mm (2 ft) of each sprinkler head and be installed in accordance with the requirements of chapter 5. Alternatively, engineering methods, such as specified in Annex B. shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. 3. 6.15.4.3• If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers. the use of devices with time -delay switches or time -delay capability shall not be permitted. 4. 6.15.4.4' Control circuits to shut down elevator power shall be montored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. 5.6.15.4.5 The Initiating devices described in 6.15.4.2 and 6.15.4.3 shall be monitored for Integrity by the fire alarm control unit required in 6.15.3.1 and 6.15.3.2. K. FLOW BELL Activation of the Flow Bell shall initiate the following functions: I . Flow Bell shall activate upon water flow. 2. Flow Bell shall sound as long as water Is flowing. 3. Flow Bell shall not be silenceable from FACP. �I System No. W -L -3065 F Ratings - 1 and 2 Hr (See Rem 1) = T Rating - 0 Hr 3. Cables - Aggregate cross - sectional area of cable in opening to be max 45 percent of the cross- sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 1/4 in. to max 3/4 in. Cables to be rigidly supported on both aides of the wall msentbllr. Any eanbination of the following typo and saes of copper conductor cabin may be used: A. Max 7/C No. 12 AWG with potyvirryl chloride (PVC) insulation and jacket. B. Max 25 pair Na 24 AWG telephone cable with PVC insulation and WAsL C. Type RG/U coandal cable with polyethyl nne ('PE) insulation and PVC jacket having a max outside diameter of X in. D. Multiple flea optical communication cable jacketed with PVC and having a max 00 of 5/8 in. E Through Penetrating Products • -- Max three copper conductor Na 8 AWG . Metal -Clad Cable +. AFC CABLE SYSTEMS INC F. Max 3/C (with groundxor smaller) No. 8 AWG copper conductor cable with PVC insulation 4. Fell, Veld or Ca* Matelot -- SeWont Fill material applied within the ovx* s, flush with each end of the steel sleeve or wall surface. Fill moterial Installed synmetricaily on both sides of the wall. A min 5/8 h thickness of sealant is required for the 1 or 2 hr F Rating . M additional 1/2 in. dam bead of fill material stall be applied wound the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HIL11 CONSTRUCTION CHEMICALS, DN OF HILTI INC -- CP601S, CP606 or FS-One Seakwnt *Bewinng the UL Classification Mark `S1gFo utaw.w..le �nl�o Im `i �sroP sYsi on Jinn 2116 sow C US STROBE OR Horn /Strobe 80" A.F.F. OR 6' BELOW CEILING fMOM OF LENS) (WHICHEV1ER IS LOWER) PULL STATION 48" A.F.F. ADA HEIGHT REQUIREMENTS NO SCALE HSHA" M 2 d, d� f to D21 YEL [tOW40ttor oena r. 2 It 2 R R R R m ®mr9 FACP ELEVATOR 1SL_ L€VEL MACH. RM. T TO SHUNT t TRIP DEVICE m SHAFT THIS DIAGRAM IS AN APPROXIMATION. PLEASE CONSULT YOUR ELECTRICAL ENGINEER FOR THE SPECIFIC REQUIREMENTS OF YOUR PROJECT. NIO ES: 1. DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO PRIMARY FLOOR RELAY. I SMOKE DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO SECONDARY FLOOR RELAY. & SMOKE DETECTOR ACTIVATION SHALL ACTIVATE ELEVATOR WARNING LIGHT. 4. HEAT DETECTOR SHALL BE LOCATED WITH IN 18' OF SPRINKLER AND SHALL ACTIVATE SHUNT TRIP BREAKER. ELEVATOR FIRE SAFETY STANDARD NOT TO Sc#a CUSTOMER APPROVAL I have reviewed these plans and they conform to our requirements. I understand that ary modifications to these plans will be an additional service. Print Name 1 Accepted as is O Accepted as noted 0 , Unaccepted Date 5 Ali: r.. --.........I FIALLO'S NIEP DESIGN, INC. CA #28637 9301 SW 92nd Ave. A213 Miami, FL 33176 Phone (305) 877 -1845 Fax (305) 595 -6334 REGISTRATION des E -MAIL: JORGE FIALLO: 65527 fiall o2004`®ynhoo. com N' MO. rY. •` t iY.ro Z) iAT'• ,- � n _A U� i 0 I as t-; A '1 CO d T.j W . o to �r CY7 J ! 02 Z.. ...i O O 0 .--4 b o, ind � tY H W U al. LUJ U CO U O I gJ � ice_- w N 0 z � � U_ 0 N e rS � . EIn Sheet Number FA -03 of 04 i 0 I A '1 d J ! I CC :2 I rS � . EIn Sheet Number FA -03 of 04