Loading...
11-1013-0055co pe Of Work 1. The fire alarm should be UL certificated. 2. The Fire Alarm System is design for Larkin Community Hospital at 6129 5W 70th Street South Miami FL 33143. 3. All equipment shall be new and U.L. Listed. 4. This Design is based on the building having a 100% Sprinkler fire Protection System. 5. Knox box is provided by others. G. Visual devices in rooms MRI 123, Gamma room 109, PET Cr 118, are not required based on been covered in control rooms. 7. The installation of the Fire Alarm System shall also comply with the NFPA-70 National Electrical Code (NEC) 2005 edition and the Honda Accessibility Code for Budding Construction. The installation shall also comply with NFPA -101, 2006 and NFPA -72, 2002. 8. The Fire Alarm System shall consist of a Manual fine Detection and Notification System. The fire Alarm System 15 a new 1050OGD Addressable Fire Alarm Control Panel. 9. All Fire Alarm equipment for this project shall be rated' POWER LIMITED' 10. The Fire Alarm Control Panel shall have a standby battery backup as per NFPA 72, 2002, Article 4.4.1.5.3.1 providing battery power capacity for the entire system to operate for 24 hours in normal mode and then, at the end of the period, for 5 minutes in the emergency mode. General Notes 1. Cable sou shall comply with article 760-71 and the cable installation shall comply with the separation and use of conductors and cables as specified In articles and 760-61 of the National Electrical Code. 2. Building wiring shall specifically confirm with the National Electrical Code article 760 part III for Power - Limned Fire Protection Signal Circuits with emphasis on article 760 -52(b) on Power Limited Wiring Method and Materials. 3. MINIMUM CABLE 51ZE: A. # 16 AWG Copper (2 # 16 FPLP) for: Smoke Detectors, Duct Detectors, Pull Stations, Water and Tamper Switches. B. # 14 AWG Copper (2 # 14 FPLP) for: Horns, Strobes and Hor*trobea notification devices. 4. All new wring installed in ducts, plenums and other spaces used for environmental air shall be type FPLP, as per NEC (National Electrical Code) article 760 -61. 5. The Design installation complies with FBC 11-4-28.3. G. Al! Alarm notification devices shall be audible and Visual and shall be done via Horl/5trobe combination devices. 5trobes shall be clear xenon type, with intensity of 75 candelas as per Article 4.28 (1) through (5) of the ADA guidelines of July 26,1992 and as per article 4.28 4 4.28.3 of the Florida Accessibility Code for Budding Construction. 7. Hoff4trobe and Strobe devices shall be placed 80' (9-6) to the bottom of lens above the highest floor level within the space or G" below the telling whichever is lower as per ADA guidelines and article 4.28 (6) of the Ronda Accessibility Code for Budding Construction. 8. The distance from any place to a notification device shall not exceed 50' as per article 4.28 (7) and (8) of the Florida Accessibility Code for Budding Construction. 9. Pull Stations and zone number shall be Installed at 48" AFF to lever as per article 4.2.5 of the Flonda Accessibility Code for Budding Construction. 10. The location of the audible devices has been designed as to be effectively heard 15 dB above ambient noise level obtained under normal condition of occupancy as per Article 7.4.2.1 of the NFPA 72 2002 edition., the NFPA 101 article 9.6.3 and the Florida Accessibility Code for Budding Construction and the Ronda Budding Code. I I. This design was based on calculations over a set of plans provided to the design engineer. If the post Installation on site tests conducted by the authority having jurisdiction determines that, because unforeseen conditions or changes In field parameters, the audible alarm level falls blow the required level In specific areas, the number of audible Horr1/strobes shall be Increased to comply with the requirements and to the satisfaction of the authority having Jurisdiction. 12. Smoke Detectors shalt be installed as per article 5.7.3.2 of NFPA 72, 2002 edition. 13. Heat Detectors shall be Installed as per article 5.6.3.1 of NFPA 72.2002 edition. 14. Fire wall penetrations shall have steel sleeves 15. This system will be Certificated or Placarded as a Central Station Service Fire Alarm System and Is stated as such on the Plans (24 hours of secondary power supply). i G. Conduit fill shall not exceed 40% as per NEC (National Electrical Code) edition 2005. 17. Conduit most meet a minimum of s/4 . 18. Visible Signals Shall not be required In Exit Stair Enclosures as per Article 9.6.3.5.5 of NMA 101 2006 Edition. 19. Visible Notification Appliances Shall be Located not more than 4.75 m (15 ft) from the end of the corridor with a separation not greater than 30.4 m ( 100 ft) between appliances as per article 7.5.4.2.5 of NFPA 72 2002 Edition. 20. The room containing the FACP and/or Power Supply (NAC) is Mechanically ventilated. 22. The FA logbook will be stored within 5 feet of the FACP. Deficient free record of completion paper work will be provided at time of Fire Division Alarm inspection. 23. All Strobes shall be synchronized when more than two are in any field of Vision unless they are separated by 55 feet. 24. Knox Box provided by others. 25. No Access Control or Maglocks to be part of the Scope of Worts. Fire Alarm System 5eauence Of Operation General Alarm System No. W -L -3060 F Rating - 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Aswn* - Min 5 in. tick reinforced ightweNht or nomad weigh (tOD -150 pd) carnaete. Wall may also be constructed of any UL Classified Concrete Mocks*. Max alum of opening Is 4 stn. See Concrete Bolden (Wo cotegory in the Fn Resistance Directory for macs or matifochrers. 2. Steel Sleeve - Nom 4 h dam (or smatter) steel sleeMool metallic tubing (EM7) or Schedule 5 (or heavier) steel ppippee or min 0.016 in. nick (28 MSG) gale steel sleeve friction fit or oast into wall fludn With wd eufooes. NAheh Sclodde 5 steel pips or EMT is used, sleeve may extend up to 18 in. beywnd tM wall stdoom 3. Cables Aggregate crass - sectional aria of cables to be max 45 percent of the crow- sectional arso of the gwk4 Cables inataded offlw co n entriedy or eccentrically within the fire stop system. The annular apex between tM cables and the periphery of the opening stall be min 1/4 h to max 3/4 in. Cables to be rigidly supported on both On of the wd an=*. The (dosing types of gables may be used: A. 7/C No. 12 AiNG with myf dheA* (PVC) insulation and outer jaduL B. Max 25 pair No. 24 = ele'lionet le' cable w M PVC insulations and outer jocloet. C. Max RG 59 (or smaller) coaxial cable with p**Om (PE) insulation and PVC jadtet. D. Multiple 24 fiber optical corrinvinication cable wM PVC jacicat, has a max OD of 5/8 h E. 11 rough IS NSW - � Om No` 8 AN ' Metal -Clad Cable+. 4. FiL Void or Cavity Material$ - Sealant Min 5/8 h ttidatesa of Fill matin applied wft a aAm flesh wdh both surfaces of wad ossernby. M additional 1/2 h than bead of fill material sad be applied around the perimeter of dem on both sides of the wd when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DN OF Han INC -- CP601S, CP6D5 or FS-one Sealant Vearhg the UL 0=11111cation Mark +Bearing the UL Listing Mark L.r�JI� U Ow tt ey iuttaeorrbwiorwewea, of rTmESTaP srsrE►rs +tween �. 20w C us E. TAMPER 5WITCHE5 Activation of the Tamper Switches shall Initiate the following functions: 1. Generate an Audible Supervisory Signal at the Fire Alarm Control Panel. 2. Indicate the location of the Tamper Switch by displaying, in English, the 5upermsory device and its location on the FACP alphanumeric display. 3. Transmit a supervisory signal to the designated third party Listed Central station by way of DACT. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. F. TROUBLE Activation of the Trouble shall initiate the following functions: I. Generate an audible Trouble 51gnal at the fire Alarm control Panel. 2. Indicate the location of the Trouble by displaying, In English, the troubled device and its location on the FACP alphanumeric display. 3. Generate an audible Trouble Condition 51gnal at the fire Alarm control Panel. 4. Indicate the location of the Trouble Condition by displaying, In English, the device and Its location on the FACP alphanumeric display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. G. ELEVATOR LOBBY SMOKE DETECTORS (elevator lobby 4 machine room) Activation of the Smoke Detectors (elevator lobby 4 machine room only) shall Initiate the following functions of all the elevators associated with the corresponding Elevator Lobby or Machine Room: I. Generate an Audible alarm signal at the fire Alarm Control Panel and at the Remote Annunciator Panel, 2. Generate an audible alarm signal simultaneously on all areas of the budding by means of a Horns Devices. Generate a Visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horl5trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, In English, the alarmed device and Its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. H. 5MOKE DAMPERS CONTROL RELAY5 Activation of the Smoke Damper Control Relays shall initiate the following functions: I. lased on Smoke Control 5quence of Operation (by others), In the event of a fire alarm activation Control Relay will open or close the corresponding fire smoke damper. The maximum time rend from actuation of the Initiating device until Initiation of all related functions as listed above shall be ten seconds. ALL SIGNALING LINE CIRCUIT5 5HALL BE CLA55 B, STYLE 4 ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLA55 A. STYLE Z ALL INITIATING DEVICE CIRCUITS SHALL BE CLA55 Be STYLE A 5 System No. W -L -3065 F Ratings - 1 and 2 Hr ( See Item 1) T Rating - 0 Hr SECTION A -A 1. Wd Aria" -- The 1 or 2 fire -rated gypsum wallboard/stud wd assembly slid be constructed of fie materials and in the manner specified In fie individual 11300 or U400 Saks Nod and Partition Designs in the UL Fire Resistance Directory and dab inckide the fdbwkg construction features: A. Studs -- Wd framhg may r o -list of either wood ands or steel channel studs. Wood atuda to cxsrelet of tam 2 by 4 in. lumber spaced 16 h OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 in. OC. B. Ojpsum Bond' -- Nan 5/8 in. thick gypsun walDoard, wit► square or tapered edges. The gypsum wallboard type, thickness, number of layers, fostarer type and sliest orientation std be as specified in tM individual U300 or U400 Series Designs in the UL Fn Resistance Directory. Max dom of opening is 4 h The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. dam (or under) abet electrical metallic tubing 9* ded Awn cost Into onerrnbip ) with joint compound and installed flesh wb wall w ) rfaoon. WM n SC We 5 item pipe or BiT is treed, sina may extend up to 18 h beyond the wd sufatss. 1'r rincsrav SYSTEMS ,imay 2a, 2ow C ® US I. ELEVATOR RECALL A. Smoke Detectors In elevator lobbies, shaft and or elevator machine room shall: I. Initiate an alarm condition in the building for evacuation purposes. 2. initiate the recall of the elevator cars as follows in accordance with NFPA 72 (2002 edition), chapter 6.15.3. B. Phase I recall: Any elevator lobby smoke detector located on floors 2 and above and/or any smoke detector in the elevator machine or elevator shaft shall Initiate phase I recall which will bring the elevator car to the first floor and lock the doors In the open position. C. Phase II recall: Any elevator lobby smoke detector located on the first floor shall initiate recall which will bring the elevator car to the second floor and lock the doors in the open position. D. Elevator Warning Lights: Actuation of any elevator machine room smoke detector or elevator hoistway detector shall also Initiate the elevator warning lights to alert emergency personnel taht the elevators are not safe for use as required in NFPA 72 (2002 edition) chapter 6.15.3.9. E. 5hunt - Trip heat detectors: Heat detectors dedicated for elevator shunt shall be connected where required and activate a control shunt to disconnect the elevator power upon activation. The shunt power source shall be monitored by the fire alarm control panel as required in NFAP 72 (2002 edition) chapter 6.15.4.4. J. ELEVATOR SHUTDOWN 1. 6.15.4.1 • Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. 2. 6.15.4.2 If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 610 mm (2 ft) of each sprinkler head and be installed in accordance with the requirements of chapter 5. Alternatively, engineering methods, such as specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. 3. 6.15.4.3' If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time -delay switches or time -delay capability shall not be permitted. 4. 6.15.4.4' Control circuits to shut down elevator power shall be monntored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. 5. 6.15.4.5 The initiating devices described in 6.15.4.2 and 6.15.4.3 shall be monitored for integrity by the fire alarm control unit required In 6.15.3.1 and 6.15.3.2. K. FLOW BELL Activation of the Flow Bell shall Initiate the following functions: I . Flow Bell shall activate upon water flow. 2. Flow Bell shall sound as long as water Is flowing. g'jRE ALARM SYSTEM TO BV, 3. Flow Bell shall not be sdenceable from FACP. INSTALLED IN ACCORDANCE WITH NFPA72; 70;101- APPROVED D NRA 11 -DA.DE COUNTY FIRE DEPARTMENT BLDG. PERMIT FIRE ALARM_ FiRE SUPPRESSION WATER MAIN EXT. OAT hzzi By FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 1 Syystem No. W -L -3065 F Rafings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr 3. Cables -- Aggregate am- sectional area of cable in operwrg to be max 45 percent of the -' cross- sectional area of the opening. The mnulcr space between the cable bundle and the pedpWry of the opening to be min 1/4 in. to mox 3/4 h Cables to be rigidly supported on both skin of tM wall anemby. Arty combination of the following typo and can of copper conductor cables may be user: A. last 7/C No. 12 AMC with polyvinyl dioride (PVC) insuaation and locket. B. Max 25 pair Na 24 AWG; telephone cable vft PVC insulation and jodet. C. Type RG/U waial cable with potyethyles (PE) insulation and PVC jacket having a max outside diameter of A in. D. Multiple fiber optical tommiunication cable jociceted wM PVC and hawing a max OD of 518 in. E Through Paietrating Products' -- Max tare copper conductor No. 8 MG . Metal -Clad CCable +. AFC CABLE SYSTEMS INC F. Max VIC (with groundxor smada) No. 8 ANiG copper conductor cable with PVC insulation and jacketing. 4. F8, Void or Cavity Material$ -- Sealant Fill material applied within the annulus, flush with each and of Ire steel desve or wall surface. Fri material inetoled Wmw** on both sides of the wall. Adiamm bead oaf fill tMdmn of soda Is required material shall be applied aroundfd the perimeter pleriime ter of sl an both additional oft /Me�wall when sleeve extends beyond surface of wall. HiLTi CONSTRUCTION CHEMICALS, DN OF HiLTi INC - CP601S, CM or FS-One Sealant 'Bearing the UL Classification Mark PAP �+lAlduw kin mica d Neap �r d rhitrsTOP srsa°a ,iwhxrwr za crow C US STROBE OR Hom /Strobe SW A.F.F. OR 6' BELOW CEIUNG BOTTOM OF LENS) (WHICHEYVt is LOWER) PULL STATION 48" A.F.F. ADA HEIGHT REQUIREMENTS NO SCALE �b� n 2 � t«note 2t�D VYEL Dr w con a Da «. T H 2 R R R R m ®mom 1S FACP 1ST MARCH. RAM. �2 � TO SHUNT TRIP DEVICE m v. sH THIS DIAGRAM IS AN APPROXIMATION. PLEASE CONSULT YOUR ELECTRICAL ENGINEER FOR THE SPECIFIC REQUIREMENTS OF YOUR PROJECT. NOTES! 1. DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO PRIMARY FLOOR RELAY. 2. SMOKE DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO SECONDARY FLOOR RELAY. * SMOKE DETECTOR ACTIVATION SHALL ACTIVATE ELEVATOR WARNING LIGHT. 4. HEAT DETECTOR SHALL BE LOCATED WITH IN 18' OF SPRINKLER AND SHALL ACTIVATE SHUNT TRIP BREAKER. ELEVATOR FIRE SAFETY STANDARD NOT TO SCAB 101.15TOMER APPROVAL I have reviewed thew plans and they conform to Accepted as is our requirements. I understand that ary modifications Accepted as rioted to these plans will be an additional service. Unaccepted Pnnt Name 5'gnatur+c Date Automatic response functions shall be lnitlaited only by the first fire alarm received. Additional alarms shall be received, annunciated and shall Initiate functions associated exclusively with subsequent alarm. Common alarm function shall not be Initiated unless the first alarm Is returned to normal. °�: The actuation of the fire alarm Initiating device shall automatically Initiate the function detailed below: -4--d A. MANUAL FIRE ALARM PULL STATION ..... RGE F1A •65527 Activation of the Manual Fire Alarm Pull Station shall Initiate the following functions: NfigIIt$65*Ahoo.c m,,r 1. Generate an audible alarm signal at the Fire Alarm Control 2. Generate an audible alarm signal simultaneously on all areas of the budding by means J(jt �- of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the - budding by the use of strobe devices or combination Horn6trobe notification devices. 3. Indicate the location of the Pull Station by displaying, In English, the alarmed device and Its location on the FACP alphanumeric display - - 4. Transmit a fire alarm signal to the designated third party Lasted Central - Station by way of DACT. B. 5MOKE AND HEAT DETECTORS Activation of Smoke and heat Detectors shall Initiate the following functions: 1. Generate an Audible alarm signal at the Fire Alarm Control Panel. 2. Generate an audible alarm signal simultaneously on all areas of the building by means of Horn devices. Generate a visual alarm signal simultaneously on all areas of the building by the use of strobe devices or combination HonV5trobe notification devices. U 3. Indicate the location of the 5moke Detector by displaying, in English, the alarmed device and Its location on the FACP alphanumeric display. C/0 4. Indicate the location of the Heat Detector by displaying, in English, the alarmed device and M Its location on the FACP alphanumeric display. 5. Transmit a fire alarm signal to the designated third party Listed Central Station by way of DACT. C. DUCT DETECTORS Activation of Duct Detectors shall Initiate the following functions: cr I. Generate a Supervisory signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2. Indicate the location of the Duct Detector by displaying, In English, the alarmed device and ct its location on the FACP aiphanumem display and on the Remote Annunciator alphanumeric display. ;-4 3. Transmit a 5upervlsory signal to the designated third party Listed Central Station by way of DACT. 4. Activation of a Duct Detector shall cause its associated air handler to shutdown Inmedlately, without delay. 5. Duct Smoke Detector shall set fire alarm Into supervisory mode, and the remote test switch shall be provided with an audioAmual LED indicator, located in a normally occupied area 48' AFF'. NFPA 90A 6- 4.4.3(1), and (2) 2002 Edition. D. WATER FLOW DETECTORS Activation of the Water Flow Detectors shall Initiate the following functions: 1. Generate an Audible alarm signal at the Fire Alarm Control Panel. CHtC �' 2. Generate an audible alarm signal simultaneously on all areas of the building by DATE, 08.22.1 1 means of a Horn Devices. Generate a visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horni5trobe notification devices. 3. Indicate the location of the Water Flow Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display. 4. Transmit a Water low Alarm signal to the designated third party Listed Central 5tation by way of DACT. Integrated Security Systems 'non' 1876 RW 7th Street Florida 33125 SMiami, Voice :305.324.8800 Fox 305.324.0008 E -moll infoOTeamISS com URL www,Twml4Seem It PROPRIETARY TO INTEGRATED SECURITY SYSTEMS COPYRIGHT 0 2011 System No. W -L -3060 F Rating - 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Aswn* - Min 5 in. tick reinforced ightweNht or nomad weigh (tOD -150 pd) carnaete. Wall may also be constructed of any UL Classified Concrete Mocks*. Max alum of opening Is 4 stn. See Concrete Bolden (Wo cotegory in the Fn Resistance Directory for macs or matifochrers. 2. Steel Sleeve - Nom 4 h dam (or smatter) steel sleeMool metallic tubing (EM7) or Schedule 5 (or heavier) steel ppippee or min 0.016 in. nick (28 MSG) gale steel sleeve friction fit or oast into wall fludn With wd eufooes. NAheh Sclodde 5 steel pips or EMT is used, sleeve may extend up to 18 in. beywnd tM wall stdoom 3. Cables Aggregate crass - sectional aria of cables to be max 45 percent of the crow- sectional arso of the gwk4 Cables inataded offlw co n entriedy or eccentrically within the fire stop system. The annular apex between tM cables and the periphery of the opening stall be min 1/4 h to max 3/4 in. Cables to be rigidly supported on both On of the wd an=*. The (dosing types of gables may be used: A. 7/C No. 12 AiNG with myf dheA* (PVC) insulation and outer jaduL B. Max 25 pair No. 24 = ele'lionet le' cable w M PVC insulations and outer jocloet. C. Max RG 59 (or smaller) coaxial cable with p**Om (PE) insulation and PVC jadtet. D. Multiple 24 fiber optical corrinvinication cable wM PVC jacicat, has a max OD of 5/8 h E. 11 rough IS NSW - � Om No` 8 AN ' Metal -Clad Cable+. 4. FiL Void or Cavity Material$ - Sealant Min 5/8 h ttidatesa of Fill matin applied wft a aAm flesh wdh both surfaces of wad ossernby. M additional 1/2 h than bead of fill material sad be applied around the perimeter of dem on both sides of the wd when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DN OF Han INC -- CP601S, CP6D5 or FS-one Sealant Vearhg the UL 0=11111cation Mark +Bearing the UL Listing Mark L.r�JI� U Ow tt ey iuttaeorrbwiorwewea, of rTmESTaP srsrE►rs +tween �. 20w C us E. TAMPER 5WITCHE5 Activation of the Tamper Switches shall Initiate the following functions: 1. Generate an Audible Supervisory Signal at the Fire Alarm Control Panel. 2. Indicate the location of the Tamper Switch by displaying, in English, the 5upermsory device and its location on the FACP alphanumeric display. 3. Transmit a supervisory signal to the designated third party Listed Central station by way of DACT. The maximum time period from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. F. TROUBLE Activation of the Trouble shall initiate the following functions: I. Generate an audible Trouble 51gnal at the fire Alarm control Panel. 2. Indicate the location of the Trouble by displaying, In English, the troubled device and its location on the FACP alphanumeric display. 3. Generate an audible Trouble Condition 51gnal at the fire Alarm control Panel. 4. Indicate the location of the Trouble Condition by displaying, In English, the device and Its location on the FACP alphanumeric display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. G. ELEVATOR LOBBY SMOKE DETECTORS (elevator lobby 4 machine room) Activation of the Smoke Detectors (elevator lobby 4 machine room only) shall Initiate the following functions of all the elevators associated with the corresponding Elevator Lobby or Machine Room: I. Generate an Audible alarm signal at the fire Alarm Control Panel and at the Remote Annunciator Panel, 2. Generate an audible alarm signal simultaneously on all areas of the budding by means of a Horns Devices. Generate a Visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horl5trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, In English, the alarmed device and Its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. H. 5MOKE DAMPERS CONTROL RELAY5 Activation of the Smoke Damper Control Relays shall initiate the following functions: I. lased on Smoke Control 5quence of Operation (by others), In the event of a fire alarm activation Control Relay will open or close the corresponding fire smoke damper. The maximum time rend from actuation of the Initiating device until Initiation of all related functions as listed above shall be ten seconds. ALL SIGNALING LINE CIRCUIT5 5HALL BE CLA55 B, STYLE 4 ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLA55 A. STYLE Z ALL INITIATING DEVICE CIRCUITS SHALL BE CLA55 Be STYLE A 5 System No. W -L -3065 F Ratings - 1 and 2 Hr ( See Item 1) T Rating - 0 Hr SECTION A -A 1. Wd Aria" -- The 1 or 2 fire -rated gypsum wallboard/stud wd assembly slid be constructed of fie materials and in the manner specified In fie individual 11300 or U400 Saks Nod and Partition Designs in the UL Fire Resistance Directory and dab inckide the fdbwkg construction features: A. Studs -- Wd framhg may r o -list of either wood ands or steel channel studs. Wood atuda to cxsrelet of tam 2 by 4 in. lumber spaced 16 h OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 in. OC. B. Ojpsum Bond' -- Nan 5/8 in. thick gypsun walDoard, wit► square or tapered edges. The gypsum wallboard type, thickness, number of layers, fostarer type and sliest orientation std be as specified in tM individual U300 or U400 Series Designs in the UL Fn Resistance Directory. Max dom of opening is 4 h The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. dam (or under) abet electrical metallic tubing 9* ded Awn cost Into onerrnbip ) with joint compound and installed flesh wb wall w ) rfaoon. WM n SC We 5 item pipe or BiT is treed, sina may extend up to 18 h beyond the wd sufatss. 1'r rincsrav SYSTEMS ,imay 2a, 2ow C ® US I. ELEVATOR RECALL A. Smoke Detectors In elevator lobbies, shaft and or elevator machine room shall: I. Initiate an alarm condition in the building for evacuation purposes. 2. initiate the recall of the elevator cars as follows in accordance with NFPA 72 (2002 edition), chapter 6.15.3. B. Phase I recall: Any elevator lobby smoke detector located on floors 2 and above and/or any smoke detector in the elevator machine or elevator shaft shall Initiate phase I recall which will bring the elevator car to the first floor and lock the doors In the open position. C. Phase II recall: Any elevator lobby smoke detector located on the first floor shall initiate recall which will bring the elevator car to the second floor and lock the doors in the open position. D. Elevator Warning Lights: Actuation of any elevator machine room smoke detector or elevator hoistway detector shall also Initiate the elevator warning lights to alert emergency personnel taht the elevators are not safe for use as required in NFPA 72 (2002 edition) chapter 6.15.3.9. E. 5hunt - Trip heat detectors: Heat detectors dedicated for elevator shunt shall be connected where required and activate a control shunt to disconnect the elevator power upon activation. The shunt power source shall be monitored by the fire alarm control panel as required in NFAP 72 (2002 edition) chapter 6.15.4.4. J. ELEVATOR SHUTDOWN 1. 6.15.4.1 • Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. 2. 6.15.4.2 If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 610 mm (2 ft) of each sprinkler head and be installed in accordance with the requirements of chapter 5. Alternatively, engineering methods, such as specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. 3. 6.15.4.3' If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time -delay switches or time -delay capability shall not be permitted. 4. 6.15.4.4' Control circuits to shut down elevator power shall be monntored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. 5. 6.15.4.5 The initiating devices described in 6.15.4.2 and 6.15.4.3 shall be monitored for integrity by the fire alarm control unit required In 6.15.3.1 and 6.15.3.2. K. FLOW BELL Activation of the Flow Bell shall Initiate the following functions: I . Flow Bell shall activate upon water flow. 2. Flow Bell shall sound as long as water Is flowing. g'jRE ALARM SYSTEM TO BV, 3. Flow Bell shall not be sdenceable from FACP. INSTALLED IN ACCORDANCE WITH NFPA72; 70;101- APPROVED D NRA 11 -DA.DE COUNTY FIRE DEPARTMENT BLDG. PERMIT FIRE ALARM_ FiRE SUPPRESSION WATER MAIN EXT. OAT hzzi By FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 1 Syystem No. W -L -3065 F Rafings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr 3. Cables -- Aggregate am- sectional area of cable in operwrg to be max 45 percent of the -' cross- sectional area of the opening. The mnulcr space between the cable bundle and the pedpWry of the opening to be min 1/4 in. to mox 3/4 h Cables to be rigidly supported on both skin of tM wall anemby. Arty combination of the following typo and can of copper conductor cables may be user: A. last 7/C No. 12 AMC with polyvinyl dioride (PVC) insuaation and locket. B. Max 25 pair Na 24 AWG; telephone cable vft PVC insulation and jodet. C. Type RG/U waial cable with potyethyles (PE) insulation and PVC jacket having a max outside diameter of A in. D. Multiple fiber optical tommiunication cable jociceted wM PVC and hawing a max OD of 518 in. E Through Paietrating Products' -- Max tare copper conductor No. 8 MG . Metal -Clad CCable +. AFC CABLE SYSTEMS INC F. Max VIC (with groundxor smada) No. 8 ANiG copper conductor cable with PVC insulation and jacketing. 4. F8, Void or Cavity Material$ -- Sealant Fill material applied within the annulus, flush with each and of Ire steel desve or wall surface. Fri material inetoled Wmw** on both sides of the wall. Adiamm bead oaf fill tMdmn of soda Is required material shall be applied aroundfd the perimeter pleriime ter of sl an both additional oft /Me�wall when sleeve extends beyond surface of wall. HiLTi CONSTRUCTION CHEMICALS, DN OF HiLTi INC - CP601S, CM or FS-One Sealant 'Bearing the UL Classification Mark PAP �+lAlduw kin mica d Neap �r d rhitrsTOP srsa°a ,iwhxrwr za crow C US STROBE OR Hom /Strobe SW A.F.F. OR 6' BELOW CEIUNG BOTTOM OF LENS) (WHICHEYVt is LOWER) PULL STATION 48" A.F.F. ADA HEIGHT REQUIREMENTS NO SCALE �b� n 2 � t«note 2t�D VYEL Dr w con a Da «. T H 2 R R R R m ®mom 1S FACP 1ST MARCH. RAM. �2 � TO SHUNT TRIP DEVICE m v. sH THIS DIAGRAM IS AN APPROXIMATION. PLEASE CONSULT YOUR ELECTRICAL ENGINEER FOR THE SPECIFIC REQUIREMENTS OF YOUR PROJECT. NOTES! 1. DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO PRIMARY FLOOR RELAY. 2. SMOKE DETECTOR ACTIVATION SHALL RECALL ELEVATOR TO SECONDARY FLOOR RELAY. * SMOKE DETECTOR ACTIVATION SHALL ACTIVATE ELEVATOR WARNING LIGHT. 4. HEAT DETECTOR SHALL BE LOCATED WITH IN 18' OF SPRINKLER AND SHALL ACTIVATE SHUNT TRIP BREAKER. ELEVATOR FIRE SAFETY STANDARD NOT TO SCAB 101.15TOMER APPROVAL I have reviewed thew plans and they conform to Accepted as is our requirements. I understand that ary modifications Accepted as rioted to these plans will be an additional service. Unaccepted Pnnt Name 5'gnatur+c Date O v o, inr N • OL !LJ Z lLJ V OC � LU - V m V 1 � � J � 1w E H � O 0 m N Z s,D e MT DESIGN, INC. CA #28637 _- -MI -SW 92nd ATe. °�: A213 Miami, n33176 1$)4otiEt (909 J1y77 -1845 -4--d ..... RGE F1A •65527 NfigIIt$65*Ahoo.c m,,r = J(jt �- c7 - - - - O v o, inr N • OL !LJ Z lLJ V OC � LU - V m V 1 � � J � 1w E H � O 0 m N Z s,D e -4--d - - - F U CO C/0 M 1:13 cr I ct � ;-4 ow O 0 O v o, inr N • OL !LJ Z lLJ V OC � LU - V m V 1 � � J � 1w E H � O 0 m N Z s,D e E to Z N Sheet Number FA -03 of 04 ° a 1-{*- -; E to Z N Sheet Number FA -03 of 04