14-1041-006SCOPE OF WORK SEQUENCE OF OPERATION ABOVE ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL INSTALLATION OF A NEW CELLULAR DIGITAL ALARM COMMUNICATOR TRANSMITTER (CDAC) TO GO INTO ALARM CONDITION, DISPLAY THE DEVICE OR ZONE ON THE TO THE EXISTING FIRE ALARM SYSTEM FOR TRANSMITTING FIRE ALARM SIGNALS FRONT OF PANEL AND REMOTE ANNUNCIATOR, ACTIVATE ALL NOTIFICATION PWR DEVICES THROUGHOUT THE BUILDING, TRANSMIT SIGNAL TO UL LISTED EXISTING FIRE ALARM SYSTEM INSTALLATION IS A LOCAL SYSTEM AND WILL BE CENTRAL STATION. AND ACTIVATE OR OPERATE ANY AUX. RELAYS OR LISTED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM FUNCTIONS AS NOTED ON FLOOR PLANS AND RISER DIAGRAM. BE PLACED SUCH THAT ANY TROUBLE SIGNAL SHALL BE INDICATED AT THE FIRE ALARM CONTROL LESS THAN 80" PANEL, REMOTE ANNUNCIATOR AND UL LISTED CENTRAL STATION. GENERAL NOTES ANY ALARM SIGNAL SHALL BE INDICATED AT THE FIRE ALARM CONTROL 6"._BEL.OW THE_._CEILING WHICHEVER IS PANEL, REMOTE ANNUNCIATOR AND UL LISTED CENTRAL STATION. 1. THIS FIRE ALARM SYSTEM IS PROVIDED UNDER NFPA 101 2009ed CHAPTER 17 ANY SUPERVISORY SIGNAL SHALL BE INDICATED AT THE FIRE ALARM CONTROL FOR DAY -CARE OCCUPANCIES AND UNDER FLORIDA BUILDING CODE PANEL, REMOTE ANNUNCIATOR AND UL LISTED CENTRAL STATION. 2. SYSTEM IS A POWER LIMITED FIRE ALARM SYSTEM. UPON ACTIVATION OF ANY MANUAL STATION THE FOLLOWING SHALL OCCUR: 3. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS B, STYLE 4. 1. THE FACP SHALL DISPLAY THE DEVICE OR ZONE IN ALARM. 4. NOTIFICATION APPLIANCE CIRCUIT SHALL BE CLASS B, STYLE Y. 2. THE FACP SHALL ACTIVATE ALL NOTIFICATION DEVICES THROUGHT THE 5. BUILDING FIRE ALARM SYSTEM IS CLASSIFIED AS A CENTRAL STATION SERVICE BUILDING. FIRE ALARM SYSTEM AND IS PROVIDED WITH 24 HOURS OF SECONDARY UPON ACTIVATION OF ANY SMOKE DETECTOR THE FOLLOWING SHALL OCCUR: NON -ALARM POWER AND 5 MIN. OF SECONDARY ALARM POWER AS PER 0 NFPA 72 (2007ed) 1. THE FACP SHALL DISPLAY THE DEVICE OR ZONE IN ALARM. FACP AC POWER LOSS 2. THE FACP SHALL ACTIVATE ALL NOTIFICATION DEVICES THROUGHT THE 6. BUILDING IS NOT SPRINKLERED. BUILDING. 7. ALL EQUIPMENT SHALL BE UL LISTED, COMPATIBLE AND LISTED UPON ACTIVATION OF ANY DUCT SMOKE DET. THE FOLLOWING SHALL OCCUR: FOR USE IN FIRE ALARM. 1. THE FACP SHALL DISPLAY THE DEVICE OR ZONE IN ALARM. 8. INSTALLATION SHALL COMPLY WITH FLORIDA BUILDING CODE (2010ed) 2. THE FACP SHALL SHUT DOWN RELATED HVAC EQUIPMENT FLORIDA FIRE PREVENTION CODE (2010ed) AND ALL CODES ADOPTED BY THE LOCAL 3. THE FACP SHALL GO INTO SUPERVISORY CONDITION. AHJ. 0 9. INSTALLATION SHALL COMPLY WITH THE ADOPTED EDITION OF NFPA 72 (2007ed), UPON ACTIVATION OF ANY HEAT DETECTOR THE FOLLOWING SHALL OCCUR: NFPA1 (2009ed), NFPA 101 (2009ed), AND NFPA 70 (2008ed). 1. THE FACP SHALL DISPLAY THE DEVICE OR ZONE IN ALARM. 10. INSTALLATION SHALL COMPLY WITH 2010 FLORIDA BUILDING CODE: ACCESSIBILITY 2. THE FACP SHALL ACTIVATE ALL NOTIFICATION DEVICES THROUGHT THE 11. CONDUITS SHALL BE 1/2" MINIMUM WITH A MAXIMUM FILL OF 40 %, BUILDING. AND COMPLY WITH NEC. UPON ANY AC POWER LOST OR BATTERY FAILURE THE FOLLOWING SHALL 12. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS. OCCUR: 13. MINIMUM WIRE SIZE SHALL BE #18 AWG COPPER UNLESS NOTED 1. THE FACP SHALL DISPLAY AC OR BATTERY FAILURE TROUBLE. OTHERWISE. 14. CONDUCTORS SHALL HAVE MINIMUM RATING OF 300V AND SHALL BE UPON ANY OPEN CIRCUIT, GROUND FAULT OR SHORT CIRCUIT IN ANY OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS. NOTIFICATION APPLIANCE CIRCUIT THE FOLLOWING SHALL OCCUR: TYPE AS SPECIFIED ON PLANS. 1. THE FACP SHALL DISPLAY THE CIRCUIT OR NAC IN TROUBLE. 15. ALL DEVICES OR UNITS SHALL BE INSTALLED USING APPROVED UPON ANY OPEN CIRCUIT OR GROUND FAULT IN ANY INITIATING DEVICE MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE NATIONAL CIRCUIT THE FOLLOWING SHALL OCCUR: ELECTRIC CODE NFPA 70 (2008ed) ARTICLE #760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAL WIRING ORDINANCES 1. THE FACP SHALL DISPLAY THE CIRCUIT OR ZONE IN TROUBLE. 16. CEILING HEIGHT LESS THAN 10' (EXCEPT WHERE SPECIFIED) FIRE ALARM PANEL SHALL TRANSMIT ALL ALARM, TROUBLE AND SUPERVISORY 17. ALL OUTDOOR FIRE ALARM DEVICES TO BE WEATHERPROOF TYPE. SIGNALS TO THE UL LISTED CENTRAL STATION 18. OFF -SITE MONITORING WILL BE PROVIDED 19. ALL SMOKE DETECTORS MOUNTED MORE THAN 3' AWAY FROM A/C DIFFUSERS. 20. INTERCONNECTED FIRE ALARM CONTROL PANEL, NAC POWER SUPPLY, AND DEVICES SHALL BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM AND MONITORED FOR INTEGRITY PER NFPA 72 (2007ed). 21. ALL HORN /STROBES SHALL BE UL LISTED UNDER STANDARD 1971 (SIGNALING DEVICES FOR THE HEARING- IMPAIRED) 22. VISUAL NOTIFICATION DEVICES SHALL COMPLY WITH THE LATEST EDITION OF ADA GUIDELINES, BE SYNCHRONIZED WHEN REQUIERED, CLEAR BUILDING IS NOT SPRINKLERED XENON TYPE, AND WITH MIN. INTENSITY OF 75 CANDELAS UNLESS NOTED OTHERWISE ON PLANS 23. AUDIBILITY SHALL BE AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND OR 5 dB ABOVE THE MAX. SOUND LEVEL, WHICHEVER IS GREATER IN THE OCCUPIABLE AREA. PWR 2 #12 AWG, THWN & 1 #12 (G) IN 1/2 "C SMOKE DETECTOR 24. AUDIBLE /VISIBLE AND VISIBLE DEVICES SHALL BE PLACED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80" ABOVE THE HIGHEST FLOOR "-- LEVEL- WITHIN THE SDACE..rOR-- 6"._BEL.OW THE_._CEILING WHICHEVER IS LOWER AS PER ADOPTED EDITIONS OF ADA GUIDELINES, FLORIDA BUILDING CODE AND NFPA 72. 25. WALL - MOUNTED AUDIBLE NOTIFICATION APPLIANCES SHALL HAVE THEIR TOPS ABOVE THE FINISHED FLOOR AT HEIGHTS OF NOT LESS THAN 90" AND BELOW THE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6" AS PER ADOPTED EDITIONS OF NFPA 72 (2007ed). 26. THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL BE AT 48 INCHES ABOVE FLOOR LEVEL AND COMPLY WITH NFPA 72 AND ADA REQUIREMENTS. ASIF� o�j-� C� \�,�jUS Gesufi� b} Undawr tars Laba�mr a s, tc, m UL 1479 and CANNLGS1115 System No. C-AJ -1226 F Rating - 3 Hr a T Rating -0 Hr v L Rating At Ambient -Less Than 7 CFM/Sq Ft L Rating At 400 F - 4 CFMISq Ft Lam- A SECTION A-A 1. Floor or Wall Assembly - Min 4 -1/2 in. thick reinforced lightweight or normal weight (100.150 pd) concrete. Wail may also be constructed of any UL Classified Concrete Blocks'. Max diam of opening is 32 in. 1 Metallic Sleeve - (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor orwall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wail. 2A. Sheet Metal Sleeve - (Optional) Max 6 in. diam, min 26 ga gaty steel provided with a 26 ga galv steel square flange spotwelded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 28. Sheet Metal Sleeve - (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga gaiv steel square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 3. Through - Penetrant -One metallic pipe, tube or conduit to be installed either eoncentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to max 1 -7/8 in. Penetrant maybe installed with continuous point contact. Penetrant to be rigidly supported on both sides of floororwail assembly. The following types and sizes of metallic penetrants may be used: A. Steel Pipe - Nom 30 in. diam (or smaller} Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Conduit - Nom 6 in. diam (or smaller) steel conduit F. Conduit- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT). 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 4 in. thickness of min 4 pd mineral wool bait insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be applied at the concrete or sleevel pipe penetrant interface on the trop surface of floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -FS -One Sealant 'Bearing the UL Cla 6ftton Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hilt! Firestop Systems June 27,2007 P OR- C) �G t�,� t1• JO �4 MANUAL PULL STATION 0 0 0 A SLC 2 #18 FPLP P PWR 2 #12 AWG, THWN & 1 #12 (G) IN 1/2 "C SMOKE DETECTOR 0 0 0 0 e s � HEAT DETECTOR 0 0 0 0 SMOKE DUCT DETECTOR 0 0 0 0 0 0 FACP AC POWER LOSS 0 0 0 0 FACP LOW BATTERY 0 0 0 0 CKT /CABLING GROUND 0 0 0 AUDIBLE DEVICES CKT. VISUAL DEVICES CKT. SEQUENCE OF OPERATION MATRIX BATTERY CALCULATION BATTERY CALCULATION FOR EXISTING FIRE ALARM SYSTEM HAS NOT BEEN MODIFIED. NO NEW DEVICE, APPLIANCE AND/OR LOAD OF ANY TYPE THAT DRAW CURRENT FROM THE FIRE ALARM CONTROL UNIT HAS BEEN ADDED TO THE SYSTEM. NEW EXTERNAL DIGITAL ALARM COMMUNICATOR TRANSMITTER WILL INTERFACE WITH EXISTING FACP TO SUPERVISE THE STATUS OF BUILT -IN DRY CONTACT RELAYS IN THE FACP FOR FIRE ALARM SYSTEM SIGNALS. THIS INTERFACE WILL NOT DRAW CURRENT FROM EXISTING FACP. FIRE ALARM LEGEND CDAC NEW CELLULAR DIGITAL ALARM COMMUNICATOR TRANSMITTER (CDAC) 8 DSC MODEL: 3G3070 -CF FACP EXISTING FIRE ALARM CONTROL PANEL 0 NAPCO MODEL: FIRE ALERT 6000 SERIES E - DENOTES EXISTING DEVICE N - DENOTES NEW DEVICE SCOPE OF WORK INSTALLATION OF A NEW CELLULAR DIGITAL ALARM COMMUNICATOR TRANSMITTER (CDAC) TO THE EXISTING FIRE ALARM SYSTEM FOR TRANSMITTING FIRE ALARM SIGNALS EXISTING FIRE ALARM SYSTEM INSTALLATION IS A LOCAL SYSTEM AND WILL BE LISTED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM THE METHOD OF COMMUNICATION TO THE MONITORING STATION IS BY CELLULAR DIGITAL ALARM COMMUNICATOR TRANSMITTER (CDAC) FIRE ALARM ROOM TO BE MECHANICALLY VENTILATED. THE LOCATION OF FIRE ALARM CONTROL UNITS COMPLY WITH THE REQUIREMENTS OF NFPA72 (2007ed) ARTICLE 4.4.4 PERFORMANCE AND LIMITATIONS ACCESS AND WORKING SPACE IS PROVIDED FOR THE FIRE ALARM CONTROL UNITS IN COMPLIANCE WITH THE NEC (2008ed) ARTICLE 110.26 MAX. MOUNTING HEIGHT FOR NEW COMMUNICATOR IS 6' -0' WIRE LEGEND CHART TYPE CKT. CONDUCTOR /DESCRIPTION A SLC 2 #18 FPLP P PWR 2 #12 AWG, THWN & 1 #12 (G) IN 1/2 "C LOCATION OF EXISTING FACP & NEW CDAC SCOPE OF WORK AREA STORAGE BATH BATH TOR CLASSROOM CLASSROOM KITCHEN CLASSROOM BATH BAT STORAGE STORAGE STORAGE CLASSROOM OFFICE DAC BATH ACP VESTIBULE ATH OFFICE ELECT. OFFICE ROOM STORAGE OFFICE _j FIRE ALARM SITE PLAN, SCALE N.T.S. S E _ TO EXISTING IDC & NAC Z1 -1 (NOT MODIFIED UNDER THIS SCOPE OF WORK) NEW CDAC 3A EXISTING FACP DSC FIRE ALARM PANEL 3G3070 -CF NAPCO FIRE ALERT 6000 C2 N Cl SERIES E 20A RATED DEDICATED 120V BRANCH CIRCUIT PNL. E -1 P FIRE ALARM SYSTEM RISER D IAG RAM (PARTIAL CLASSROOM 11 KITCHEN STORAGE /_ NEW CDAC CDAC %- EXISTING SMOKE DETECTOR OFFICE N (3)E 5C1 ACP Z1 -1 E VESTIBULE OFFICE EXISTING FACP 1 Mink ,• 1 1 SCALE 1/8" = 1' -0" L � LW ,'t1iiAF;rti OE CGif!F�r� -}r> �itZ . IDEPARTME rL rlir FIRE SUF PRE3Z ON " �! 0,!, ALARM SHALL BE A CENTRAL 7TATION SMVICC'E. A CERTIFICATE t;;R PLACARD SHALL BE P©ISTSD AT FINAL INSPECTION, AS PER NFPA 72 !'IRE ALARM SYSTEM TO BE IN,*-,) FALIL, 911,,4 r,s CORDANCE WITH NRA 72; 70; lot 11 * No. 53858 �W 4 t STAte OF f� . P to I ii s rss+e 7 t0 1` IA r r � N 1A H 06 m110 Z ...-% ''W o0 %00 NOR WE X Q W I- �J0 H Q4 4r IC C4 " W , CO) y Zr �a IxZ00 W W cc W q � G 0 oc W C�WVZ 0 T W W u�.5W� w rti A ry 100 ry K. 1 -1 � 75E Q = UO� 6,- Q G DRAWN RV CHECKED CJ DATE 04 -03 -14 SCALE AS SHOWN JOB NO. 040314 SHEET PA -1 OF 1 SHEETS 0 i s e s � DRAWN RV CHECKED CJ DATE 04 -03 -14 SCALE AS SHOWN JOB NO. 040314 SHEET PA -1 OF 1 SHEETS 0 i