Loading...
13-1329R-004PANEL MDP LOCATION: ELECTRICAL ROOM VOLTAGE: 20SY /120V 30 4W MIN. AIC RATING: 22K AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND is NEUTRAL BUS SERVICE ENTRANCE RATED TYPE: SQUARE -D I -LINE MAINS: 1200A ❑ MLO N MCD MOUNTING: SURFACE FED FROM: SERVICE ENTRANCE XFMR LUGS: ❑ SUB-FEED ❑ FEED -THRU ENCLOSURE: NEMA 1 ENCLOSURE: NEMA 1 CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION Cn W Z BRANCH CIRCUIT BKR LOAD KVA PHASE 0 LOAD KVA BKR BRANCH CIRCUIT o z CIRCUIT DESCRIPTION ~ 1 / INEUTIGND COND COND 0 NEUT GND COND 1 1 PANEL L1 12 - - - - 225/3 12.74 A 28.08.400/3 8 - - - - PANEL SL5 PANEL LR 2 3 - 12 - - -- - - 12.74 B 28.08 - - - - - - - 4 5 - 12 - - - - 0.36 12.74 C 28.08 - - - -- - - - 6 7 PANEL L2 12 - - - -- 400/3 23.59 A 10.28 125/3 - - - - PANEL SL7 PANEL EL1 VIA ATS -E s - - 12 -- - - - - 23.59 B 10.28 - - - - - - - 10 11 - 12 - - - - - 23.59 C 10.28 - - - - - EMERGENCY LIGHTING - ELEVATOR PIT - 12 13 PANEL L3 12 - - - - 225/3 13.48 A 13.58 150/3 - - - - DWDP PANEL SL1 VIA ATS -S 14 15 - 12 - - - - - 13.48 B 13.58 - - - - - - 16 16 171- C 12 - - - - - 13.48 C 13.5E - - - - - - 1s 1s 19 1 PANEL L5 12 - - - 1 - 125/3 8.77 A 8.77 125/3 - - - - SPACE ONLY PANEL L7 20 21 - 12 - - - - - 8.77 B 8.77 - - - - - ISPACE ONLY - 22 23 - - - - - - - 8.77 C 8.77 - - - - - SPACE ONLY - 24 25 - - - - - - - - A - - - - - - SPACE ONLY - 26 27 - - - - - - - - B - - - - - - SPACE ONLY - 28 29 - - - - - - - - C - - - - - - SPACE ONLY 30 30 31 A - - - -- - - - A - - - - - - SPACE ONLY - 32 33 B - - - - - - - B - - - - - - SPACE ONLY - 34 35 - - - - - - - - C - - - - - - SPACE ONLY - 36 37 - - - - - - - -- A - 30/3 10 10 10 3/4*1 SPACE ONLY SURGE PROTECTIVE DEVICE (SPD) 39 39 - - - - - - - - B - - 10 - - - SPACE ONLY 40 40 41 - - - - - - - »- C - - 10 - - - SPACE ONLY - 42 EQUIPMENT SERVED CONN. LOAD L.F. LF. D.F. DEMAND LOAD PANELS 357.87 KVA 3.68 KVA 100% 357.87 KVA 14 EQUIPMENT 9.00 KVA 4.20 KVA 100% 9.00 KVA TOTAL DEMAND LOAD: 32.87 KVA LIGHTING 1.48 KVA 125% 1.85 KVA A _4 NOTES: NOTES: TOTAL DEMAND LOAD: 357.87 KVA TOTAL DEMAND LOAD: 8.80 KVA TOTAL DEMAND AMPS: 994.08 AMPS PANEL SL1 LOCATION: 1 ST FLOOR ELECTRICAL ROOM VOLTAGE: 208Y /12OV 30 4W MIN. AIC RATING: 22K AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND & NEUTRAL BUS TYPE: SQUARE -D NQOD MAINS 150A El MLO ®MCB MOUNTING: SURFACE FED FROM: MDP VIA ATS LUGS: ❑ SUB -FEED ❑ FEED -THRU ❑ FEED -THRU ENCLOSURE: NEMA 1 x U CIRCUIT DESCRIPTION N k`' z BRANCH CIRCUIT BKR LOAD KVA PHASE 0 LOAD KVA BKR BRANCH CIRCUIT W z CIRCUIT DESCRIPTION Y I NEUT GND COND / NEUT GND COND COND 1 TTB -- 1ST FLOOR FATC -3 12 12 12 1/2" 20/1 0.36 A 2.74 40/3 8 8 10 1" 1/2" PANEL SL5 2 3 TTB - 1ST FLOOR 1 FATC -4 12 12 12 1 /2" 20/1 0.36 B 2.74 - 8 - - - 11/2*1 - 4 5 TI1 - 1 ST FLOOR FATC -5 12 12 12 1/2' 20/1 0.36 C 2.74 - 8 - - - 1/2" - 6 7 GENERATOR BLOCK HEATER FATC -6 12 12 12 3/4" 20/2 0.50 A 8.78 125/3 - - - - 1/2* PANEL SL7 s s - FATC -7 12 - - - - 0.50 B 8.78 - - - - - 1/2" - 10 11 GENERATOR BATTERY CHARGER A SPARE 12 12 12 1/2" 1/2" 20/1 0.50 1 C 8.78 - - - - - 1/2" EMERGENCY LIGHTING - ELEVATOR PIT 12 13 EMERGENCY CALL SYSTEM 1 SAFETY RADIO - 3RD FLOOR 12 12 12 1/2" 1/2" 20/1 0.50 A 2.64 40/3 a a 10 1" - DWDP 14 15 LIGHTING - 2ND FLOOR CORRIDOR SAFETY RADIO - 4TH FLOOR 12 12 12 1/2" 1/2" 20/1 0.22 B 2.64 - 8 - - - 12 - 16 17 LIGHTING - 2ND FLOOR GAMEROOM C 12 12 12 1/2" 2 20/1 0.92 C 2.64 - 8 - - - 12 - 1s is LIGHTING - 2ND FLOOR LAUNDRY A 12 12 12 1/2" 12 20/1 0.34 1 A - - - - - - 12 SPACE ONLY 20 21 LIGHTING - 1ST FLOOR CORRIDOR B 12 12 12 1/2" 12 20/1 0.20 B - - - - - - - ISPACE ONLY 22 23 SPARE C - - - - 20/1 - C - - - - - - 12 SPACE ONLY 24 25 SPARE A - - - - 20/1 - A - - - - - - - SPACE ONLY 268 27 SPARE B - - 12 - 20/1 - B -- - - - - - 12 SPACE ONLY 28 29 SPACE ONLY C - - - - - - C - 30 - - - - 12 SPACE ONLY 30 31 SPACE ONLY A - -- - - - - A - - - - - - 12 SPACE ONLY 32 33 SPACE ONLY B - - - - - - B - - - - - - - SPACE ONLY 34 35 SPACE ONLY - - - - - - - C - - - - - - 2.93 SPACE ONLY 36 37 SPACE ONLY - - - - - - - A - - - - - - 2.93 SPACE ONLY 38 39 SPACE ONLY - - - - - - - B - - - - - - 2.93 SPACE ONLY 40 41 SPACE ONLY - - - - - - - C - - - - - - - SPACE ONLY 42 EQUIPMENT SERVED CONN. LOAD EQUIPMENT L.F. D.F. IDEMAND LOAD 6.58 KVA PANELS 34.56 KVA 3.68 KVA 100% 34.56 KVA 14 EQUIPMENT 9.00 KVA 4.20 KVA 100% 9.00 KVA TOTAL DEMAND LOAD: 32.87 KVA LIGHTING 1.48 KVA 125% 1.85 KVA A _4 NOTES: NOTES: TOTAL DEMAND LOAD: 45.41 KVA TOTAL DEMAND LOAD: 8.80 KVA TOTAL DEMAND AMPS: 126.14 AMPS /3\ 14 PANEL EL1 LOCATION: 5TH FLOOR STORAGE VOLTAGE: 20aY /120V 30 4W MIN. AIC RATING: 22K AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND & NEUTRAL BUS TYPE: SQUARE -D NQOD MAINS: 125A ❑ MLO ® MCD MOUNTING: SURFACE FED FROM: MDR VIA ATS LUGS: ❑ SUB -FEED ❑ FEED -THRU ❑ FEED -THRU ENCLOSURE NEMA 1 �- x U CIRCUIT DESCRIPTION Cn �' z BRANCH CIRCUIT BKR LOAD KVA PHASE 4 LOAD KVA BKR BRANCH CIRCUIT Cn z CIRCUIT DESCRIPTION r / NEU GND COND 0 NEUT GND COND COND 1 EMERGENCY LIGHTING - STAIRWELL FATC -3 12 12 12 1/2" 20/1 0.97 A 0.58 20/1 12 12 12 1/2" 1/2" EMERGENCY GARAGE LIGHTING - 1ST 2 3 EMERGENCY LIGHTING - STAIRWELL 1 FATC -4 12 12 12 1/2" 20/1 0.97 B 1 0.33 20/1 12 12 12 1/2" 11/2*1 EMERGENCY GARAGE LIGHTING - ENTRY 4 5 EMERGENCY LIGHTING - STAIRWELL FATC -5 12 12 12 1/2" 20/1 1.30 C 0.35 20/1 12 12 12 1/2" 1/2" EMERGENCY GARAGE LIGHTING - 2A 6 7 EMERGENCY LIGHTING - STAIRWELL FATC -6 12 12 12 1/2" 20/1 1.19 A 0.33 20/1 12 12 12 1/2 1/2* 1EMERGENCY LIGHTING - 2ND FLOOR s s 1EMERGENCY LIGHTING - STAIRWELL FATC -7 12 ' 12 12 1/2" 20/1 0.65 B 0.45 20/1 12 12 12 1/2" 1/2" EMERGENCY GARAGE LIGHTING - 20 10 11 EMERGENCY LIGHTING - STAIRWELL SPARE 12 12 12 1/2" 20/1 0.65 C 0.40 20/1 12 12 12 1/2" 1/2" EMERGENCY LIGHTING - ELEVATOR PIT 12 13 EMERGENCY LIGHTING - 1ST FLOOR SAFETY RADIO - 3RD FLOOR 12 12 12 1/2" 20/1 0.47 A - 1 20/1 - 12 12 12 - 1/2 ", - EMERGENCY LIGHTING - COURTYARD 14 15 EMERGENCY LIGHTING - 1ST FLOOR SAFETY RADIO - 4TH FLOOR 12 12 12 1/2" 20/1 1.24 B 0.10 168 17 EMERGENCY LIGHTING - EXTERIOR - 12 12 12 1/2" 20/1 0.59 C .3 Z0/1 1 2 1 0.58 C E E C L H ­5 AW is is EMERGENCY LIGHTING - 2ND FLOOR - 12 12 12 1/2" 20/1 0.50 A 0.35 20/1 12 12 12 1/2" A EMERGENCY LIGHTING - 5TH FL PATIO 20 21 EMERGENCY LIGHTING - 2ND FLOOR - 12 12 12 1/2" 20 20/1 0.52 B 0.20 20/1 12 12 12 1/2" B SAFETY RADIO - 1ST FLOOR 22 23 SPARE - - - - - 20/1 - C 0.20 20/1 12 12 12 1/2" C SAFETY RADIO - 2ND FLOOR 24 25 DIESEL FIRE PUMP CONTROLLER - 12 12 12 1/2" 24 20/1 1.00 A 0.90 20/3 12 12 12 /4" A FIRE PUMP JOCKEY PUMP (2HP) 26 27 SPARE - - - - - 20/1 - B 0.90 - 12 - - - B - 28 29 FIRE PUMP ROOM RECEPTACLE - 12 12 12 1/2" 28 20/1 0.18 C 0.90 - 12 - - - C - 30 31 FIRE PUMP HEATER - 12 12 12 1/2" 30 20/1 1.20 A 0.11 1 20/1 12 1 12 - - A G - - 33 FRCP - 1 ST FLOOR - 12 12 12 1/2', 32 20/1 0.50 B 12 1/2" - EMERGENCY LIGHTING - TERRACE 34 35 SPACE ONLY - - - - - - - C - - - - - - - 5 A L 36 37 PANEL EL5 - 6 6 10 .25 60/3 2.93 A - - - - - - - SPACE ONLY 38 39 - - 6 - - - - 2.93 B - - j - - - - - SPACE ONLY 40 41 B 16 - - - - - 2.93 C - - I - - - - - SPACE ONLY 42 EQUIPMENT SERVED CONN. LOAD -- LF. D.F. DEMAND LOAD - LIGHTING 14.00 KVA EQUIPMENT 125% 17.50 KVA LOAD EQUIPMENT 6.58 KVA D.F. 100% 6.58 KVA PANEL EL5 8.79 KVA 3.68 KVA 100% 8.79 KVA 14 NOTES: 2.26 KVA 4.20 KVA 125% 2.83 KVA TOTAL DEMAND LOAD: 32.87 KVA TOTAL DEMAND AMPS: 91.31 AMPS PANEL SL5 LOCATION: 5TH FLOOR STORAGE VOLTAGE: 208Y/120V 30 4W MIN. AIC RATING: 1 O AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND & NEUTRAL BUS TYPE: SQUARE -D NQOD MAINS: 125A ® MLO ❑ MCB MOUNTING: SURFACE FED FROM: SL1 LUGS: ❑ SUB -FEED ❑ FEED -THRU ❑ FEED -THRU ENCLOSURE: NEMA 1 ENCLOSURE: NEMA 1 CIRCUIT DESCRIPTION o z BRANCH CIRCUIT BKR LOAD KVA PHASE LOAD KVA BKR BRANCH CIRCUIT 'n W z CIRCUIT DESCRIPTION x 0 NEUT GND COND 0 NEUT GND COND COND 1 RECEPTACLES - 5TH k 6TH LOUNGE FATC -3 12 12 12 1/2" 20/1 0.36 A 0.36 20/1 12 12 12 1/2" 1/2" RECEPTACLES - 3RD FLOOR LOUNGE 2 3 RECEPTACLES - 5TH k 6TH LOUNGE 1 FATC -4 12 12 12 1/2" 20/1 0.36 B 0.36 20/1 12 12 12 1/2" 11/2*1 TTD - 3RD FLOOR 4 5 TTB - 5TH FLOOR FATC -5 12 12 12 1/2" 20/1 0.36 C 0.36 20/1 12 12 12 1/2" 1/2" TTB - 3RD FLOOR 6 7 TTB - 5TH FLOOR FATC -6 12 12 12 1/2" 20/1 0.36 A 0.36 20/1 '12 12 12 1/2" 1/2* RECEPTACLES - 4TH FLOOR LOUNGE s s TI1 - 6TH FLOOR FATC -7 12 12 12 1/2" 20/1 0.36 B 0.36 20/1 12 1 12 12 1/2"1 1/2" IRECEPTACLES - 4TH FLOOR LOUNGE 10 11 TTB - 6TH FLOOR SPARE 12 12 12 112" 20/1 0.36 1 C 0.36 20/1 12 12 12 1/2" 1/2" TTB - 4TH FLOOR 12 13 RECEPTACLES - 5TH k 6TH LOUNGE SAFETY RADIO - 3RD FLOOR 12 12 12 1/2" 20/1 0.36 A 0.36 20/1 12 12 12 1/2" - TTB - 4TH FLOOR 14 15 RECEPTACLES - 5TH k 6TH LOUNGE SAFETY RADIO - 4TH FLOOR 12 12 12 1/2" 20/1 0.36 B - 20/1 - - - - - SPARE 16 17 LIGHTING - 3RD FLOOR SAFETY RADIO - 5TH FLOOR 12 12 12 1/2" 12 20/1 0.58 C - 20/1 - - - - -- SPARE 1s 19 LIGHTING - 4TH FLOOR SAFETY RADIO - 6TH FLOOR 12 12 12 1/2" 12 1/2" 20/1 0.42 A - 20/1 - - - - - SPARE 20 21 LIGHTING - 5TH FLOOR SAFETY RADIO - 7TH FLOOR 12 12 12 1/2" 12 1/2" 20/1 0.42 B - 20/1 - - - - - ISPAR E 22 23 LIGHTING - 6TH FLOOR FIRE COMM ROOM - ROOF 12 12 12 1/2" 12 1/2" 20/1 0.42 C - 20/1 - - - I - SPARE 24 25 LIGHTING - 7TH FLOOR SPACE ONLY 12 12 12 1/2" - 20/1 0.42 A - 20/1 - - - - - SPARE 26 27 SPACE ONLY SPACE ONLY - - - - - - B - 20/1 - - - - - SPARE 28 2s SPACE ONLY SPACE ONLY - - - - - - C - 20/1 - - - - - SPARE 30 31 SPACE ONLY SPACE ONLY - - - - - - A - - - - - ISPACE ONLY 32 33 SPACE ONLY SPACE ONLY - - - - - - B - - - •- - - ISPACE ONLY 34 35 SPACE ONLY SPACE ONLY - - - - - - C - - - - - - - SPACE ONLY 36 37 SPACE ONLY SPACE ONLY - - - - - - A - - - -- - - - SPACE ONLY 38 39 SPACE ONLY SPACE ONLY - - - - - -- B - - - - - -- - SPACE ONLY 40 41 SPACE ONLY SPACE ONLY - - - - - - C - - -- - - - - SPACE ONLY 42 EQUIPMENT SERVED CONN. LOAD LOAD LF. D.F. DEMAND LOAD DEMAND LOAD RECEPTACLES k EQUIPMENT 5.40 KVA 3.68 KVA 100% 5.40 KVA 4.60 KVA LIGHTING 2.26 KVA 4.20 KVA 125% 2.83 KVA 4.20 KVA 14 NOTES: NOTES: TOTAL DEMAND LOAD: 8.23 KVA TOTAL DEMAND LOAD: 8.80 KVA TOTAL DEMAND AMPS: 22.86 AMPS /3\ / 11� /14\ i3\ '4\ n2l PANEL EL5 LOCATION: 5TH FLOOR STORAGE VOLTAGE: 20BY /120V 30 4W MIN. AIC RATING: 1 O AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND & NEUTRAL BUS TYPE: SQUARE -D NQOD MAINS 125A 19 MLO ❑MCB MOUNTING: SURFACE FED FROM. EL1 LUGS: ❑ SUB-FEED ❑ FEED -THRU ENCLOSURE: NEMA 1 ENCLOSURE: NEMA 1 F- � CIRCUIT DESCRIPTION � Z BRANCH CIRC IT U BKR LOAD KVA PHASE 0 LOAD KVA BKR BRANCH CIRCUIT c z CIRCUIT DESCRIPTION � f NEUT GND COND 0 NEUT GND COND 1 1 FATC -3 12 12 1 12 1 12 1/2" 20/1 0.50 A 0.58 20/1 12 12 12 1/2" ELEVATOR 1 CONTROLLER EMERGENCY LIGHTING - 3RD FLOOR 2 3 1 FATC -4 12 12 12 12 1/2" 20/1 0.50 1 B 0.42 20/1 12 12 12 11/2*1 - EMERGENCY LIGHTING - 4TH FLOOR 4 5 FATC -5 12 12 12 12 1/2" 20/1 0.50 C 0.42 20/1 12 12 12 1/2" - EMERGENCY LIGHTING - 5TH FLOOR 6 7 FATC -6 1 12 12 12 12 11/2'1 20/1 20/1 0.50 A 0.42 20/1 12 12 12 1/2* 1 ELEVATOR 2 CONTROLLER JEMERGENCY LIGHTING - 6TH FLOOR s s FATC -7 12 12 12 12 1/2" 20/1 0.50 B 0.42 20/1 12 12 12 1/2" - 1EMERGENCY LIGHTING - 7TH FLOOR 10 11 SPARE 12 - - - - 20/1 - C 0.42 20/1 12 12 12 1/2" JEMERGENCY LIGHTING - 8TH FLOOR 12 SPARE SAFETY RADIO - 3RD FLOOR - 12 12 12 1/2" 20/1 0.20 A 0.50 20/1 - - - - ELEVATOR ROOM RECEPTACLE ELEVATOR CAD LIGHTS 14 r19 SAFETY RADIO - 4TH FLOOR - 12 12 12 1/2" 20/1 0.20 B 0.50 20/1 - - - - SPARE ELEVATOR CAB LIGHTS 168 17 SAFETY RADIO - 5TH FLOOR - 12 12 12 1/2" 20/1 0.20 C - 20/1 - - - -- SPARE SPARE 1s SAFETY RADIO - 6TH FLOOR - 12 12 12 1/2" 20/1 20/1 0.20 A - - - - - - SPARE SPACE ONLY 20 21 SAFETY RADIO - 7TH FLOOR - 12 12 12 1/2" - 20/1 0.20 1 B - - - - - - ISPACE ONLY 22 23 FIRE COMM ROOM - ROOF - 12 12 12 1/2" - 20/1 0.18 C - - - - ISPACE ONLY 24 25 SPACE ONLY - - - - - - - A - - - - - - SPACE ONLY SPACE ONLY 26 27 SPACE ONLY - - - - - - - B - - - - - - SPACE ONLY SPACE ONLY 28 29 SPACE ONLY - - - - - - - C - - - - - - SPACE ONLY SPACE ONLY 30 31 SPACE ONLY - - - - - - - A - - - - - - SPACE ONLY SPACE ONLY 32 33 SPACE ONLY - - - - - - - B - - - - - - SPACE ONLY SPACE ONLY 34 35 SPACE ONLY - - - - - -- C - - - - - - SPACE ONLY SPACE ONLY 36 37 SPACE ONLY - - - - - - - A - - - - - - SPACE ONLY SPACE ONLY 38 39 SPACE ONLY - - - - - - - B - - - - - - SPACE ONLY SPACE ONLY 40 41 SPACE ONLY - - - - - - - C - - - - - - SPACE ONLY SPACE ONLY 42 EQUIPMENT SERVED CONN. LOAD L.F. LF. D.F. DEMAND LOAD RECEPTACLES LIGHTING 3.68 KVA 100% 125% 4.60 KVA ELEVATORS EQUIPMENT 4.20 KVA 100% 100% 4.20 KVA 14 NOTES: TOTAL DEMAND LOAD: 26.34 KVA TOTAL DEMAND LOAD: 8.80 KVA TOTAL DEMAND AMPS: 73.11 AMPS TOTAL DEMAND AMPS: 24.44 AMPS PANEL SL7 LOCATION: 7TH FLOOR STORAGE VOLTAGE: 208Y/120V 30 4W MIN. AIC RATING: 1 O AIC NOTES: PROVIDE TYPED WRITTEN DIRECTORY PROVIDE GROUND k NEUTRAL SUS ME: SQUARE -D NQOD MAINS: 125A 9 PALO ❑MCB MOUNTING: SURFACE FED FROM: SL1 LUGS: ❑SUB -FEED ❑ FEED -THRU ENCLOSURE: NEMA 1 CIRCUIT DESCRIPTION o Z BRANCH CIRCUIT BKR LOAD KVA PHASE 4 LOAD KVA BKR BRANCH CIRCUIT z CIRCUIT DESCRIPTION Y f NEUT GND COND 0 NEUT GND COND 1 RECEPTACLES - 7TH LOUNGE 12 12 12 1/2" 20/1 0.18 1 A 3.88 60/3 6 6 10 1.25 ELEVATOR 1 CONTROLLER 2 3 RECEPTACLES - 7TH LOUNGE 12 12 12 1/2" 20/1 0.18 B 3.88 - 6 - - - - 4 5 TTB - 7TH FLOOR 12 12 12 1/2- 20/1 0.36 C 3.88 - 6 - - - - 6 7 ITTB - 7TH FLOOR 1 12 1 12 12 1/2" 20/1 1 0.36 A 3.88 60/3 1 6 6 ' 10 11.25 1 ELEVATOR 2 CONTROLLER s s RECEPTACLES - 7TH LOUNGE 12 12 12 1/2" 20/1 0.18 1 B 3.88 6 - - I - - 10 11 RECEPTACLES - 7TH LOUNGE 12 12 12 1/2" 20/1 0.18 C 3.88 6 - - - 12 13 SPARE - - - - 20/1 - A 0.18 20/1 - - - - ELEVATOR ROOM RECEPTACLE 14 15 SPARE - - - 20/1 - B - 20/1 - - - - SPARE 16 17 SPARE - - - - 20/1 - C - 20/1 - - - - SPARE 1s 19 SPARE - - - - 20/1 - A - 20/1 - - - - SPARE 20 21 SPACE ONLY - - - - - - B - 20/1 - - - - SPARE 22 23 SPACE ONLY - - - - - - C - 20/1 - - - SPARE 24 25 SPACE ONLY - - - - - - A - - - - - - SPACE ONLY 26 27 SPACE ONLY - - - - - - B - - - - - - SPACE ONLY 28 29 SPACE ONLY - - - - - C - - - - - SPACE ONLY 30 31 SPACE ONLY - - - - - - A - - - - - - SPACE ONLY 32 33 SPACE ONLY - - - - - - B - - - - - SPACE ONLY 34 35 SPACE ONLY - - - - - C - - - - - - SPACE ONLY 368 37 SPACE ONLY - - - - - A - -- - - - SPACE ONLY 38 3s SPACE ONLY - - - - - - B - - - - - - SPACE ONLY 40 41 SPACE ONLY - - - - - - C - - - - - - SPACE ONLY 42 EQUIPMENT SERVED CONN. LOAD L.F. D.F. DEMAND LOAD RECEPTACLES 3.06 KVA 100% 3.06 KVA ELEVATORS 23.28 KVA 100% 23.28 KVA NOTES: TOTAL DEMAND LOAD: 26.34 KVA TOTAL DEMAND AMPS: 73.11 AMPS • • iii•• ri•i• iiU ••• ri •• r • u i • • • • i •r••N � • • IU9 i i � • Y rr� rrr Y mum • • � ti N N • N • Y •• YNr r.. ., ARCHITECTURE, INC. N..�.1�7�NG I F�Ft�`rCTECT1�FtE • Y•Ui 745 orienta avenue, suite 1121 altamonte springs, fl 32701 phone: 407.830.1400 fax: 407.830.4143 51170 www.forumarchitecture.com loik Dun 11 2 . BENEFICIAL COMMUNITIES 2206 Jo -An Drive Sarasota, FL 34231 Metro SOUth Apartments South Miami, FL JLC 12.0050.00 0`1RENC /// S 0 / ✓j77 QNAI Blake Lawrence Suddeth P.E. #: 69060 SET DISTRIBUTIONS: 2L SHEET REVISIONS: 12119112 10125113 03131114 01109/15 3 . 4, 14 21 1,Idg Dept Comments 2 Seven Stogy! Revision ildg Dept Comments.5 Cour�ard�Electrical Revision EDITED BY: MJR/BLS PROJECT NO. 11 -2795 Electrical w Schedules Z w a U w 9