Loading...
14-879-008i GREASE DUCT SPECIFICATION Furnish single -wall, factory built, grease duct for use with Type I kitchen hoods, which conforms to the requirements of NFPA -96. Products shall be ETL listed to UL -1978 for venting air and grease vapors from commercial cooking operations as described in NFPA -96. The duct wall shall be constructed of .036 thick type 430 stainless steel and be available in diameters 8" through 24 ". All supports, fan adapters, hood connections, fittings and expansion joints required to install grease duct shall be included. Roof penetrations shall comply with listed clearance to combustibles, see "Clearance to Combustibles" guide for details. The grease duct will terminate at the fan adapter plate, will be fully welded to the fan adapter plate and the fan adapter plate will be fastened to the curb using a suitably sized fastener provided by others; see page 12 of the 'Installation, Operation and Maintenance Manual' for details. Grease duct joints shall be held together by means of formed vee clamps and sealed with 3M Fire Barrier 2000 +. Screws used to secure the vee clamps shall be of the hex -head type with flanged stops and tapered 'lead in" threads for easy starting. Nuts shall be retained by means of a free - floating cage to allow easy alignment. Single -Wall Grease Duct shall be installed in accordance with the manufacturer's 'Installation, Operation and Maintenance Manual", ETL listing and state and local codes. Grease duct installed outside of the building shall be protected against accidental damage or vandalism. Support vertically installed grease duct from the building structure using rigid structural supports. Anchor supports to the structure by welding or bolting steel expansion anchors or concrete inserts. Support horizontally installed grease duct from the building structure using above method or use Duct Mate, Wire Rope & Clutchers, part numbers WR20 & CL20. 1/2" Threaded rod and saddles may also be used for the support of horizontal grease duct. Fans shall be supported independently from the grease duct sections. Protect grease duct from twisting or movement caused by fan torque or vibration. 12X12' 16 GA WELDED NOTEi USE OF CAPTIVE AIRE ETL LISTED GREASE CAN BE USED SUPPLY AIR UNIT, WALL 42 GA UNISTRUT BRACKET WELDED TO DUCT AND ATTACHED 0 BUILDING WITH 1!' CONCRETE SLEEVE ANCHORS, MIN. 2 PER BRACKET NOTEi ONE BRACKET EVERY 8' MINIMUM SUPPLY AIR UNIT, WALL MOUNTED NOTE: THERE ARE N❑ COMBUSTIBLES WITHIN 18" OF GREASE DUCT HOOD INSTALLED WITH S/S WALL FLASHING EXTENDING, 18" PAST ROOF ACCESSIBLE VIA FIXED LADDER ATTACHED TO BUILDING EXHAUST FAN LOCATED NOT LESS HAN 10' FROM ROOF EDGE 24 GA MUA DUCT 20 GA S/S BACKSPLASH SECTIFIN VIEW JOIST ROOF OR HOOD ALL SIDES NO-TEI::-PER- ERPR- M❑TION­ -FOR - APPROVAL ALL WORK SHALL BE IN COMPLIANCE WITH SECTI ❑N 20 -3.6 (Q)(1) OF THE LAND DEVELOPMENT CODE EXTERIOR DUCTWORK SHALL BE PAINTED TO MATCH THE COLOR OF THE BUILDING PAINT SHALL BE THE HIGH TEMP TYPE AND RATED OR ITS INTENDED USE THE EXTERIOR GARGAE DOOR SHALL BE RMEOVED AND REPLACED WITH A FIRE RATED PARTITI ❑N TO CREATE A CONTINUOUS FACADE AT THAT PORTION OF THE BUILDING. SET BUT SHALL BE DONE BY THE OWNERS CONTRACTOR NOTE: EXHAUST DUCT OUT BACK OF HOOD NOT SHOWN FOR CLARITY, REFER TO SECTI ❑N VIEW FOR DETAILS I I I I 14X14' 24 GA MUA DUCT I I I I 10' 0 SNAP Lgp FE 1z 0 SNAP LOCK PIPE OOD JOIST ROOF i.00i i.001 ELEVATION VIEW THIS WORK IS REFERENCED ON OUR PERMIT CH ,4 GENS • r • y .•o• kSh.T kE • v• .� . SEP 0 0 2014 NA� .•`�� BUCHANAN RE CONSULTING INC. ELECTRICAL * MECHANICAL * PLUMBING EN G /NEE RING 6191 W. ATLANTIC BLVD, SUITE# 1W MARGATE, FL 33064 Phi 954 - 590 -3300 Fax1 954 - 590 -2232 Errialtl Mepenglneers@aol,coM RAJA BUCHANAN FL RE # 48916 CERTIFICATE OF AUTHORIZATION # 8842 REVISIONS WON WON �- E 8 CL r� .2 11r a II rrrrrr � r I W I � i� M rn W LL � U oNo n O � ui I a z 1 C oft Q L.L LLJ H a J LL- H Q H Li LLJ ly F_ F— 3 CD Ln T___1 DATE: 3/13/2014- DWG. #: 1845940 DRAWN JTS SCALE: 3/4" = 1' -0" MASTER DRAWING SHEET NO. 3 A A >� °cop ++ V 4-4 X X y X X =LJ Oia• �LJ L Gin-• C) ct °ocm 0) M_� �_� ELEVATION VIEW THIS WORK IS REFERENCED ON OUR PERMIT CH ,4 GENS • r • y .•o• kSh.T kE • v• .� . SEP 0 0 2014 NA� .•`�� BUCHANAN RE CONSULTING INC. ELECTRICAL * MECHANICAL * PLUMBING EN G /NEE RING 6191 W. ATLANTIC BLVD, SUITE# 1W MARGATE, FL 33064 Phi 954 - 590 -3300 Fax1 954 - 590 -2232 Errialtl Mepenglneers@aol,coM RAJA BUCHANAN FL RE # 48916 CERTIFICATE OF AUTHORIZATION # 8842 REVISIONS WON WON �- E 8 CL r� .2 11r a II rrrrrr � r I W I � i� M rn W LL � U oNo n O � ui I a z 1 C oft Q L.L LLJ H a J LL- H Q H Li LLJ ly F_ F— 3 CD Ln T___1 DATE: 3/13/2014- DWG. #: 1845940 DRAWN JTS SCALE: 3/4" = 1' -0" MASTER DRAWING SHEET NO. 3