11-816-004r
MI7V -
GON5TRUCTION AREA AIRFLOW
TEE FITTING
METAL FLEX
DUCT. (TYPJ
J�
1_
ADJACENT SPACE
:,ZAI2 L? =11 CEILING DIFFUSER
TRAN5FER AIR BACK TO
CONSTRUCTION ARE
COMBINATION NEGATIVE AIR PRESSURE
MACHINE AND AIR SCRUBBER DETAIL
SCALE: N.T.5
INFECTION CONTROL RISK ASSESSMENT (ICRA)
THE ICRA MATRIX SHALL BE COMPLETED DURING PRE - CONSTRUCTION AND APPROVED BY THE
FACILITIES 5AFETY, AND INFECTION CONTROL OFFICE. CONTRACTOR SHALL 51GN THE ICRA AGREEMENT
AS PART OF THE CONSTRUCTION CONTRACT DOCUMENT5. PRE56RIBED PRECAUTIONS MUST BE IN PLACE
PRIOR TO WORK 5TART AND MU5T BE MAINTAINED THROU6HOUT THE DURATION OF THE PROJECT.
ICRA MATRIX
PATIENT
CON5TRUCTION ACTIVITY TYPE
TYPE A
TYPE B
TYPE G
TYPE D
R15K 6ROUP
LOW
GLASS I
GLASS II
. "..ra..- CLA_% 11 - _
GLASS IIIAV
MEDIUM
GLA_% I
CLASS 11
CLA55 III
CLA55 IV
HIGH
CLASS 1
CLA65 11
CLASS III/IV
GLASS IV
H16HE5T
GLA% 111
CLASS III/IV
CLASS 111 1IV
GLASS IV
INFECTION CONTROL RISK LEVELS
6ROVP I
IS
LOW RISK:
OFFICE AREAS
CONSTRUCTION ACTIVIY TYPES
240 SF
WORK THAT 6ENERATE5 MODERATE TO H164i LEVEL OF DUST OR REQUIRE5 DEMOLITION OR REMOVAL OF ANY
IH
FIXED BUILDING COMPONENT5 OR A55EMBLIES. INCLUDES, BUT 15 NOT LIMITED TO:
5,905
• SANDING OF WALLS FOR PAINTING OR WALL COVERING
TYPE C
• REMOVAL OF FLOOR COVERING, WALL COVERING, CEILING TILES AND CASEWORK
TREATMENT
• NEW WALL CONSTRUCTION
240 5F
• MINOR DUCT WORK OR ELECTRICAL HOW ABOVE CEILINGS
Ii
• MAJOR CABLING ACTIVITIES
5,585
• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A 51W-ALE WORK SHIFT.
24
ICRA CLASSIFICATION
SCHEDULE
1,115
AGTION5 TO BE PERFORMED
ACTIONS TO BE PERFORMED
TOTAL - FIRST LEVEL
DURING CONSTRUCTION OR RENOVATION
UPON COMPLETION / PRIOR TO OCCUPANCY
UA55 II
I. PROVIDES ACTIVE MACS TO PREVENT AIR -BORNE DUST FROM
I. PET MOP/MPE EXPOSED SURFACES VITH APPROPRIATELY
015PER51NO INTO ATMOSMRE.
LABELED AND BH5F APPROVED LABEL 0151NFEGTANT.
2. HATER MST WORK SIRFACE5 TO CONTROL DUST MILE CJJTTU46
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN T16HTLY
3. SEAL UNU5ED DOORS HTH DUCT TAPE.
COVERED SOLID LID CONTAINERS.
4. BLOCK OFF AND 5EAL AIR VENTS.
3. VET MOP AND /OR VACaH WTH HEPA FILTERED VACIAIM
5. REMOVE OR 15CLATE HVAG 5Y5TEM IN AREA HEM HM 15 BEMG
BEFORE LEAVING WORK AREA
DONE TO PREVENT CONTAMINATION OF THE DUCT SYSTEM.
4. REMOVE 15MATION OF HVAC SYSTEM IN AREAS
b. PLACE DUST MAT AT ENTRANCE AND EAT OF WORK AREA
WHERE WORK 15 BEING PERFORMED.
1. PIPE 5URFACES WITH DIWECTANT.
6. COVER TRAKPORT REGEPTACLE5 OR CARTS. TAPE COVERING UNLESS
SOLID LID.
PARTIAL FIRST FLOOR LIFE SAFETY PLAN
SCALE: OF = 1' -0'
SMOKE COMPARTMENT SUMMARY
SMOKE
COMPARTMENT
PRIMARY
USE
AREA
S.F.
OCCUPANT
LOAD FACTOR
PER PER50N
OCCUPANT
LOAD
IA
TREATMENT
14�2b5
240 5F
b0
IB
TREATMENT
15,215
2405F
84
IC
A55EMBLY
BUSINESS
5UB -TOTAL
3,158
9,209
12961
15 SF
100 5F
250
612
342
ID
TREATMENT
5TORA6E
BUSINESS
SUB -TOTAL
1,995
3,343
9,340
14,618
240 SF
300 5F
100 5F
8
II
q3
112
IE
KITCHEN
DINNING
SUB -TOTAL
61,503
5,101
15,210
200 5F
115E
48
518
566
IF
MECH. EQ.
5,330
300 5F
IS
I6
TREATMENT
8,440
240 SF
35
IH
TREATMENT
5,905
2405F
25
II
TREATMENT
1,1615
240 5F
30
Ii
TREATMENT
5,585
240 5F
24
IK
TREATMENT
1,115
240 5F
33
TOTAL - FIRST LEVEL
112,565
1,309
BUILDING INFORMATION
PROJECT NAME: BAPTI5T HEALTH 50TH MIAMI H05PITAL
LIFE SAFETY SURVEY
APPRE55: 6200 5H 13 STREET SOUTH MIAMI, FLORIDA 33243
APPLICABLE CODES
FLORIDA BUILDING CODE: BUILDING CODE -2001 EDITION HITH 2009 AMENOMENT5
THE 6UIDELINES OF DESIGN AND CON5TRUGTION OF HEALTH CARE
FACILITIES 2006 EDITION
FIRE CODE: NFPA I, UNIFORM BUILDING CODE/ FLORIDA FIRE PREVENTION CODE 2001
LIFE SAFETY CODE: NFPA 101 - LIFE SAFETY CODE 2006
ACCE551BILITY CODE: 2001 FLORIDA BUILDING CODE WITH 2O0q SUPPLEMENTS CHIP. II
STATE FIRE MARSHALL RULE: NFPA 10 -2001, STANDARD FOR PORTABLE FIRE EXTINGUISHER
NFPA 13, 2002 STANDARD FOR THE INSTALLATION OF SPRINKLER 5Y5TEM5
NFPA 12, 2002 NATIONAL FIRE ALARM CODE
NFPA 60, I61g61, STANDARD FOR FIRE DOOR AND WINOOH5
NFPA qq, 2005 STANDARD FOR HEALTHCARE FACILITIES
NFPA 105, 2003 SMOKE CONTROL DOOR A55EM13LY
NFPA 221,200(b STANDARD OF FIRE WALLS AND FIRE BARRIER WALLS
BUILDING PLANNING
OCCUPANCY: INSTITUTIONAL GROUP I (FBC 200(b)
MIXED OCCUPANCY: NO
REQUIRED FIRE SEPARATION: IHR.
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE: FEY, TYPE IB - NFPA 220
H \p
OC SG G OE��
WO RK� \ - "" ��
CS:
�1
EXIT SUMMARY
EXIT
TYPE/FACTOR
WIDTH IN
INCHE5
PROVIDED
CAPACITY
IN
PER5ON5
A
EXT. DR 1.2
48'
240
B
EXT. DR1.2
48'
240
G
EXT. DR1.2
84'
480
D
EXT. DRJ.2
84'
480
E
EXT. DR1.2
84'
480
F
EXT. DR 1.2
84'
480
6
EXT. DR1.2
60'
300
H
EXT. DR1.2
48'
240
1
EXT.ORJ.2
42'
210
J
EXT. DR1.2
b0'
300
EXT. DR1.2
42'
210
L
EXT. DR 1.2
84'
480
DO
M
EXT. DR1.2
10'
350
EXIT CAPACITY AVAILABLE
4,490
EXIT CAPACITY REQUIRED
1509
O
O�
O
o �
�o
A
SALTS MICHELSON
A R C H I T E C T S
3501 Griffin Road
Ft. Lauderdale, FL 33312
(954) 266 -2700 Fx: (954) 266 -2701
sma @saltzmichelson.com
' , T? j �.T
AA- 0002897
.;C
Charles Michelson AR0009976
F
a
s
Project No.:
2011 -168
Drawn By:
GM
Checked By:
LS
Date:
08 -10 -11
Revisions
mi