14-229-011.. THE SCOPE OF WORK INCLUDES THE ADDITION OF ff& DEVICES TO AN EXISTIN( FIRE ALARM SYSTEM AND IS LIMITED TO A SPECIFIC AREA OF THE BUILDING AS SHOWN ON THE DRAWINGS. ALL Lac DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES AND MANUFACTURER, INSTRUCTIONS. THE FOLLOWING DEVICES (IF APPLICABLE), SHALL RESPOND AS FOLLOWS: MANUAL PULL STATIONS: THE ACTIVATION OF A NEW MANUAL PULL STATION SHALL INITIATE AN "ALARM" CONDITION IN THE BUILDING FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2007 EDITION) CHAPTER 5.13 AND NFPA 1 CHAPTER 13.7.3.3 OF THE FLORIDA FIRE PREVENTION CODE (2010 EDITION) AT NOT LESS THAN 3 -1/2' do NOT MORE THAN 4-1/2' AFF. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARM SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL AND ANY REMOTE ANNUNCIATOR. THE ALARM SHALL ALERT THE ENTIRE BUILDING OCCUPANTS-BY WAY OF HORNS, HORNS /STROBES AND /OR STROBE DEVICES. THE ALARM CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF FIRE DEPARTMENT NOTIFICATION AND ACTION. THE ACTIVATION OF A NEW SMOKE DETECTOR SHALL INITIATE AN "ALARM" CONDITION IN THE BUILDING FOR EVACUATION PURPOSES AS PER NFPA 72, (2007 EDITION) CHAPTER 5.5. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARM SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE ALARM SHALL ALERT THE ENTIRE BUILDING OCCUPANTS S' WAY OF HORNS, HORNS /STROBES AND /OR STROBE DEVICES. THE ALARM CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF FIRE DEPARTMENT NOTIFICATION AND ACTION. CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW, NOR CLOSER THAN 3' FROM AN AIR SUPPLY DIFFUSER IN ACCORDANCE WITH NFPA 72, (2007 EDITION) CHAPTER 5.7.4.1 WALL MOUNT SMOKE DETECTORS SHALL BE MOUNTED 4' MINIMUM FROM CEILING WITH 12" MAXIMUM FROM CEILING, AS PER NFPA 72, (2007 EDITION) CHAPTER 5.7.3.2.1 IF APPLICABLE, THE ACTIVATION OF ANY NEW CORRIDOR SMOKE DETECTOR SHALL RELEASE THE MAGNETIC HOLD OPEN DEVICES ASSOCIATED WITH ANY SMOKE/FIRE DOORS SO THAT THE DOORS CLOSE. MAGNETIC HOLD OPEN DEVICES ARE FAIL -SAFE AND SHALL RELEASE (CLOSE) ON A POWER FAILURE OF THE FIRE ALARM SYSTEM, PER NFPA 72, (2007 EDITION) CHAPTER 6.16 SMOKE DETECTORS IN ELEVATOR LOBBIES: THE ACTIVATION OF A NEW SMOKE DETECTOR IN AN ELEVATOR LOBBY, ELEVATOR SHAFT AND /OR ELEVATOR MACHINE ROOM SHALL, IN ADDITION TO THE ABOVE, ALSO INITIATE THE RECALL OF THE ELEVATOR CARS AS FOLLOWS IN ACCORDANCE WITH NFPA 72, (2007 EDITION) CHAPTER 6.16.3: PHASE 1 RECALL, ANT IF THEL VE E�AT.yOR MACHINE ROOM IS LOCATED ON THE MAIN FLOOR, THE ACTIVATION OF THAT SMOKE DETECTOR WILL INITIATE PHASE I RECALL ALTERNATE FLOOR RESPONSE. ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON FLOORS 2 AND ABOVE AND /OR ANY SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM OR ELEVATOR SHAFT SHALL INITIATE PHASE I RECALL WHICH WALL BRING THE ELEVATOR CAR TO THE FIRST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON THE FIRST FLOOR SHALL INITIATE PHASE I RECALL ALTERNATE WHICH WILL BRING THE ELEVATOR CAR TO THE SECOND FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. ELEVATOR WARNING LIGHTS: ELEVATOR WARNING LIGHTS: ACTUATION OF ANY ELEVATOR MACHINE ROOM SMOKE DETECTOR OR ELEVATOR HOIST WAY DETECTOR SHALL ALSO INITIATE ANY EXISTING ELEVATOR WARNING LIGHTS TO ALERT EMERGENCY PERSONNEL THAT THE ELEVATORS ARE NOT SAFE TO USE. HEAT DETECTOR DEDICATED FOR ELEVATOR SHUNT SHALL BE CONNECTED WHERE REWIRED. AND ACTIVATE A CONTROL SHUNT TO DISCONNECT POWER UPON ACTIVATION. THE SHUNT POWER SOURCE SHALL BE MONITORED. HEAT DETECTORS: THE ACTIVATION OF A NEW HEAT DETECTOR SHALL INITIATE AN "ALARM" CONDITION IN THE BUILDING FOR EVACUATION PURPOSES. HEAT DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, (2007 EDITION) CHAPTER 5.6. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARM SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE ALARM SHALL ALERT THE ENTIRE BUILDING OCCUPANTS BY WAY OF HORNS, HORNS /STROBES AND /OR STROBE DEVICES. THE ALARM CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF FIRE DEPARTMENT NOTIFICATION AND ACTION. DUCT DETECTORS: ANY AHU ABOVE 2000 CFM AND RETURNS RECIRCULATING OVER 15,000 CFM OR SERVING MORE THAN ONE FLOOR SHALL BE PROVIDED WITH A DUCT DETECTOR PER NFPA 72 (2007 EDITION), CHAPTER 5.7.4 THE ACTIVATION OF A NEW DUCT DETECTOR SHALL INITIATE A "SUPERVISORY" CONDITION AT THE FIRE ALARM CONTROL PANEL AN AUDIBLE SUPERVISORY TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANELS AND THE SUPERVISORY LOCATION SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE SUPERVISORY SIGNAL SHALL SHUT DOWN ALL HVAC UNITS ASSOCIATED IN THAT ZONE. THE SUPERVISORY CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF NOTIFICATION AND ACTION. THE NEW RELAY CONTACTS HAVE A MAXIMUM CAPABILITY OF 1.0 AMPS O 24V AND 0.3 AMPS O 120 VAC. CONTRACTOR SHALL VERIFY THAT THE SHUTDOWN CIRCUIT SHALL NOT EXCEED THESE MAXIMUM CURRENT RATINGS. SUPERVISORY SIGNAL INITIATING DEVICES: (TAMPERS, PIV, FIRE PUMP SUPERVISION, EMERGENCY GENERATOR, ETC.) THE ACTIVATION OF ANY NEW SUPERVISORY SIGNAL INITIATING DEVICE MODULES SHALL INITIATE A "SUPERVISORY TROUBLE" CONDITION AT THE FIRE ALARM CONTROL PANEL IN ACCORDANCE WITH NFPA 72, (2007 EDITION) CHAPTER 5.15. AN AUDIBLE SUPERVISORY TROUBLE TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE SUPERVISORY CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR. ALARM MONITORING POINTS: (KITCHEN HOOD SYSTEMS, SUPPRESSION PANEL, ETC.) THE ACTIVATION OF ANY NEW MODULE THAT MONITORS AN ALARM POINT SHALL INITIATE AN "ALARM' CONDITION IN THE BUILDING FOR EVACUATION PURPOSES PER NFPA 72, (2007 EDITION) CHAPTER 6.8.5. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL THE LOCATION OF THE ALARM SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE ALARM SHALL ALERT THE ENTIRE BUILDING OCCUPANTS BY WAY OF HORNS, HORNS /STROBES AND /OR STROBE DEVICES. THE ALARM CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF FIRE DEPARTMENT NOTIFICATION AND ACTION. THE ACTIVATION OF A NEW SPRINKLER FLOW SWITCH SHALL INITIATE AN 'ALARM' CONDITION IN THE BUILDING FOR EVACUATION PURPOSES AS PER NFPA 72, (2007 EDITION) CHAPTER 6.8.5.5 AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARM SHALL BE DISPLAYED, IN ENGLISH, AT THE CONTROL PANEL(S) AND ANY REMOTE ANNUNCIATORS. THE ALARM SHALL ALERT THE ENTIRE BUILDING OCCUPANTS BY WAY OF HORNS, HORNS /STROBES AND /OR STROBE DEVICES. THE ALARM CONDITION SHALL BE REPORTED TO A REMOTE SUPERVISING STATION BY WAY OF AN APPROVED COMMUNICATOR FOR THE PURPOSES OF FIRE DEPARTMENT NOTIFICATION AND ACTION. FLOW BELL: A. FLOW BELL SHALL ACTIVATE UPON WATER FLOW ONLY. B. FLOW BELL SHALL CONTINUE TO SOUND AS LONG AS WATER IS FLOWING. C. FLOW BELL SHALL NOT BE SILENCE ABLE FROM FACP. POWER UP AND POWER DOWN SEQUENCE FOR FIRE ALARM PANELS: POWER DOWN: 1. DISCONNECT BATTERY 2. TURN OFF AC POWER PRIMARY & SECONDARY POWER UP: 1. TURN ON AC POWER PRIMARY do SECONDARY 2. RECONNECT BATTERIES THE FIRE ALARM SYSTEM SHOWN IS IN ACCORDANCE MATH THE NFPA LIFE SAFETY CODE (2009 EDITION), CHAPTER 39. THE SCOPE OF WORK IS LIMITED TO ONLY THAT WHICH IS SPECIFICALLY DETAILED ON THE FLOOR PLAN. 1. ALL tff& EQUIPMENT INSTALLED AS PART OF THIS SCOPE OF WORK SHALL BE UL LISTED. ALL NEW DEVICES PULLING POWER FROM INITIATING OR SIGNAUNG CIRCUITS SHALL BE LISTED FOR THE CONTROL UNIT PER NFPA 72 - 4.4.2 (2007 EDITION). 2. THE INSTALLATION OF THE NEW FIRE ALARM DEVICES SHALL COMPLY WITH NFPA 70 (NATIONAL ELECTRICAL CODE, 2008 EDITION), THE FLORIDA FIRE PREVENTION CODE (2010 EDITION), NFPA 72 (2007 EDITION), THE FLORIDA ACCESSIBILITY CODE (2012 EDITION) AND THE FLORIDA BUILDING CODE (2010 EDITION). THE SYSTEM MEETS THE MANUFACTURER'S PUBLISHED INSTRUCTIONS AND NFPA 72 REQUIREMENTS 4.5.1 AND 4.5.2 (2007 EDITION) THE EXISTING FIRE ALARM SYSTEM CONSISTS OF A FIRE DETECTION CONTROL PANEL AND INITIATION AND NOTIFICATION APPLIANCES. 3. THE EXISTING FIRE ALARM SYSTEM IS "POWER LIMITED'. 4. THE EXISTING FIRE ALARM CONTROL PANEL IS INTELLIGENT AND HAS STANDBY BATTERY BACKUP AS PER NFPA 72 - 4.4.1.5 (2007 EDITION), PROVIDING BATTERY POWER CAPACITY FOR THE ENTIRE SYSTEM TO OPERATE FOR 24 HOURS IN STANDBY MODE AND 5 MINUTES IN ALARM MODE. BATTERIES SHALL BE PERMANENTLY MARKED WITH THE MONTH AND YEAR OF MANUFACTURE (MM/YYY ). 5. CABLE TYPE, SIZE AND INSTALLATION REQUIREMENTS FOR ALL NEW DEVICES SHALL COMPLY WITH ARTICLE 760 OF NFPA 70 (NATIONAL ELECTRICAL CODE, 2008 EDITION) FOR 'POWER LIMITED' FIRE PROTECTION SIGNALING CIRCITS- WIRING METHODS AND MATERIALS. 6. MINIMUM CABLE SIZE - -- REFER TO WIRE LEGEND FOR DETAIL 7. ALL NEW WIRING AND CONDUIT TO BE INSTALLED IN ACCORDANCE WITH NFPA 70 (NATIONAL ELECTRICAL CODE, 2008 EDITION). WIRE SHALL BE SOUD COPPER OR STRANDED COPPER WITH A MAXIMUM OF 7 STRANDS FOR SIZES 16 AND 18 AWG. STRANDED COPPER WITH A MAXIMUM OF 19 STRANDS. 8. ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES WITH ENVIROMENTAL AIR SHALL BE TYPE 'FPLP ", AS PER NFPA 70 (NATIONAL ELECTRICAL CODE, 2008 EDITION). 9. ALL NEW ALARM NOTIFICATION APPLIANCES SHALL BE VISUAL, AUDIBLE - VISUAL AND /OR AUDIBLE TYPE. 10. ALL NEW AUDIBLE DEVICES SHALL BE HORNS, AND SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 - 7.4. (2007 EDITION), FOR LOCATION, SPACING AND AUDIBILITY REQUIREMENTS 11. ALL NEW VISUAL DEVICES SHALL BE XENON TYPE, WITH A MINIMUM CANDELA RATING OF 15 CANDELA. WALL MOUNTED UNITS SHALL BE PLACED BETWEEN 80' - 96" AFF (OR 6' FROM THE CEILING, WHICHEVER IS LOWER), CEILING MOUNTED DEVICES SHALL BE SUSPENDED AT OR BELOW 30 FT. ALL VISUAL DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 - 7.5 (2007 EDITION) AND THE FLORIDA ACCESSIBILITY CODE (2012 EDITION). IF MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES OR GROUPS OF SYNCHRONIZED APPLIANCES IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW ARE PRESENT, THEY WILL FLASH IN SYNCHRONIZATION PER NFPA 72 - 7.5.4 (2007 EDITION). 12. THE LOCATION OF NEW SMOKE AND HEAT DETECTORS SHALL BE SPECIFIED ON THE DRAWINGS AND SHALL BE IN COMPLIANCE MATH NFPA 72 - 5.4 AND 5.5 (2007 EDITION). 13. NEW MANUAL PULL STATIONS SHALL BE MOUNTED NOT LESS THAN 3 1/2' AND NOT MORE THAN 4 1/2' AFF AND SHALL BE INSTALLED IN ACCOPROANCE WITH NFPA 72 - 5.13 (2007 EDITION) AND THE FLORIDA ACCESSIBILITY CODE 14. CONTRACTOR WILL MAKE ANY CORRECTIONS TO DRAWINGS (AS- GUILTS) TO REFLECT THE FIRE ALARM SYSTEM, AS INSTALLED). DEVICES SHOWN ON PLANS MAY NEED TO BE RELOCATED DUE TO ACTUAL BUILDING AND SPRINKLER CONFIGURATION. 15. CIRCUIT POLARITY WILL BE OBSERVED. 16. NEW CONDUIT, WHERE REQUIRED, SHALL NOT EXCEED 4OX FILL, PER NFPA 70, (NATIONAL ELECTRICAL CODE, 2008 EDITION) 17. ALL NEW FIRE STOP PENETRATIONS SHALL BE SEALED WITH A UL APPROVED FIRESTOP MATERIAL (SEE FIRESTOP DETAIL). 18. NEW FIRE ALARM RISER CIRCUITS SHALL BE CLASS "B STYLE "4 ". 19. A BREAK IN ANY FIELD WIRING OR GROUNDING OF ANY NEW CONDUCTOR WILL RESULT IN THE ACTIVATION OF THE FIRE ALARM CONTROL PANEL "TROUBLE" SIGNAL, AND WALL PRODUCE AN AUDIBLE AND VISIBLE ANNUNCIATION AT THE PANEL AND ANY REMOTE ANNUNCIATORS. (PER NFPA 72, 2007 EDITION) 20. THE FIRE ALARM SYSTEM SHALL BE MONITORED OFF- PREMISE BY A 'REMOTE SUPERVISING STATION" IN ACCORDANCE WITH NFPA 72 - 8.5 (2007 EDITION). 21. TWO TELEPHONE LINES ARE PROVIDED TO THE FIRE ALARM COMMUNICATOR FOR PURPOSES OF MONITORING THE FIRE ALARM SYSTEM. TELEPHONE LINES SHALL BE CONNECTED IN CONFORMANCE WITH NFPA 72 - 8.6 (2007 EDITION). 22. AT THE FINAL INSPECTION, A - CERTIFICATE OF COMPLETION- SHALL BE PROVIDED TO THE CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION FOR ALL NEW DEVICES INSTALLED. A LOG BOOK SHALL REMAIN ON THE PREMISES THAT SHALL INCLUDE AS -BUILT DRAWINGS, MANUALS, INSPECTION RECORDS, ETC. PERTAINING TO THIS SCOPE OF WORK. ADA HEIGHT VI AUDIBL TO BE LOCATED E 80" AND 96" 6" BELOVI (WHICHEVER I; PER NFPA 72 PULL TO BE LOCATED 312' -A PER NFPA 7i 1900 BOX PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING CEILING PLUG - IN DETECTOR BASE DETECTOR HEAD BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS (MUST BE INSTALLED WITH CONDUIT) THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. 1 OR 2 HOUR FIRE RATED THROUGH f� 2 HOUR FIRE RATED THROUGH 1 f f� PENETRATION FIREST FOR PENETRATION FIRESTOP FOR SINGLE METAL PIPE THROUGH GYPSUM GS Gass MULTIPLE METAL PIPE TH H ROUGH CONCRETE FLOORS WALLS WALLS USING TREMSTOP WBM. � USING FYRE- SHIELD. F- RATING = 1 AND 2 HR. � F- RATING = 2 HR. WL1147 T- RATING = 0 AND 12 HR. CAJ -1304 T- RATING = 0 HR. 1 2 1 SECURITY INC. IT IS NOT TO ` a+�t. t� K..•tiN O9 LINE VOLTA( BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN 9111 CONSENT OF ADVANCED FIRE & 1. FLOOR OR WALL ASSEMBLY = 4 "THICK CONCRETE, MAX. AREA OF OPENING IS 288 SQ. IN. SECURITY INC. 2. COPPER PIPE: 4 "DIA. (OR SMALLER) REGULAR (OR HEAVIER) COPPER. STEEL PIPE: 8" DIA. (OR SMALLER) SCHAD (OR HEAVIER) STEEL. If any document prepared by Advanced CONDUIT: 4" DIA. (OR SMALLER) EMT OR 6" DLA. (OR SMALLER) STEEL CONDUIT. 1. 1 OR 2 - HOUR FIRE RATED GYPSUM WALLBOARD /STUD ASSEMBLY COPPER TUBING: 4" DIA.(OR SMALLER) TYPE L(OR HEAVIER) COPPER. Fire & Security Inc. is altered in any IRON PIPE: 8" DIA.(OR SMALLER) CAST OR DUCTILE IRON. 2. A) STEEL PIPE - 6" DIAM.(OR SMALLER) SCH. 40 (OR HEAVIER) STEEL MAX. NUMBER OF PIPES WITH OPENING IS THREE (3). B) CONDUIT - 4" DIAM.(OR SMALLER) EMT OR RIGID STEEL 3 A) FORMING MATERIAL - (NOT SHOWN) - NOM. 1" THICK POLY 3. TREMSTOPWBM - FILL MAX. 3/4" ANNULUS AT A THICKNESS URETHANE BACKER ROD FRICTION FITTED INTO OPENING. OF 1 " (2 HR. F- RATING) OR 314' (1 HR. F- RATING). B) NOM. Ys" FYRE- SHIELD THICKNESS INSTALLED WITHIN OPENING. NOTE: FOR WALL APPLY FYRE- SHIELD TO BOTH SURFACES OF WALL. 2 HOUR FIRE RATED THROUGH 1 OR 2 HOUR FIRE RATED THROUGH f ff� PENETRATION FIRESTOP FOR SINGLE pass I f� PENETRATION FIRESTOP FOR Gass PLASTIC PIPE THROUGH V PLASTIC PIPE THROUGH U CONCRETE FLOORS OR WALLS GYPSUM WALLS USING USING BLAZEMASTER CAULK & WALK FYRE -CAN SLEEVE em F- RATING = 2 HR. em F- RATING = 2 HR. CAJ 2221 T- RATING = 1 -12 HR. WL2151 T- RATING = 1 HR. 3 4 1 °• 4 tl . ....... . . . a' a. 1. PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4-12" THICKNESS Fire & Security Inc. for any and all acts 1. PRE -RATED GYPSUM WALLBOARD/STUD ASSEMBLY. 2. PLASTIC PIPE - A) NOM. 2" DIAM. (OR SMALLER) SCH. 40 PVC PIPE. 2. PLASTIC PIPE - 3" DIA. OR 2" DIA. SCHAD PVC FOR USE B) NOM. 2" DIAM. (OR SMALLER) CPVC PIPE IN CLOSED OR VENTED PIPING SYSTEMS, THE ANNULAR SPACE RANGE SHALL BE MIN MIN 1/4' TO MAX 318" 3. FYRE -CAN SLEEVE/INTUMESCENT DEVICE: NOTE: FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS. NOM. PIPE DIAM. OF ANNULAR 3. FORMING MATERIAL - FOAM BACKER ROD FIRMLY PACKED INTO THE OPENING DIAM. (IN.) DEVICE SIZE OPENING (IN.) SPACE (IN.) AS A PERMANENT FORM. 2 TS2 3.12 1/4 TO 7/8 Contractor shall field verify all information 3 TS3 4-3/4 12 TO 314 4. BLAZEMASTER CAULK & WALK - MIN 1/2" THICKNESS OF SEALANT APPLIED WITHIN OPENING, FLUSH TOP SURFACE OF FLOOR OR BOTH SURFACES OF 4. TREMSTOP WBM - MIN. 1/4" THICK SEALANT APPLIED AT WALL ASSEMBLY SLEEVE/PIPE AND SLEEVENVALL INTERFACES. responsible for design and installation of THE PRODUCTS USED IN THE ABOVE ASSEMBLY HAVE The and products ha a beendtested anted are 09M the system in accordance with the based on both past and anticipated BEEN TESTED IN ACCORDANCE WITH THE FOLLOWING: performance criteria. tremco shall Beachwood, OH, 44122 • ASTM E814 (UL1479) STANDARD TEST METHOD not be liable for arty damages, direct To the best of our knowledge the FOR THROUGH PENETRATION FIRESTOPPING. or consequential, resulting from use • ASTM E119 (UL 263) STANDARD FOR FIRE TESTS of this material or design. tremco OF BUILDING CONSTRUCTION AND MATERIALS. shall only be responsible for replacing DRAWING NOT TO SCALE material found to be defective. FROM INTFC BOARD[7 AT FACPL- NOTE: 1- NOTE:3 CABLE 300 0 COITYP LOOP`S ESS 300 O C]ITYP LOOPADDRESS -NOTE: 3 NHERENEXT DEVICE APPLICABLE) NOTE 1: DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE NOTE 2: DO NOT LOOP WIRE UNDER TERMINALS 1 & 2. BREAK WIRE RUN TO PROVIDE SUPERVISION NOTE 3: OBSERVE POLARITY. DO NOT GROUND CONTROL WIRES OR SHIELDS. TIE SHIELDS TOGETHER AT EACH DETECTOR. NOTE 4: SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE NOTE 5: RECORD THE LOOP ADDRESS & DEVICE TYPE IN THE SPACES PROVIDED ON BOX MOUNTING IN CONDUIT 4" SQUARE (2 -1/8" DEEP) BOX (OR 4" BOX). PROVIDE 0 0 ADEQUATE SUPPORT FOR BOX IN CEILING FLEX 4" SQUARE (2 -1/8" DEEP) BOX 4" SQUARE BOX TO 3-0 ADAPTER RING (OR NO RING IF 4-0 BOX IS USED) NOTE: MIN PIPE FLEX 1/2" FREE WIRE IN CEILING CEILING PLUG - IN DETECTOR BASE DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, AND IS NOT AN EXACT SPECIFICATION. NOTES & DETAILS SCALE: N.T.S. TYPICAL ELEVATOR WIRING FOR INTELLIGENT SYSTEM OELEVATOR DISCONNECT SWITCH WITH SHUNT - TRIP. OELEVATOR F O(NUMBER N( OELEVATOR N SYSTEM SM( FIRE FIGHTEI O5 SYSTEM HEM 24" OF SPR 06 FIRE ALARM OSHUNT - TF 08 SHUNT - TF OF SYSTEM SECURITY INC. IT IS NOT TO DISCONNECT O9 LINE VOLTA( SOB CO., _ rI $ 50 Signat e: EF# 0001026 KATFRLEEN B O'NEAL MY COMMISSION # EE172765 EXPIRES February 26, 2016 ♦•�` FIRE & SECURITY 2780 GATEWAY DRIVE POMPANO BEACH, FL 33069 (954)772 -1700 (954)772 -0500 fax WNW W.ADVFIREONLI NE.COM STATE AND U.L. LICENSED EF#0001026 U.L.# S7195 -1 0 J a N O Z a Iftft mftft g 0 v z a. 4 a J t O W CIO M �" er LIJloft W M � C j- co Cn O O j�. �j 40 6 THIS DRAWING AND ITS CONTENTS ARE THE PROPERTY OF ADVANCED FIRE & SECURITY INC. IT IS NOT TO BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN CONSENT OF ADVANCED FIRE & SECURITY INC. If any document prepared by Advanced Fire & Security Inc. is altered in any manner by owner, its agents or by any third party if construction is not in accordance with unaltered documents prepared by Advanced Fire & Security Inc. then it is understood that Advanced Fire and Security Inc. has no liability in whole or in part, related to the project and that the owner and its agents Indemnify and holds harmless Advanced Fire & Security Inc. for any and all acts related to the project. This concept drawing is for information only to potential system arrangement. Contractor shall field verify all information contained on these drawings and is responsible for design and installation of the system in accordance with the specifications. To the best of our knowledge the drawings and specifications submitted herewith, comply with existing Interpretations and previsions of the applicable N.F.P.A. codes in effect at the date shown below. No warranty express or implied is hereby rn REVISIONS: N I` O N g Q W J H (L N 0 U v ` AFSI PROJECT NUMBER: 7120272 Y DATE: SCALE: 9/24/12 AS SHOWN r N c ' DRAWN BY: CHECKED BY: I.E.A. E.J.W. m 11 of 11 JL1