14-229-009BATTERY CALCULATIONS TYP A-IP 11 5.0 EXTERNAL DEVICE POWER THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL DEVICES IS LIMITED. USE TABLE Sl STANDBY OR NONALARM AND A TABLE S2 (ALARM) TO l 1 ( 1 DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBILITIES OF THE POWER SUPPLY. REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND THE STANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW f'A4WNAid 'iRli@fOlif>f<R.Y'{JDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES ON EACH ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. DEVICE TYPE N OF DEVICES CURRENT TOTAL (AMP) AMPS MAIN PC BOARD WITHOUT AC X 0.032 FAIL REPORT DELAY ENABLED (1 MAXIMUM) OR 0.048 MAIN PC BOARD WITH AC 1 X 0.048 MPM-4 X 0.008 . 0 EOL RELAYS X 0 SMOKE DETECTORS X 0.002 • 0 SMOKE DETECTORS X 0 EOL RESISTERS X 0 . 0 ANNUNCIATORS X 0 AUXILARY DEVICES % 0 AUXILARY DEVICES X 0 AUXILARYDEVICES X 0 SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALNUTIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND S2 FOR THE FOLLOWING BATTERY CALCULATION STANDBY LOAD x REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOURS 2880 0.048 60 X 0.002 • ALARM LOAD REQUIRED STANDBYTIME IN HOURS CURRENT AMPS ICE 5 MIN.• 0.084 HOURS THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0 084 0.143 ADD STANDBY ANDAURM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.626 tUAIItKYWFIFULU B.OAMPHOUR ITERY CALCULATIONS TYP A4CP #5 EXTERNAL DEVICE POWER E FCPS PROVIDES FILTERED 24VDC POWER THAT MAY 8 T BE USED FOR OPERATING NOTIFICATION CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL E E N I ICES IS LIMITED. USE TABLE SI STANDBY OR NONALARM ANDTABLE S 2 (ALARM) TO 1 1 U ) 'ERMINE IF EXTERNAL LOADING IS WITHIN 1 I THE CAP B LILIES OF THE POWER SUPPLY. ER TO THE DEVICE MANUFACTURE'S DATA SHEETS ET PACKAGE WITH EACH DEVICES TO FIND ANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW 9W ffAAMWLE'l A9fflMftDE THE TOTAL STANDBY CURRENT RA D W OF ALL DEVICES EACH WE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. CURRENT DEVICE TYPE MOF DEVICES TOTAL � H (AMP) AMPS IN PC BOARD WITHOUTAC X 0.032 .REPORT DELAY ENABLED (1 MAXIMUM) . 0.048 IN PC BOARD WITH AC 1 X 0.048 mrm-9 X U.W6 . U EOL RELAYS X . 0 2.880 SMOKE DETECTORS X 0.002 • 0 THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION SMOKE DETECTORS X . 0 3.023 EOL RESISTERS X 0 . 0 3.628 ANNUNCIATORS X 0 THE AUXILARY DEVICES X 0 DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES AUXILARY DEVICES X . 0 ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. AUXILARY DEVICES X . 0 CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOU SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES 5.1 AND 5-2 FOR THE FOLLOWING BATTERY CALCULATION STANDBYLOAD X REQUIRED STANDBYTIME IN HOURS CURRENT AMPS 24OR60HOUR5 2.880 0.048 60 S.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS ICE 5 MIN. 0.084 HOURS THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATrERYSUPPUED &OAMPHOUR SCOPE OF WORK TABLE 5 -1: LOAD IN ALARM @ 24VDC ME 5-1: LOAD IN STANDBY @ 24VDC DNDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND S2 THE FOLLOWING BATTERY CALCULATION STANDBY LOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AM 24OR60HOUR5 sATTERY K CALCULAMONS TYP A- P 92 CURRENT CALCULATIONS S.0 EXTERNAL DEVICE POWER 1. WHEN USING TH E 6.0 AMPS MAXIMUM CURRENT AVAILABLE: THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 3DAH OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AN CAPACITY MUST SUPPORT THE FCPS WRING ITS REQUIRE APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL STANDBY TIME. BECAUSE OF THIS AN R THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES UST DEVICES IS UNITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE S2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTIES OF THE POWER SUPPLY. 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.166A) • 336AH STANDBY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIM E, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.0664) • 3.96AH ON EACH 3 STANDBY CURRENT CALCUUTION ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3) STANDBY CURRENT CALCULATION CURRENT TOTAL SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY O CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOU DEVICE TYPE N OF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRM ENTS ARE FOR GREATER THAN 7A AH: FAIL REPORT DELAY ENABLED 1MAXIMUM CUT FCPS JUMPER 1P1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY MPM-4 X 0.008 • 0 CHARGER. MPM-4 X 0.008 . 0 VDC 124 HOURS X 0.166A) • 3.96AH EOL RELAYS X 0 SMOKE DETECTORS X 0.002 • 0 q&[15M LEYAff6&*&DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f1k9bKOM1Vtl"fA1fLE9W&DL tt1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES CURRENT iHCYVLEWVU417iBLC3flFf&L bDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES TOTAL N OF DEVICES DEVICE TYPE N OF DEVICES k_� (AMP) k_� SMOKE DETECTORS X 0 OF ADVANCED FIRE & SMOKE DETECTORS X 0 AMPS I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 AMPS MAIN PC BOARD WITHOUT AC % 0.032 EOL RESISTERS X 0 0 ANNUNCIATORS X 0 MAIN PC BOARD WITHOUT AC X 0.032 AMPS FAIL REPORT DELAY ENABLED (1 MAXIMUM) OR . 0.048 AUXILARY DEVICES X 0 OR • 0048 MAIN PC BOARD WITH AC 1 X 0.048 AUXILARY DEVICES X 0 MAIN a BOARD WITH AC 1 % 0.048 FAIL REPORT DELAY ENABLED 1 MAXIMUM AUXIURY DEVICES X 0 SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC ME 5-1: LOAD IN STANDBY @ 24VDC DNDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND S2 THE FOLLOWING BATTERY CALCULATION STANDBY LOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AM 24OR60HOUR5 2880 0.048 60 .0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AM ICE 5 MIN.- 0.084 HOURS THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF L2 0 605 TOTALAMPERE HOURS AH REQUIRED 3.628 BATTERY5UPFULD BAAMPHOUR CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: .0 EXTERNAL DEVICE POWER FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES NT EQ RE53.0 AH OF AH THE FCPS PROVIDE FIT 4 S FILTERED VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AN CAPACITY CITY UST SUPPORT THE FCPS DURING ITS REQUIRED QU APPLIANCE PLI VICE CIRCURE OR OTHER EXTERNAL DEVICES. TH POWER FOR OPERATING EXTER E VIAL STANDBY TIME BECAUSE OF THIS THE STANDBY CURR NT E DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLES (STANDBY NOSY OR NONALARM) AND TABLE S2(AURM)TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBILMES OF THE POWER SUPPLY. BELOW: REFER TO THE DEVICE MANUF R ACLU EY DATA SHEETS PACKAGE WITH EACH DEVK2ST0 FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.166A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW 2 FOR 60 HOUR STANDBY TIME THE STANDBY CURRENT DRAW CANNOT EXCEED 0066 AMPS AT 24 1 fF##dQEd6SIF1'LE.10D91F(LY'(1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.0664) • 3.96AH ON EACH VDC (60 HOURS X 0.066A) .3.96AH ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3 STANDBY CURRENT CALCUUTION CFIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. SUBTRACT TOTAL STAN DBY LOAD CALCULATED A80VE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE NOF DEVICES (AMP) I IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS IS LESS THAN ZERO, THE REQUIRED STANDBYTIME WILL NOT BE ACHIEVED. MAIN PC BOARD WITHOUT AC X 0.032 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR 0.04E USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: FAIL REPORT DELAY ENABLED IMAXIMUM CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY L REPORT DELAY ENABLED (I MAXIMUM) CHARGER MPM-4 X 0.008 • 0 CHARGER EOL RELAYS X • 0 SMOKE DETECTORS X 0.002 • 0 VDC 124 HOURS X 0.166A) • 3.96AH RELAYS X . 0 OKE DETECTORS % 0.002 • 0 q&[15M LEYAff6&*&DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f1k9bKOM1Vtl"fA1fLE9W&DL tt1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES TOTAL iHCYVLEWVU417iBLC3flFf&L bDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES DEVICE TYPE N OF DEVICES �_l CURRENT (AMP) k_� (AMP) k_� SMOKE DETECTORS X 0 OF ADVANCED FIRE & OKE DETECTORS % 0 AMPS I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 MAIN PC BOARD WITHOUT AC % 0.032 RESISTERS X 0 • 0 NNUNCIATORS % 0 FAIL REPORT DELAY ENABLED (1 MAXIMUM) AMPS AUXILARY DEVICES % 0 OR . 0.048 UXIURY DEVICES % 0 AUXILARY DEVICES X • 0 MAIN PC BOARD WITH AC 1 X 0.048 AUXIURY DEVICES X 0 AUXILARY DEVICES X . 0 FAIL REPORT DELAY ENABLED 1 MAXIMUM UXIURY DEVICES X 0 SUM COLUMN FOR STANDBY LOAD . 0 048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS TABLE S-1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALNUTIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES 5-1 AND 5.2 FOR THE FOLLOWING BATTERY CALCULATION MPM-4 X 0.008 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND 5.2 FORTHE FOLLOWING BATrERYCALCULATION EOL RELAYS X 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS INTABLLSSI AND S2 FOR THE FOLLOWING BATTERY CALCULATION SMOKE DETECTORS X 0 002 0 TOTAL SMOKE DETECTORS X 0 MPM-4 X 0.008 0 EOL RESISTERS X 0 0 (AMP) NOTIFICATION APPLIANCE 16 X 0 023 0.368 SMOKE DETECTORS X 0.002 0 STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS 2.860 NOTIFICATION APPLIANCE 10 X 0.088 0.68 NOTIFICATION APPLIANCE 11 X 0.05 0.55 0.048 60 NOTIFICATION APPLIANCE 4 X 0.12 0.48 DEVICE TYPE ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 1 E 5 MIN.- 0.084 HOURS NOTIFICATION APPLIANCE X 0 NOTIFICATION APPLIANCE 1 X 0.05 0.05 NOTIFICATION APPLIANCE X 0 0.048 60 1.708 X 0084 0.143 AUXIURYDEVICES X 0 AMPS ADO STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 SUM COLUMN FOR STANDBY LOAD 2.326 AMPS IMULTIPLYBYTHE DERATINGFACrOROF1.2 • 0.605 TABLE 5 -1: LOAD IN ALARM @ 24VDC TOTAL AMPERE HOURS AH REQUIRED 3.628 BATTERYSUPPUED B.OAMPHOUR TABLE 5 -1: LOAD IN ALARM @ 24VDC ME 5-1: LOAD IN STANDBY @ 24VDC DNDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 THE FOLLOWING BATTERY CALCULATION STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS TTERY CALCULATIONS TYP A4CP 03 CURRENT CALCULATIONS .0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 8 X 0.088 FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 3.0 AH OF A 7.0 AH E FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED PWNCEaRNITEOR OTHER EX TERMAL DEVICES. THE POWER FOR OPERATING DMRNAL STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES USTE EVICES IS LIMITED. USE TABLE SI (STANDBY OR NONALARM) AND TABLE 5-2 (ALARM) TO BELOW: ETERMINE IF EXTERNAL LOADING tS WITHIN THE CAPIBILRIES OF THE POWER SUPPLY. 0 FER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND I) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.266 AMPS AT 24 E VDC (24 HOURS X 0.1664) • 3.96AH ANOSY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIM E, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AM PS AT 24 L'CYI YrtYl(JDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A) .3.96AH N EACH AUXILARY DEVICES CFIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3 STANDBY CURRENT CALCULATION ) DEVICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE 5-2 (ALARM) TO SUBTRACTTOTALSTANDBYLOADCALCULATEDABOVEFROMO .166AMP5FOR24HOUR55TANDBYOR CURRENT TOTAL 0.066 AMPS FOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE N OF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBYTIME WILL NOT BE ACHIEVED. AMPS DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTIES OF THE POWER SUPPLY. N PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: L REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.0 AH: AIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: L REPORT DELAY ENABLED (I MAXIMUM) CUT FOPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY .NDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW CHARGER MPM4 X 0.008. 0 VDC 124 HOURS X 0.166A) • 3.96AH RELAYS X . 0 OKE DETECTORS % 0.002 • 0 q&[15M LEYAff6&*&DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f1k9bKOM1Vtl"fA1fLE9W&DL tt1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES CURRENT iHCYVLEWVU417iBLC3flFf&L bDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES TOTAL VDC (60 HOURS X 0.066A) • 3.96AH DEVICE TYPE N OF DEUCES k_� (AMP) k_� CURRENT OF ADVANCED FIRE & OKE DETECTORS % 0 BE USED OR DUPLICATED BY I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 3) STANDBY CURRENT CALCULATION RESISTERS X 0 • 0 NNUNCIATORS % 0 MAIN PC BOARD WITHOUTAC X 0.032 AMPS FAIL REPORT DELAY ENABLED (1 MAXIMUM) 3) STANDBY CURRENT CALCULATION UXIURY DEVICES % 0 OR . 0.048 NOF DEVICES AUXIURY DEVICES X 0 MAIN PC BOARDWITHAC 1 X 0.048 AUXIURY DEVICES X • 0 UXIURY DEVICES X 0 FAIL REPORT DELAY ENABLED 1 MAXIMUM FAIL REPORT DELAY ENABLED 1 MAXIMUM SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC ME 5-1: LOAD IN STANDBY @ 24VDC DNDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 THE FOLLOWING BATTERY CALCULATION STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS RRENT AMPS ICE 5 MIN.- 0.084 HOURS 8 X 0.088 1.708 X 0.084 0.143 DD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 ULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTALAMPERE HOURS AH REQUIRED 3.628 BATTERYSUPPUED B.OAMPHOUR � � � � � BATTERY CALCULATIONS TYP A4CP Rl CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 8 X 0.088 FIVE MINUTES UNDER FULL LOAD 6.OAMPS CURRENT DRAW) REQUIRES 3.OA OF A AH ( W) CU H 70 THE FCPS PROVIDES FILTERED 24 VDC POWER THAT MAY BE USED FOR OPERATING NOTFICA TK)N CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE DURING REQUIRED FCPS ITS EQV RFD APPLIANCE CIRCUITE R LIA ITEO OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE 5-2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAMBIUTIES OF THE POWER SUPPLY. 0 REFER TO THE DEVICE MANUFACTURE'S ATA H A D SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBYTIME, THE STANDBY CURRENT DRAW CANNOT EXCEED O.166AMPS AT 24 THE VDC (24 HOURS X 0.166A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 b;EgbK15 LE9A% 8V&& ItIJDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A).3.96AH ON EACH AUXILARY DEVICES ACTIVE OUTPUT, INCLUDUNG END OF UNE RELAYS WHEN USED FOR SUPERVISION. 3 1 STANDBY CURRENT CALCULATION DEVICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE 5-2 (ALARM) TO SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT R OT BELESSTHANZE O, IFTHEAMOUNT DEVICE TYPE N OF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTIES OF THE POWER SUPPLY. MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SITE OR . 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.0 AH: MAIN PC BOARD WITH AC 1 % 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: FAIL REPORT DELAY ENABLED (I MAXIMUM) CUT FCPS JUMPER JP1 TO DISABLE ON BOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY .NDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW CHARGER MPM-4 X 0.008 • 0 VDC 124 HOURS X 0.166A) • 3.96AH EOL RELAYS % 0 SMOKE DETECTORS X 0.002 . 0 q&[15M LEYAff6&*&DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f1k9bKOM1Vtl"fA1fLE9W&DL tt1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES CURRENT iHCYVLEWVU417iBLC3flFf&L bDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES TOTAL VDC (60 HOURS X 0.066A) • 3.96AH DEVICE TYPE N OF DEVICES � k_� (AMP) k_� CURRENT OF ADVANCED FIRE & SMOKE DETECTORS X . 0 BE USED OR DUPLICATED BY I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 3) STANDBY CURRENT CALCULATION EOL RESISTERS X 0 . 0 ANNUNCIATORS X 0 MAIN PC BOARD WITHOUT AC X 0.032 AMPS FAIL REPORT DELAY ENABLED (1 MAXIMUM) 3) STANDBY CURRENT CALCULATION AUXILARY DEVICES X 0 OR . 0.048 NOF DEVICES AUXILARY DEVICES X . 0 MAIN PC BOARD WITH AC 1 X 0.048 AUXIURY DEVICES X • 0 AUXILARY DEVICES X . 0 SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM CURRENT TOTAL AUXILARY DEVICES X 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND 5.2 FORTHE FOLLOWING BATrERYCALCULATION MPM-4 X 0.008 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS INTABLLSSI AND S2 FOR THE FOLLOWING BATTERY CALCULATION EOL RELAYS X 0 TOTAL SMOKE DETECTORS X 0.002 0 MPM-4 X 0.008 0 SMOKE DETECTORS X 0 (AMP) EOL RESISTERS X 0 0 SMOKE DETECTORS X 0.002 0 NOTIFICATION APPLIANCE 26 X 0.023 0.598 5.0 EXTERNAL DEVICE POWER NOTIFICATION APPLIANCE 8 X 0.088 0.704 0.143 NOTIFICATION APPLIANCE 2 X 0.05 0.1 0.605 NOTIFICATION APPLIANCE X 0 iFCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION NOTIFICATION APPLIANCE X 0 THE FCPS PROVIDES FILTERED 24VOC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION NOTIFICATION APPLIANCE X 0 CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED AUXILARY DEVICES X 0 DEVICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE 5-2 (ALARM) TO STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES USTED SUM COLUMN FOR STANDBY LOAD . 1.45 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STAND BY TIME IN HOURS CURRENT AM ICE 5 MIN.. 0.084 HOURS EXTERNAL DEVICE POWER 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 t5A11tKT5UPPULV B.OAMPHOUK rTERY CALCULATIONS TYP A-ICP N9 2.880 BATTERY CALCULATIONS TYP A4CP 810 5.0 EXTERNAL DEVICE POWER BATTERY CALCULATIONS TYP A4CP 931 EXTERNAL DEVICE POWER CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER MULTIPLY BY THE DERATING FACTOR OF 1.2 1. WHEN USING THE &O AMPS MAXIMUM CURRENT AVAILABLE: TOTALAMPEREHOURS AH REQUIRED 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 iFCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 3.0 AH OFA7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAIN REQUIRES 3.0 AN OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VOC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 'LIANCE CIRCURE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED APPLIANCE CIRCURE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL 'ICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) AND TABLE 5-2 (ALARM) TO STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT OCCEEDTHE FIGURES LISTED DEVICES IS LIMITED. USE TABLE Sl (STANDBY OR NONALARM) ANDTABLE 5-2 (ALARM) TO STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES USTED DEVICES 15 LIMITED. USE TABLE Sl (STANDBY OR NONALARM) AND TABLE S2 (ALARM) TO 'ERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIlJITES OF THE POWER SUPPLY. BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPABILITIES OF THE POWER SUPPLY. BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTIES OF THE POWER SUPPLY. ER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.0 AH: 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE .NDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW VDC (24 HOURS X 0.166A) . 3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW VDC 124 HOURS X 0.166A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW q&[15M LEYAff6&*&DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f1k9bKOM1Vtl"fA1fLE9W&DL tt1DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 iHCYVLEWVU417iBLC3flFf&L bDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES EACH VDC (60 HOURS X 0.066A) • 3.96AH ON EACH VDC (60 HOURS X 0.066A) • 3.96AH ON EA04 IVE OUTPUT, INCLUDING END OF LINE RELAYS WHEN USED FOR SUPERVISION. k_� ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. OF ADVANCED FIRE & ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. BE USED OR DUPLICATED BY I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 3) STANDBY CURRENT CALCULATION EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 EOL RESISTERS X 0 . 0 ..... ANNUNCIATORS % 0 MAIN PC BOARD WITHOUT AC X 0.032 AMPS FAIL REPORT DELAY ENABLED (1 MAXIMUM) 3) STANDBY CURRENT CALCULATION AUXIURY DEVICES X 0 DEVICE TYPE NOF DEVICES CURRENT TOTAL AUXIURY DEVICES X • 0 SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR DEVICE TYPE NOF DEVICES CURRENT TOTAL AUXILARY DEVICES X 0 SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR MPM-4 X 0.008 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS INTABLLSSI AND S2 FOR THE FOLLOWING BATTERY CALCULATION CURRENT TOTAL SMOKE DETECTORS X 0.002 0 MPM-4 X 0.008 0 SMOKE DETECTORS X 0 (AMP) RIM SMOKE DETECTORS X 0.002 0 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT SMOKE DETECTORS X 0 (AMP) NOTIFICATION APPLIANCE 48 X 0.023 1.104 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE III OF DEVICES (AMP) NOTIFICATION APPLIANCE 1 X 0.05 0.05 0.048 60 NOTIFICATION APPLIANCE X 0 AMPS NOTIFICATION APPLIANCE X 0 IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. NOTIFICATION APPLIANCE % 0 1.708 X 0.084 0.143 AMPS IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. SUM COLUMN FOR STANDBY LOAD 1.73 AMPS MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TABLE 5 -1: LOAD IN ALARM @ 24VDC AMPS BATTERYSUPPUED B.OAMPHOUR IN PC BOARD WITHOUTAC X 0.032 MAIN PC BOARD WITHOUT AC X 0.032 MAIN PC BOARD WITHOUT AC % 0.032 . REPORT DELAY ENABLED (1 MAXIMUM) 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (I MAXIMUM) 2. WHEN USING LESS THAN 6.OAMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) . 0.048 USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE. OR . 0.048 USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR 0.048 IN PC BOARD WITH AC 1 X 0.048 MAIN PC BOARD WITH AC 1 % 0.048 MAIN PC BOARD WITH AC 1 % 0.048 . REPORT DELAY ENABLED (I MAXIMUM) 3. WHEN BATTERY AMP -HOUR REQUIRMENTSARE FOR GREATERTHAN 7.OAH: FAIL REPORT DELAY ENABLED (I MAXIMUM) 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.OAH: FAIL REPORT DELAY ENABLED (I MAXIMUM) CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY M-4 X 0.008 . 0 CHARGER MPM4 X 0.008 . 0 CHARGER MPM4 X 0.008 • 0 . RELAYS % 0 EOL RELAYS X 0 EOL RELAYS X . 0 OKE DETECTORS X 0.002 0 CURRENT TOT)- SMOKE DETECTORS X 0.002 • 0 TOTAL SMOKED ETECTORS % 0.002 • 0 DICE DETECTORS X 0 DEVICE TYPE N 01 DEVICES (AMP) SMOKE DETECTORS X 0 DEVICE TYPE N OF DEVICES CURRENT SMOKE DETECTORS X 0 . RESISTERS X 0 . 0 AMPS EOL RESISTERS X 0 . 0 (AMP) AMPS EOL RESISTERS X 0 . 0 4UNCIATORS X 0 MAIN PC BOARD WITHOUT AC X 0.032 ANNUNCIATORS % 0 MAIN PC BOARD WITHOUTAC X 0.032 ANNUNCIATORS X 0 KIURY DEVICES X 0 FAIL REPORT DELAY ENABLED (I MAXIMUM) AUXILARY DEVICES X 0 FAIL REPORT DELAY ENABLED (1 MAXIMUM) AUXILARY DEVICES X 0 KDEVICES RY DEVICES X 0 OR . 0.048 AUXILARY DEVICES X 0 OR . 0.048 AUXILARY DEVICES % 0 KIURY DEVICES X 0 MAIN PC BOARD WITH AC 1 X 0.048 AUXILARY DEVICES X 0 MAIN PC BOARD WITH AC 1 X 0.048 AUXILARY DEVICES % 0 SUM COLUMN FOR STANDBY LOAD . 0 048 AMPS FAIL REPORT DELAY ENABLED I MAXIMUM SUM COLUMN FOR STANDBY LOAD • 0.048 A IFAIL REPORT DELAY ENABLED I MAXIMUM SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS BLE 5 -1: LOAD IN STANDBY @ 24VDC TABLE 5 -1: LOAD IN STANDBY @ 24VDC TABLE 5 -1: LOAD IN STANDBY @ 24VDC MPM-4 X 0.008 0 :ONDARY POWER SOURCE CALCULATIONS EOL RELAYS X 0 SECONDARY POWER SOURCE CALCULATIONS MPM-4 % 0.008 0 EOL RELAYS % 0 SECONDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 SMOKE DETECTORS X 0.002 0 USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 SMOKE DETECTORS X 0.002 0 USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES SI AND S2 t THE FOLLOWING BATTERY CALCULATION SMOKE DETECTORS % 0 FOR THE FOLLOWING BATTERY CALCULATION SMOKE DETECTORS X 0 FOR THE FOLLOWING BATTERY CALCULATION STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOURS 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS ICE 5 MIN.- 0.094 HOURS THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0 605 TOTALAMPEREHOURS AH REQUIRED 3628 BATTERYSUPPUED &OAMPHOUR DNS BATTERY CALCULATIONS TYP A-ICP NU 5.0 EXTERNAL DEVICE POWER THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL DEVICES IS LIMITED. USE TABLE Sl STANDBY OR NONALARM AND TABLE S2 TO ( I (ALARM) DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTES OF THE POWER SUPPLY. REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND THE STANDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW fAC0NG5MMWLRAffffltP#ftDE THE TOTAL STANDBY CURRENT DRAWOF ALL DEVICES ON EACH ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. DEVICE TYPE NOF DEVICES CURRENT TOTAL � H � (AMP) AMPS MAIN PC BOARD WITHOUTAC X 0.032 FAIL REPORT DELAY ENABLED (IMAXIMUM) OR . 0.048 MAIN PC BOARD WITH AC 1 X 0.048 Ni A U.UUB . U RELAYS X 0 )KE DETECTORS X 0.002 • 0 )KE DETECTORS % . 0 RESISTERS X 0 . 0 IUNCWTORS X 0 1LARY DEVICES X 0 :ILARY DEVICES X 0 IILARY DEVICES X 0 SUM COLUMN FOR STANDBYLOAD . 0.048 AMPS KE 5 -1: LOAD IN STANDBY @ 24VDC ONDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND 5-2 THE FOLLOWING BATTERYCALCULATKON STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOUR5 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBYTIME IN HOURS CURRENT(AMPS) .E 5 MIN OJ)84 HOURS THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3 023 MULTIPLY BY TH E DERATING FACTOR OF 1.2 0 605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATrERYSUPPUED &OAMPHOUR DNS TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBY LOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOUR5 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AM LE 5 MIN.- 0.084 HOURS THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION L708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATTLRT5UPPUED 8.OAMPHOUR DNS __ TABLE 5 -1: LOAD IN ALARM @ 24VDC TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES 5-1 AND 5-2 FOR THE FOLLOWING BATTERY CALCULATION STANDBYLOAD x REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS BATTERY CALCULATIONS TYP A4CP 914 CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT V AVAILABLE: THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 3.OAH OF A 7.0 AN THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AN CAPACITY CtrY UST SUPPORT FCPS DURING RS REQUIRED QU APPLIANCE CIRCUITE R 0 OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING FJ(TERNAL STANDBY TIME. BECAUSE OF THIS THE STANDBY OBY CURRENT DRAW CANNOT IXCEEDTHE FIGURES LASTED DEVICES IS LINKED. U TABLE BLE Sl STANDBY OR NO NAIARM ANDTABLE S2 ALARM TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPISILITIES OF THE POWER SUPPLY. 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED M166 AMPS AT 24 THE VDC (24 HOURS X 0.166A). 336MI STANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPSAT 24 fA4b9AkA>;TJMk9WM9PR&%DE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A) • 396AH ON EACH 3) STANDBY CURRENT CALCULATION ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3) STANDBY CURRENT CALCULATION CURRENT TOTAL SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE NOF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR . 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.0 AH: MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: FAIL REPORT DELAY ENABLED 1MAXIMUM CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY MPM4 X 0.008 • 0 CHARGER MPM-4 X 0.008 • 0 CHARGER EOL RELAYS X 0 SMOKE DETECTORS X 0.002 • 0 1.482 CURRENT TOTAL CURRENT DEVICE TYPE TOTAL DEVICE TYPE N OF DEVICES 1 k_� (AMP) k_� AMPS OF ADVANCED FIRE & SMOKE DETECTORS X 0 BE USED OR DUPLICATED BY I AMPS MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 FAIL REPORT DELAY ENABLED (1 MAXIMUM) EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 EOL RESISTERS X 0 . 0 ..... ANNUNCIATORS % 0 MAIN PC BOARD WITHOUT AC X 0.032 AMPS FAIL REPORT DELAY ENABLED (1 MAXIMUM) MAIN PC BOARD WITH AC 1 X 0.048 AUXIURY DEVICES X 0 OR 0.048 FAIL REPORT DELAY ENABLED 1 MAXIMUM 1 AUXIURY DEVICES X 0 MAIN PC BOARD WITH AC 1 % 0.048 AUXIURY DEVICES X • 0 AUXIURY DEVICE X . 0 SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS FAIL REPORT DELAY ENABLED I MAXIMUM SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES 5-1 AND 5-2 FOR THE FOLLOWING BATTERY CALCULATION STANDBYLOAD x REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24 OR 60 HOURS 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AM ICE 5 MIN.- 0.084 HOURS THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 DADS TOTAL AMPERE HOURS AH REQUIRED 3.628 TABLE BATrERYSUPPUED B.OAMPHOUR TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AM 24 OR 60 HOURS 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS LE 5 MIN.- 0.084 HOURS THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATrERYSUPPUED B.OAMPHOUR DNS CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 5.0 EXTERNAL DEVICE POWER FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAMA) REQUIRES 3.0 AN OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE F I REQUIRED E CPS DURING fTS RE ED QU APPLIANCE CIRCUITE OR OTHER R EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLE 5-2 (STANDBY OR NONALARM) AND TABLE 5-2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBtUT1ES OF THE POWER SUPPLY. TOTALAMPERE HOURS AH REQUIRED REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC 124 HOURS X 0.166A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f E> LRAkF&TCP#&LDE THE TOTAL STAN DBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A) • 3.96AH ON EACH VDC (60 HOURS X 0.066A) • 3.96AH ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3) STANDBY CURRENT CALCULATION ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE NOF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR . 0.048 USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.0 AH: FAIL REPORT DELAY ENABLED 1 MAXIMUM CUT FCPS JUMPER 1P1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY FAIL REPORT DELAY ENABLED 11 MAXIMUM CHARGER MPM4 X 0.008 • 0 CHARGER EOL RELAYS X . 0 SMOKE DETECTORS X 0.002 . 0 CHARGER EOL RELAYS X • 0 SMOKE DETECTORS X 0.002 • 0 1.482 CURRENT TOTAL f U DEVICE TYPE N OF DEVICES (AMP) N OF DEVICES DEVICE TYPE SMOKE DETECTORS % 0 k_� AMPS OF ADVANCED FIRE & SMOKE DETECTORS X 0 BE USED OR DUPLICATED BY SMOKE DETECTORS X 0 EOL RESISTERS X 0 • 0 ANNUNCIATORS % 0 MAIN PC BOARD WITHOUTAC X 0.032 EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 FAIL REPORT DELAY ENABLED (1 MAXIMUM) EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 JAUXILARYDEVICES % 0 OR 0.048 AMPS AUXILARYDEVICES X :I- MAIN PC BOARD WITH AC 1 X 0.048 AUXILARY DEVICES X 0 AUXILARYDEVICES X 0 FAIL REPORT DELAY ENABLED 1 MAXIMUM AUXILARYDEVICES X 0 SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC ILE 5 -1: LOAD IN STANDBY @ 24VDC DNDARY POWER SOURCE CALCULATIONS THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 THE FOLLOWING BATTERY CALCULATION STANDBY LOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOUR5 2.880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS I E 5 MIN.- 0 084 HOURS 3 X 0.088 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 060S TOTALAMPERE HOURS AH REQUIRED 3628 BATTERY CALCULATIONS SCALE: N.T.S. BATTERYSUPPLIED S.OAMPHOUR NOTIFICATION APPLIANCE BATTERY CALCULATIONS TYP A KZ° 94 CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER L WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 3 X 0.088 FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 34 AH OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FOPS DURING ITS REQUIRED APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLE 5-1 (STANDBY OR NONALARM) AND TABLE 5-2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUTIES OF THE POWER SUPPLY. 0 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH UCH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.166A) .3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW 2) FO R 60 HOUR STAN DBY TIM E, TH E STAN DBY CU RRENT DRAW CANNOT EXCEED 0.066 AM PS AT 24 f4E0kqWT0WLF4V&FCOIftJ DETHETOTALSTANDBYCURRENT DRAWOFALL DEVICES VDC (60 HOURS X 0.066A) • 3.96AH ON EACH AUXILARY DEVICES ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3 ) STANDBY CURRENT CALCULATION ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. SUSTRACTTOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BELESS THAN ZERO, IF THE AMOUNT DEVICE TYPE ROE' DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.OAMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE OR . 0.048 USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SCE MAIN PC BOARD WITH AC I X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.OAH: FAIL REPORT DELAY ENABLED 11 MAXIMUM CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY FAIL REPORT DELAY ENABLED 1 MAXIMUM CHARGER MPM-4 X 0.008 • 0 CHARGER EOL RELAYS X • 0 SMOKE DETECTORS X 0.002 • 0 1.482 EOL RELAYS X . 0 SMOKE DETECTORS X 0.002 • 0 % f U 0 TOTAL DEVICE TYPE N OF DEVICES DEVICE TYPE CURRENT k_� CURRENT OF ADVANCED FIRE & SMOKE DETECTORS X 0 BE USED OR DUPLICATED BY SMOKE DETECTORS X 0 (AMP) SECURITY INC. EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 manner by owner, its agents or by any third party if construction is not in EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 AMPS MAIN PC BOARD WITHOUT AC X 0.032 AMPS FAIL REPORT DELAY ENABLED (I MAXIMUM) AUXILARY DEVICES X 0 OR . 0.048 AUXILARYDEVICES X 0 AUXILARYDEVICES X 0 MAIN PC BOARD WITH AC 1 X 0.048 AUXIURY DEVICES X • 0 AUXILARY DEVICES % 0 SUM COLUMN FOR STANDBY LOAD . 0.048 AMPS FAIL REPORT DELAY ENABLED I MAXIMUM SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM AUXILARY DEVICES X 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS IN TABLES STAND 5-2 FOR THE FOLLOWING BATTERY CALCULATION MPM-4 X 0.008 0 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS INTABLLSSI AND S2 FOR THE FOLLOWING BATTERY CALCULATION EOL RELAYS X 0 SCALE: SMOKE DETECTORS X 0.002 0 MPM-4 X 0.008 0 SMOKE DETECTORS X 0 EOL RELAYS % 0 EOL RESISTERS X 0 0 SMOKE DETECTORS X 0.002 0 NOTIFICATION APPLIANCE 46 X 0.023 1.058 BATTERY CALCULATIONS TYP A-ICP 08 NOTIFICATION APPLIANCE 3 X 0.088 0.264 0.143 NOTIFICATION APPUA.NCE 4 X 0.05 0.2 0.605 NOTIFICATION APPLIANCE % 0 DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBILITIES OF THE POWER SUPPLY. NOTIFICATION APPLIANCE X 0 THE NOTIFICATION APPLIANCE X 0 fFPkK18VT LR%% MAWGDETHETOTALSTANDBYCURRENT DRAWOFALL DEVICES AUXILARY DEVICES X 0 ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3 ) STANDBY CURRENT CALCULATION SUM COLUMN FOR STANDBY LOAD . 1.57 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBY LOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOURS 2880 0.048 60 BATTERY CALCULATIONS TYP A-ICP 08 ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS LE 5 MIN.- 0.084 HOURS .0 A S EXTERNAL 1.708 X 0 084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATTERYSUPPLIED &OAMPHOUR NOTIFICATION APPLIANCE TABLE 5 -3: SECONDARY POWER SOURCE CALCULATIONS 0.598 BATTERY CALCULATIONS TYP A-ICP 08 CURRENT CALCULATIONS .0 A S EXTERNAL 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 0.143 FIVE MINUTES UNDER FULL LOAD 6.0 AMPS CURRENT DRAW) RE AAH 1 W) OUOtE53 OFA7.0 AH THE FCPS PROVIDES FILTERED 4 l ED2 VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY UST SUPPORT TTY RTTHE FCPS DURING ITS REQUIRED Q APPLIANCE CIRCUITE E C NITS OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING RN FXTE AL STANDBY TIME BECAUSE OF THIS THE STANDBY CURRENT DRAW CANNOT IXCEEDTHE FIGURES LISTED DEVICES IS LIMITED. USE TABLE 5-1 (STANDBY OR NONALARM) AND TABLE 5-2(AURM)TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBILITIES OF THE POWER SUPPLY. NOTIFICATION APPLIANCE REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.166A). 3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLES THAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 fFPkK18VT LR%% MAWGDETHETOTALSTANDBYCURRENT DRAWOFALL DEVICES VDC (60 HOURS X 0.066A) • 3.96AH ON EACH 0 ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3 ) STANDBY CURRENT CALCULATION SUM COLUMN FOR STANDBY LOAD . SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066 AMPS FOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE N OF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: MAIN PC BOARD WITHOUT AC X 0.032 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SCE OR . 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7A AH: FAIL REPORT DELAY ENABLED 1 MAXIMUM CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY MPM4 X 0.008 • 0 CHARGER MPM4 X 0.008 • 0 1.482 EOL RELAYS X . 0 SMOKE DETECTORS X 0.002 • 0 % f U 0 TOTAL TOTAL N OF DEVICES DEVICE TYPE k OF DEVICES k_� CURRENT OF ADVANCED FIRE & SMOKE DETECTORS X • 0 BE USED OR DUPLICATED BY SMOKE DETECTORS X 0 ( AMP) SECURITY INC. (AMP) manner by owner, its agents or by any third party if construction is not in EOL RESISTERS X 0 • 0 ANNUNCIATORS X 0 AMPS MAIN PC BOARD WITHOVTAC X 0.032 AMPS MAIN PC BOARD WITHOUT AC X 0.032 FAIL REPORT DELAY ENABLED (1 MAXIMUM) MAIN PC BOARD WITHOUT AC X 0.032 AUXILARYDEVICES X 0 OR . 0.048 MAIN PC BOARD WITH AC 1 X 0.048 AUXIURY DEVICES X • 0 MAIN PC BOARD WITH AC 1 X 0.048 SUM COLUMN FOR STANDBY IDAD 0.048 AMPS AUXIURY DEVICES X • 0 SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM AUXILARY DEVICES X 0 SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS FAIL REPORT DELAY ENABLED (I MAXIMUM) TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS INTABLLSSI AND S2 FOR THE FOLLOWING BATTERY CALCULATION MPM-4 X 0.008 0 SCALE: EOL RELAYS X 0 MPM-4 X 0.008 0 SMOKE DETECTORS X 0.002 0 EOL RELAYS % 0 SMOKE DETECTORS X 0 SMOKE DETECTORS X 0.002 0 EOL RESISTERS X 0 0 SMOKE DETECTORS X 0 NOTIFICATION APPLIANCE 26 X 0.023 0.598 5.0 EXTERNAL DEVICE POWER NOTIFICATION APPLIANCE 8 x 0.088 0.704 0.143 NOTIFICATION APPLIANCE 2 X 0.05 0.1 0.605 NOTIFICATION APPLIANCE % 0 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND NOTIFICATION APPLIANCE % 0 STANDBY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW NOTIFICATION APPLIANCE % 0 ON EACH AUXILARYDEVICES X 0 0.176 SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR SUM COLUMN FOR STANDBY LOAD . 1.45 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBYLOAD x REQUIRED STANDBYTIME IN HOURS CURRENT AMPS 24OR60HOURS 2880 0.048 60 5.0 EXTERNAL DEVICE POWER ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS ICE 5 MIN.- 0.084 HOURS 27 X 0.14 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BAIRKTSUPPULU B.UAMPHOUR NOTIFICATION APPLIANCE BATTERY CALCULATIONS TYP A-KP 832 CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 27 X 0.14 FIVE MINUTES UNDER FULL LOAD 16.0 AMPS CURRENT DRAW) REQUIRES 3.0 AH OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AN CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING EXTERNAL STANDBY TIME BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLE S-1 (STANDBY OR NONALARM) AND TABLE 5-2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPISIUTIES OF THE POWER SUPPLY. 0 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVICES TO FIND 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.156A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THETABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 f4E0kffWT4MLRRf81b0MDE THE TOTAL STANDBY CURRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A) • 3.96AH ON EACH AUXILARY DEVICES ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3) STANDBY CURRENT CALCULATION 0.176 SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURESHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE ROE' DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS 0.528 MAIN PC BOARD WITHOUT AC X 0.032 2. WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1 MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERYSQE. OR 0.048 NOTIFICATION APPLIANCE MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: FAIL REPORT DELAY ENABLED (I MAXIMUM) CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY X CHARGER MPM4 X 0.008 • 0 EOL RELAYS X . 0 SMOKE DETECTORS X 0.002 . 0 1.482 % f U 0 TOTAL DEVICE TYPE N OF DEVICES [�CURRENTJ CURRENT SUM COLUMN FOR STANDBY LOAD 1.577 OF ADVANCED FIRE & SMOKE DETECTORS X • 0 BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN ( AMP) SECURITY INC. EOL RESISTERS X 0 0 ANNUNCIATORS X 0 manner by owner, its agents or by any third party if construction is not in accordance with unaltered documents prepared by Advanced Fire & Security AMPS MAIN PC BOARD WITHOVTAC X 0.032 Indemnify and holds harmless Advanced Fire & Security Inc. for any and all acts FAIL REPORT DELAY ENABLED (1 MAXIMUM) EOL RESISTERS X 0 0 ANNUNCIATORS % 0 MAIN PC BOARD WITHOUT AC X 0.032 R�ItAisddr wledge the FAIL REPORT DELAY ENABLED (1 MAXIMUM) MAIN PC BOARD WITH AC 1 X 0.048 AUXILARY DEVICES X 0 OR . 0.048 SUM COLUMN FOR STANDBY IDAD 0.048 AMPS AUXILARY DEVICES X 0 MAIN PC BOARD WITH AC 1 X 0.048 LEEN B OWEAL AUXILARY DEVICES X 0 SUM COLUMN FOR STANDBY LOAD • 0.048 AMPS FAIL REPORT DELAY ENABLED (I MAXIMUM) 7120272 EOL RELAYS X 0 SCALE: TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALNUTIONS USE THE TOTAL STANDBYAND ALARM LOAD CALCULATIONS IN TABLES SI AND 5-2 FOR THE FOLLOWING BATTERY CALCULATION MPM-4 X 0.008 0 SMOKE DETECTORS % 0 EOL RELAYS % 0 EOL RESISTERS X 0 0 SMOKE DETECTORS X 0.002 0 9 of 11 SMOKE DETECTORS X 0 EOL RESISTERS X 0 0 NOTIFICATION APPLIANCE 48 X 0.023 1.104 STANDBYLOAD X REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOURS 2880 NOTIFICATION APPLIANCE 6 X 0.088 0.528 NOTIFICATION APPLIANCE 1 X 0.05 0.05 0.048 60 NOTIFICATION APPLIANCE X 0 ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS ICE S MIN.- 0.084 HOURS NOTIFICATION APPLIANCE X 0 NOTIFICATION APPLIANCE % 0 1.708 X 0.084 0.143 AUXILARY DEVICES X 0 ADD STANDBY AND ALARM LOAD FOR REQUIREDAMPERE HOURS 3.023 SUM COLUMN FOR STANDBY LOAD 1.73 AMPS MULTIPLY BY THE DERATING FACTOR OF 1.2 0.605 TABLE 5 -1: LOAD IN ALARM @ 24VDC TOTALAMPERE HOURS AH REQUIRED 3.628 BATTERYSUPPUED B.OAMPHOUR NOTIFICATION APPLIANCE BATTERY CALCULATIONS M A-I P 136 CURRENT CALCULATIONS 5.0 EXTERNAL DEVICE POWER 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: 27 X 0.14 FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 30 AH OF A 7.0 AH THE FCPS PROVIDES FILTERED 24VDC POWER THAT MAY BE USED FOR OPERATING NOTIFICATION CAPACITY BATTERY. THE REMAINIGN 4.0 AN CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED QU APPLIANCE CIRCUITE OR OTHER EXTERNAL DEVICES. THE POWER FOR OPERATING 0 ERA G EXTERNAL STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED DEVICES IS LIMITED. USE TABLE 5-1 (STANDBY OR NONALARM) AND TABLE 5.2 (ALARM) TO BELOW: DETERMINE IF EXTERNAL LOADING IS WITHIN THE CAPIBIUITES OF THE POWER SUPPLY. 0 REFER TO THE DEVICE MANUFACTURE'S DATA SHEETS PACKAGE WITH EACH DEVKiSTO FIND I) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 THE VDC (24 HOURS X 0.166A) • 3.96AH STANDBY AND ALARM CURRENT DRAW IN THE TABLESTHAT FOLLOW 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 fly#dkSW11Jt 'dG NMTd1FR'4t1DE THE TOTAL STANDBYNRRENT DRAW OF ALL DEVICES VDC (60 HOURS X 0.066A) • 3.96AH ON EACH AUXILARY DEVICES ACTIVE OUTPUT, INCLUDUNG END OF LINE RELAYS WHEN USED FOR SUPERVISION. 3) STANDBY CURRENT CALCULATION 0.176 SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR CURRENT TOTAL 0.066 AMPS FOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT DEVICE TYPE N OF DEVICES (AMP) IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. AMPS 0.528 MAIN PC BOARD WITHOUT AC X 0.032 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: FAIL REPORT DELAY ENABLED (1MAXIMUM) USE THE FOLLOWING TABLES TO DETERMINE THEPROPER BATTERYSI E OR • 0.048 NOTIFICATION APPLIANCE MAIN PC BOARD WITH AC 1 X 0.048 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: FAR REPORT DELAY ENABLED 1MAXIMUM CUT FCPS JUMPER 1P1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY X CHARGER MPM4 X 0.008 . 0 EOL RELAYS X . 0 SMOKE DETECTORS X 0.002 • 0 1.482 % f U 0 TOTAL DEVICE TYPE 0 O DEVICES 0 CURRENT SUM COLUMN FOR STANDBY LOAD 1.577 OF ADVANCED FIRE & SMOKE DETECTORS X 0 BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN (AMP) SECURITY INC. EOL RESISTERS X 0 0 ANNUNCIATORS X 0 manner by owner, its agents or by any third party if construction is not in accordance with unaltered documents prepared by Advanced Fire & Security AMPS MAIN PC BOARD WITHOVTAC X 0.032 Indemnify and holds harmless Advanced Fire & Security Inc. for any and all acts FAIL REPORT DELAY ENABLED (1 MAXIMUM) This concept drawing is for information aI,tpotential system arrangement. AUXILARY DEVICES % 0 OR . 0.048 R�ItAisddr wledge the AUXIURY DEVICES X 0 MAIN PC BOARD WITH AC 1 X 0.048 . o warranty express or implied is hereby AUXILARY DEVICES X • 0 SUM COLUMN FOR STANDBY IDAD 0.048 AMPS FAIL REPORT DELAY ENABLED 1 MAXIMUM LEEN B OWEAL MISSION # EE172765 TABLE 5 -1: LOAD IN STANDBY @ 24VDC SECONDARY POWER SOURCE CALCULATIONS USE THE TOTAL STANDBY AND ALARM LOAD CALCULATIONS IN TABLES Sl AND 5-2 FOR THE FOLLOWING BATTERY CALCULATION MPM-4 X 0.008 0 7120272 EOL RELAYS X 0 SCALE: SMOKE DETECTORS X 0.002 0 AS SHOWN SMOKE DETECTORS % 0 CHECKED BY: EOL RESISTERS X 0 0 E.J.W. NOTIFICATION APPLIANCE 1 X 0.05 0.050 0 NOTIFICATION APPLIANCE 27 X 0.14 3.78 0.143 NOTIFICATION APPLIANCE X 0 0.605 NOTIFICATION APPLIANCE % 0 0 NOTIFICATION APPLIANCE X 0 0 NOTIFICATION APPLIANCE % 0 1.058 AUXILARY DEVICES % 0 0.176 NOTIFICATION APPLIANCE SUM COLUMN FOR STANDBY LOAD . 3.878 AMPS TABLE 5 -1: LOAD IN ALARM @ 24VDC STANDBYLOAD x REQUIRED STANDBY TIME IN HOURS CURRENT AMPS 24OR60HOURS 2880 0.048 60 0 ALARM LOAD REQUIRED STANDBY TIME IN HOURS CURRENT AMPS LE 5 MIN.- 0.084 HOURS X 1.708 X 0.084 0.143 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOURS 3.023 MULTIPLY BY TH E DERATING FACTOR OF 1.2 0.605 TOTAL AMPERE HOURS AH REQUIRED 3.628 BATTERY SUPPLIED 8.0 AMP HOUR CURRENT CALCULATIONS ^ 1. WHEN USING THE 6.0 AMPS MAXIMUM CURRENT AVAILABLE: ^ _ _ _ _ _ _ . FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAW) REQUIRES 3.0 AH OF A 7.0 AH ^ CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED BELOW: _.. ^^ - - - - - _^ 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED M266 AMT:: T 2f - VDC (24HOURSX0.166A)•3.96AH - 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CU RRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 ^ VDC (60 HOURS X 0.066/) • 3.96AH 3 STANDBY CURRENT CALCULATION SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. 2 WHEN USING LESS THAN &DAMPS MAXIMUM CURRENT. USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE. 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY CHARGER DEVICE TYPE T OF DEVICES CURRENT TOTAL k_� (AMP) AMPS MAINPCBQAROWITHOUTAC x 0.032 FAIL REPORT DELAY ENABLED (1 MAXIMUM) OR . 0.048 MAIN PC BOARD WITH AC 1 x 0 048 FAIL REPORT DELAY ENABLED 1 MAXIMUM MPM-4 x 0008 0 EOL RELAYS X EF#0001026 U.L.# S7195 -1 0 SMOKE DETECTORS X 0.002 1 SMOKE DETECTORS X 0 0 EOL RESISTERS X 0 0 NOTIFICATION APPLIANCE 46 X 0.023 1.058 NOTIFICATION APPLIANCE 2 X 0.088 0.176 NOTIFICATION APPLIANCE 4 X 0.05 0.2 NOTIFICATION APPLIANCE X 0.528 0 NOTIFICATION APPLIANCE % 0.05 0 NOTIFICATION APPLIANCE X . 0 AUXILARY DEVICES X O 0 SUM COLUMN FORSTANDBYLOAD 1.482 TABLE 5 -1: LOAD IN ALARM @ 24VDC CURRENT CALCULATIONS 1. WHEN USING THE 6.0 AMPS MAXIMUM NRRENTAVAILABLE: FIVE MINUTES UNDER FULL LOAD ( 60 AMPS CURRENT DRAW) REQUIRES 3.0 AH OFA70 AH CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT TH E FCPS DURING ITS REQUIRED STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED BELOW: 1 FOR 24 HOUR STANDBY TIME THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 VDC (24 HOURS X 0.1664) • 196AH 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 VDC (60 HOURS X 0.066A) • 3.96AH 3 1 STANDBY CURRENT CALCULATION SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. 2 WHEN USING LESS THAN 6.0 AMPS MAXIMUM CURRENT: USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE. 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY CHARGER DEVICE TYPE N OF DEVICES CURRENT TOTAL k_� I (AMP) AMPS MAIN PC BOARD WIrHOUTAC X 0.032 FAIL REPORT DELAY ENABLED (1 MAXIMUM) OR . 0.048 MAIN PC BOARD WITH AC 1 X 0 048 FAIL REPORT DELAY ENABLED 1 MAXIMUM MPM-4 X X 0.008 0 EOL RELAYS EF#0001026 U.L.# S7195 -1 X SMOKE DETECTORS 0 SMOKE DETECTORS 0 X 0.002 0 SMOKE DETECTORS EOL RESISTERS % 0 0 EOL RESISTERS 48 X X 0 0 NOTIFICATION APPLIANCE 37 X 0.023 0.851 NOTIFICATION APPLIANCE 6 X 0.088 0.528 NOTIFICATION APPLIANCE 3 X 0.05 0.15 NOTIFICATION APPLIANCE % X 0 0 NOTIFICATION APPLIANCE O X 0 NOTIFICATION APPLIANCE % f U 0 AUXILARY DEVICES X 0 SUM COLUMN FOR STANDBY LOAD 1.577 TABLE 5 -1: LOAD IN ALARM @ 24VDC CURRENT CALCULATIONS 1. WHEN USING THE 6.0 AMPS MAXIMUM NRRENTAVAILABLE: FIVE MINUTES UNDER FULL LOAD 16.0 AMPS CURRENT DRAW) REQUIRES 3.0 AH OFA7.0 AH CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS DURING ITS REQUIRED STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED THE FIGURES LISTED BELOW: 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED M166 AMPS AT 24 VDC (24 HOURS X 0.166A) • 196AH 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 VDC (60 HOURS X 0.066A).3.96AH 3) STANDBY NRRENTCALCUUTWN SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. 2 WHEN USING LESS THAN 6.OAMPS MAXIMUM CURRENT: USE THE FOLLOWING TABLE5TO DETERMINE THE PROPER BATTERY SIZE 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATERTHAN 7.OAH: CUT FCPS JUMPER 1P1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY CHARGER DEVICE TYPE N OF DEVICES CURRENT k_� TOTAL (AMP) AMPS MAIN PC BOARD WITHOUTAC X 0.032 FAIL REPORT DELAY ENABLED (1 MAXIMUM) OR 0.048 MAIN PC BOARD WITH AC 1 X 0.048 FAIL REPORT DELAY ENABLED 1 MAXIMUM MPM4 X 0.008 0 EOL RELAYS X EF#0001026 U.L.# S7195 -1 0 SMOKE DETECTORS X 0.002 0 SMOKE DETECTORS % FAIL REPORT DELAY ENABLED 0 EOL RESISTERS x 0 0 NOTIFICATION APPLIANCE 48 X 0.023 1.104 NOTIFICATION APPLIANCE 6 X 0.088 0.528 NOTIFICATION APPLIANCE 2 X 005 0.1 NOTIFICATION APPLIANCE X O_q 1z 0 NOTIFICATION APPLIANCE X 0 NOTIFICATION APPLIANCE % 0 AUXILARY DEVICES X O 01 SUM COLUMN FOR STANDBY LOAD 3J8. (ABLE 5 -1: LOAD IN ALARM @ Z4VDC CURRENT CALCULATIONS 4' 1. WHEN USING THE 6.0 AMPS MAXIMUM NRRENTAVAILABLE: r"$up FIVE MINUTES UNDER FULL LOAD (6.0 AMPS CURRENT DRAIN) REQUIRES 3.0 AH OF A AN CAPACITY BATTERY. THE REMAINIGN 4.0 AH CAPACITY MUST SUPPORT THE FCPS RI G ITS REQUIRED W EQU ED STANDBY TIME. BECAUSE OF THIS, THE STANDBY CURRENT DRAW CANNOT EXCEED FffiUBEiU5TE0 BELOW: UJiI 1) FOR 24 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.166 AMPS AT 24 VDC (24 HOURS X 0.1664) • &%AH 2) FOR 60 HOUR STANDBY TIME, THE STANDBY CURRENT DRAW CANNOT EXCEED 0.066 AMPS AT 24 VDC (60 HOURS X 0.0661) • 196AH 3) STANDBY CURRENT CALCULATION SUBTRACT TOTAL STANDBY LOAD CALCULATED ABOVE FROM 0.166 AMPS FOR 24 HOURS STANDBY OR 0.066AMPSFOR 60 HOURS STANDBY. THIS FIGURE SHOULD NOT BE LESS THAN ZERO, IF THE AMOUNT IS LESS THAN ZERO, THE REQUIRED STANDBY TIME WILL NOT BE ACHIEVED. 2. WHEN USING LESS THAN &O AMPS MAXIMUM CURRENT. USE THE FOLLOWING TABLES TO DETERMINE THE PROPER BATTERY SIZE. 3. WHEN BATTERY AMP -HOUR REQUIRMENTS ARE FOR GREATER THAN 7.0 AH: CUT FCPS JUMPER JP1 TO DISABLE ONBOARD BATTERY CHARGER AND USE AND EXTERNAL BATTERY CHARGER DEVICE TYPE N OF DEVICES 0.008 CURRENT (AMP) EOL RELAYS TOTAL EF#0001026 U.L.# S7195 -1 0 SMOKE DETECTORS AMPS MAIN PC BOARD WITHOUT AC 0 X 0.032 X FAIL REPORT DELAY ENABLED (1 MAXIMUM) EOL RESISTERS X OR 0 0.048 27 X MAIN PC BOARD WITH AC 1 x 0.048 % FAIL REPORT DELAY ENABLED 1 MAXIMUM NOTIFICATION APPLIANCE X MPM-4 X 0.008 0 EOL RELAYS X EF#0001026 U.L.# S7195 -1 0 SMOKE DETECTORS X 0.002 0 SMOKE DETECTORS X 0 EOL RESISTERS X 0 0 NOTIFICATION APPLIANCE 27 X 0.14 3.780 NOTIFICATION APPLIANCE % M M 0 NOTIFICATION APPLIANCE X 0 NOTIFICATION APPLIANCE % O_q 1z 0 NOTIFICATION APPLIANCE X 0 NOTIFICATION APPLIANCE X 0 AUXILARYDEVICES X O 0 SUM COLUMN FOR STANDBY LOAD 3.828 TABLE 5 -1: LOAD IN ALARM @ Z4VDC AMPS IRE ALARM SYSTEM CALLED IN ACCORDAI NFPA 72; 70; 101- %\ DADS COUNTY FIRE i 3. F -ErWIT 7 WALE REtjt;lOPO BY, .V. JOB COST UN - Signal :re: ;7-, 1 .+ Y � My� C� I EXPI ' VANCE D FIRE & SECURITY 2780 GATEWAY DRIVE POMPANO BEACH, FL 33069 (954)772-1700 (954)772-0500 fax WVWVADVFI REONLI NE.COM STATE AND U.L. LICENSED EF#0001026 U.L.# S7195 -1 to O I I Vft to O J . is a co CIO M 1111% 111111* O veft :t M M Iftft Z n z Fft th zfteft- O_q 1z o , 0 W M%14 O OC O 1% f U LIJ +O IZ THIS DRAWING AND ITS CONTENTS ARE THE PROPERTY OF ADVANCED FIRE & SECURITY INC. IT IS NOT TO BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN CONSENT OF ADVANCED FIRE & SECURITY INC. If any document prepared by Advanced Fire & Security Inc. is altered in any manner by owner, its agents or by any third party if construction is not in accordance with unaltered documents prepared by Advanced Fire & Security Inc. then it is understood that Advanced Fire and Security Inc. has no liability In whole or in part, related to the project and that the owner and its agents Indemnify and holds harmless Advanced Fire & Security Inc. for any and all acts related to the project I This concept drawing is for information aI,tpotential system arrangement. i�hall field verify all, information contained on these drawings nd is responsi and installation of LTW( 's In acco nce with the =ns. R�ItAisddr wledge the Land s cifi tons submitted mnly vii existing i a at n nt rP t t 'Ion the s and p visions of applicable N.F.P.A. es in ff ect at the . o warranty express or implied is hereby REVISIONS: $ 500. 01026 LEEN B OWEAL MISSION # EE172765 S February 26, 2016 AFSI PROJECT NUMBER: 7120272 DATE: SCALE: 9/24/12 AS SHOWN DRAWN BY: CHECKED BY: I.E.A. E.J.W. 9 of 11