10-1110-010GENERAL NOTES: I.- GENERAL: THE ELECTRICAL CONTRACTOR IS EXPECTED TO FURNISH ALL LABOR. MATERIAL ITEMS AND EQUIPMENT SHOWN OR INDICATED FOR A COMPLETE ELECTRICAL SYSTEM IN ACCORDANCE WITH THESE PLANS. THIS CONTRACTOR SHALL PROVIDE ALL THE REQUIREMENTS NECESSARY FOR THE EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. 2.- CODES AND STANDARDS: ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE "NATIONAL ELECTRIC CODE ". COMPLY WITH ALL LOCAL CODES, RULES AND ORDINANCES: MEET ALL STANDARD REQUIREMENTS OF THE ELECTRIC UTILITY AND TELEPHONE COMPANY: BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AND IN FIRST CLASS WORKMAN -LIKE MANNER. MATERIAL SHALL BE NEW AND SHALL BEAR UNDEWRITERS LABELS WHERE APPLICABLE. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE. 3.- PLANS AND SPECIFICATIONS: THE ELECTRIC CONTRACTOR SHALL OBTAIN A COMPLETE SET OF CONSTRUCTION DOCUMENTS SO THAT THE ARCHITECTURAL STRUCTURAL. MECHANICAL AND PLUMBING REQUIREMENTS EFFECTING THIS WORK CAN BE FULLY REVIEWED AND INCLUDED. 4.- SITE VISIT: PRIOR TO BIDDING OR SUBMITTING ANY PROPOSAL THE ELECTRIC CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL OF THE CONDITIONS UNDER WHICH THIS WORK WIL BE PERFORMED. 5: BIDDING: THE ELECTRIC CONTRACTOR BIDDING SHALL INCLUDE: A COPY OF THE CONTRACTOR'S CERTIFICATION AND /OR LICENSE, PROOF OF INSURANCE. A LIST OF ALL ELECRICAL COMPONENTS AND FISTURES INCLUDED OR EXCLUDED, AND TOTAL COST OF THIS WORK G. INSURANCE: THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK PROOF OF INSURANCE SHALL HE SUBMITTED TO THE OWNER PRIOR TO COMMENCEMENT OF WORK 7.- FEES: THE CONTRACTOR SHALL PAY FOR ALL FEES, PERMITS, TESTING AND INSPECTIONS. B: COORDINATION: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER TO AVOID INTERFERENCE WITH THE PROGRESS OF THE CONSTRUCTION OR CONFLICTS. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH CORRESPONDING UTILITY COMPANIES IN ORDER TO VERIFY THE POINTS OF CONNECTION. METER LOCATION, 9: GUARANTEE: THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE OF DEFECTS FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE. CORRECTION OF DEFECTS SHALL 6E COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF INSTALLATION THAT MAY HAVE BEEN DAMAGED. 1D. EQUIPMENT: CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL EQUIPMENT PRIOR TO ROUGH -IN. DO NOT SCALE ELECTRICAL DRAWINGS. SEE MANUFACTURER'S REPRESENTATIVE FOR ALL EQUIPMENT SPECIFICATIONS, REQUIREMENTS, TEMPLATES AND SYMBOLS NOT NOTED OR SCHEDULED ON THE PLANS. 11.- CIRCUITS AND LOADS: THE CIRCUIT NUMBERS SHOWN ON THE PLANS ARE USED TO CALCULATED CIRCUIT LOADING, BREAKERS AND PANEL SIZE THE CONTRACTOR MAY MODIFY CIRCUIT NUMBERING AND PROVIDE CIRCUIT ROUTINGS TO SUIT THE JOB CONDITIONS. LOAD DATA IS BASED UPON INFORMATION SUPPLIED BY THE OWNER AT THE TIME OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING. LOADS ON ALL PANELS SHAH BE BALANCED BETWEEN PHASES. WHEN REQUIRED THE CONTRACTOR SHALL ADJUST PANEL SCHEDULE TO OBTAIN PROPER BALANCING OF ALL PHASES. 12: EQUIPMENT IDENTIFICATION: EACH PANEL DISCONNECT, GUTTER, OR OTHER ELECTRICALLY OPERATED EQUIPMENT SHALL BE IDENTIFIED BY A PERMANENTLY ATTACHED LABEL WITH A MINIMUM LETTERING HEIGHT OF 1/2 ". 13.- CIRCUIT IDENTIFICATION: BRANCH CIRCUIT IDENTIFICATION SHALL BE PROVIDED ON A TYPEWRITTEN DIRECTORY PERMANENTLY AFFIXED TO THE INSIDE SURFACE OF THE ELECTRIC PANEL(S), DOOR(S). 15.- RACEWAYS: RACEWAYS PLACED IN OR THROUGH CONCRETE SLABS OR UNDERGROUND SHALL BE SCHEDULE 40 PCV OR BITUMEN COATED GALVANIZED RIGID STEEL (GRS). IS. EMPTY CONDUITS: INSTALL A NYLON PULL CORD OF ADEQUATE STRENGHT IN ALL EMPTY CONDUITS OR CONDUITS TO BE USED IN THE FUTURE. 17.- OUTLET BOXES: OUTLET BOXES SHALL BE METALLIC OR PVC AND SHALL CONFORM TO N.E.MA. STANDARDS. 18: DISCONNECTS: DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK -MAKE, QUICK -BREAK AND N.E.MA. I OR 3R ENCLOSURE. 19.- RECEPTACLES AND SWITCHES: LIGHT SWITCHES AND RECEPTACLES SHALL BE RESIDENTIAL GRADE WITH A MINIMUM 15 AMPERE SERVICE RATING. THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF SPECIALTY RECEPTACLES WITH THE CORRESPONDING EQUIPMENT MANUFACTURER'S REPRESENTATIVE. 2D.- RECEPTACLES MOUNTING: ELECTRICAL RECEPTACLES SHALL BE MOUNTED AT 12" TO CENTERLINE ABOVE FINISHED FLOOR UNLESS SPECIFIED OTHERWISE. SEE FLOOR PLAN OR ELECTRIC PLAN FOR ALTERNATE MOUNTING HEIGHTS. SEE OWNER OR EQUIPMENT SUPPLIER FOR ALL EQUIPMENT MH AND LOCATIONS WHEN UNSPECIFIED ON ELECTRICAL PLANS. 21: SWITCH MOUNTING: SWITCHES SHALL BE INSTALLED WITH CENTERLINE OF PLATE AT 48" ABOVE FINISHED FLOOR AND G" FROM EDGE OF ADJACENT DOOR CASING OR END OF WALL 22: FIXTURES: THE CONTRACTOR SHALL FURNISH AND INSTALL ALL FIXTURE AND LAMPS AS CALLED FOR ON THE PLANS OR AS SELECTED BY OTHERS. 23.- DRIVEN GROUNDS: GROUNDING ELECTRODE RODS SHALL BE 5/8" GALVANIZED STEEL 10' -0" LONG DRIVEN A MINIMUM OF B' -O" INTO EARTH. THE GROUNDING ELECTRODES SHALL BE SPACED A MINIMUM OF 64" APART. 24.- COLD WATER GROUND: THE ELECTRICAL SYSTEM SHALL HAVE A MINIMUM 3/4" COLD WATER GROUND PIPE BONDED TO THE DRIVEN GROUNDING ELECTRODES. 25.- H.VAC. SYSTEMS: POWER AND CONTROL WIRING FOR THE H.VAC. WORK SHALL BE INSTALLED UNDER THE SUPERVISION OF THE H.VAC. CONTRACTOR. WIRING DIAGRAMS, MOTOR STARTERS, THERMOSTATS SHALL BE PROVIDED BY THE H.VAC. CONTRACTOR. 26.- GROUNDING: THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED, PROVIDE ELECTRICAL GROUNDING AS PER THE N.E.C. 27.- BRANCH CIRCUIT AFCI PROTECTION: (ARC -FAULT CIRCUIT INTERRUPTER) PROVIDE AFCI PROTECTION IN ALL BRANCH CIRCUITS THAT SUPPLY OUTLETS LOCATED IN ALL HABITABLE ROOMS (FAMILY ROOM, DINING ROOM, LIVING ROOM, BEDROOMS, HALLWAYS AREAS TO COMPLY WITH NEC 2008 210.12 28: TAMPER PROOF RECEPTACLES: ALL RECEPTACLES ON THE RESIDENCE SHALL BE TAMPER PROOF RECEPTACLES AS PER NEC 2008 406.11 AND NEC 210.5 TYPE: LOAD CENTER ,0 V. 3 WIRE TO FPL NEW GUEST HOUSE AREA. NEW PANEL POLE 7446 ve MLO: 125 AMPS RATING t KA 2- # 4/0 THWN CU 1500 va x 1 1500 va 1- # 4/0 THWN NEUTRAL 1849 va REFRIGERATOR IN 2" METAL CONDUIT MICROWAVE 1200 va DISHWASHER EXISTING PANEL A COMBO METER /BREAKERS 200 A FOR RESIDENCIAL UNIT RATING WATER HEATER 3500 va 18 320A 200 A 2304 va I METER C.B. I BATHROOM SOCK FIRST 10000 v.a. @ 100 % 1- # 2/0 THWN NEUTRAL I 2 IE I IN 2" CONDUIT 10 I EXISTING A.H.U.#1 HEATER ELEMENT 109 A NEW PANEL B REFRIGERATOR C.B. 100 A I I RATING 49698 va 21 [g SERVICE ENTRANCE CONDUCTOR: 3 - # 4/0 THWN W.H. TANKLESS �-- GNRAL LIGHTING 2- # 3 THWN CU I- # 3THWN NEUTRAL IN I" CONDUIT # 2 Cu GEC GNRAL LIGHTING CWP 6' -D" MINIMUM INSTALL TWO 5/8 " x 10' GROUNDING RODS NEW ELECTRICAL RISER GNRAL LIGHTING SCAffi US NEUTRAL TOTAL O A! ,' 240 74 Amps. M1 SCALE : 3/32 " =1 '--0)) WORK SCOPE: THE INTENT OF THIS PLAN IS TO POWERED THE NEW GUEST HOUSE I. REPLACED EXISTING 200A METER SOCKET WITH A 320A COMBO METER SOCKET WITH TWO MAIN BREAKERS 209A AND 1ODA RATINGS, 22KA, 240V. 2P, 19. METER SOCKET SHOULD BE "MIDWEST MFG CATALOG # RS45100CFMG" OR APPROVAL EQUAL 2.- INSTALL A FEEDER CONDUCTORS 3- #3 THWN IN 1" CONDUIT AS SHOWN IN THE PLAN TO FEED THE NEW PANEL "B" AT THE GUEST HOUSE. 3: WIRING THE NEW GUEST HOUSE AS SHOWN IN THSI PLAN. FOLLOW WIRING METHODOLOGY AS PER NEC -2008. f' �I; E, �1: T��i1�1�► y�Itlf��l�1�NLt1 ►�I;ifTl�Hll,��llrllly� IYIIIII SCALE tFF 0 LOAD CALCULATION SERVICE ENTRANCE CONDUCTORS: EXISTING HOUSE AREA: TO FPL NEW GUEST HOUSE AREA. 474 SOFT. x 3 v.a. = 1422 va POLE 7446 ve 1500 va x 2 2- # 4/0 THWN CU 1500 va x 1 1500 va 1- # 4/0 THWN NEUTRAL 1849 va REFRIGERATOR IN 2" METAL CONDUIT MICROWAVE 1200 va DISHWASHER EXISTING PANEL A COMBO METER /BREAKERS 200 A FOR RESIDENCIAL UNIT RATING WATER HEATER 3500 va 18 320A 200 A 2304 va I METER C.B. I 2- # 2/0 THWN CU SOCK FIRST 10000 v.a. @ 100 % 1- # 2/0 THWN NEUTRAL I 2 IE I IN 2" CONDUIT 10 I EXISTING A.H.U.#1 HEATER ELEMENT 109 A NEW PANEL B 9600 va C.B. 100 A I I RATING 49698 va 21 [g SERVICE ENTRANCE CONDUCTOR: 3 - # 4/0 THWN �-- 2- # 3 THWN CU I- # 3THWN NEUTRAL IN I" CONDUIT # 2 Cu GEC CWP 6' -D" MINIMUM INSTALL TWO 5/8 " x 10' GROUNDING RODS NEW ELECTRICAL RISER SCAffi US IYIIIII SCALE tFF 0 LOAD CALCULATION SERVICE ENTRANCE CONDUCTORS: EXISTING HOUSE AREA: 2008 SOFT. x 3 v.a. = 6024 va NEW GUEST HOUSE AREA. 474 SOFT. x 3 v.a. = 1422 va WATER HEATER (TANKLESS) 7446 ve 1500 va x 2 3000 va 1500 va x 1 1500 va EQUIPMENT LOAD: 1849 va REFRIGERATOR 1200 va MICROWAVE 1200 va DISHWASHER 1200 va RANGE 8900 va DRYER 5090 va WATER HEATER 3500 va WATER HEATER (TANKLESS) 10800 va SPRINKLE PUMP 1/2 HP 2304 va POOL PUMP I HP 1344 va DEMAND FACTOR: 46494 va FIRST 10000 v.a. @ 100 % 10090 va NEXT 36494 vA. @ 49 % 14598 va TOTAL: 24598 va A/C LOAD R 100 % EXISTING A.H.U.#1 HEATER ELEMENT 9609 va EXISTING A.H.U.#2 HEATER ELEMENT 9600 va NEW A.H.U. #3 HEATER ELEMENT 5900 va A/C COMPRESSOR IOAA 2496 va 0 va 49698 va 49698 / 249 = 207 Amps. SERVICE ENTRANCE CONDUCTOR: 3 - # 4/0 THWN ELECTRICAL: LEGEND Ceiling Mounted Light 0 PLcassed light f ;} Wall Mounted Light Uj co � o Q Duplex Receptacle < `U U° c°y -j 220 V Receptacle ® ° ce- Z 0. V 0 LU LO &j 20 A single receptacle u z w o ® W Ground Fault Interupt W �; ®r O Q Uj Uj TV outlet Z c i 0 Z ce 4 Cn SZ Phone outlet Q °L 00 CL Data outlet Wall Switch 3 -Way Switch ..___.,_._.0: 4' Flourescent light Electrical Panel Disconnect Switch (D Smoke Detector c� Spot light �. j ° *' • • A✓ Exhaust Motor Junction Box N New MANUEL °'A. CIW f.;® ,.l, E Existing ---__'- LOAD w PE. # 45176' WP Water Proof CALCULATION FEEDER CONDUCTORS GUEST HOUSE: 441111;T111110IIIRO �r1�11;IuT�fI�>IiLl REFRIGERATOR 1209 va MICROWAVE 1209 va WATER HEATER (TANKLESS) 10809 va DEMAND FACTOR: 14622va FIRST 10000 v.s. L 100 % 19900 ve NEXT 4622 v.a. C 40 % 1849 va �r TOTAL: 11849 va A/C LOAD 9 190 % NEW A.H.U. 0 HEATER ELEMENT 5900 va A/C COMPRESSOR 19.4A 2496 va 0 va 17749 va 17749 / 240 = 74 Amps. SERVICE ENTRANCE CONDUCTOR: 3 - # 3 THWN �r O �r O .. U) Date; 10/27/10 Revisions: I� Sheet 1 of 1 :m O O .. U) CL} U) � o � U � Cf) Q Date; 10/27/10 Revisions: I� Sheet 1 of 1 :m