98-137-004i i ELECTRICAL SPECIFICATIONS PART 1 - GENERAL 1.1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. "PROVIDE" MEANS "FURNISH AND INSTALL". 1.2 COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF NFPA, NEMA, NEC, ASTM, OSHA, HRS, HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY RULING AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL ALSO MEET OTHER RECOGNIZED STANDARDS AND REQUIREMENTS, SUCH AS LANDLORD'S BUILDING STANDARDS, WHERE SUCH ARE MORE STRINGENT THAN THOSE CITED ABOVE. 1.3 WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR RESPECTIVE DISCIPLINES. WORK SHALL BE DONE IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT /ENGINEER. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND BACKFILLING. 1.4 MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO ADDITIONAL C 0 ST TO T H -E T-E NANT. CO- N-T-RACT-O -R S HALL B -E R ES -P-O -N S- 1 -B -LE FO -R PR O-- V-1- S -1 -0 -N S AN -D C 0- 0- R- D- I- NA-T-I -O-N OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. 1.5 PERMITS & INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 1.6 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1.7 UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK WITH WATER, SEWER, GAS, ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS. PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES AS REQUIRED. 1.8 PLANS: DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. 1.9 INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL MEMBERS WILL BE AVOIDED. 1.10 SHOP DRAWINGS: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND MANUFACTURER'S LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UL APPROVAL, MATERIALS, FINISHES, ACCESSORIES AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED. SUBMISSION OF EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND ALL AT THE SAME TIME. 1.11 SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONS; ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY - - CONTRACTOR_ 1.12 GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT /TENANT AND LANDLORD. ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP. WHERE APPLICABLE, LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE TO THE TENANT /LANDLORD AND SHALL INCLUDE REPLACEMENTS AND /OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 1.13 RECORD DRAWINGS: MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES. USE COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND DELIVER THE SET TO ARCHITECT /ENGINEER UPON COMPLETION. CONTRACTOR SHALL STAMP "AS BUILT" ON PRINTS AND PLANS, DATE AND SIGN IN INK. WORK SHALL NOT BE CONSIDERED COMPLETED UNTIL SUCH PLANS ARE REVIEWED AND APPROVED BY ARCHITECT /ENGINEER. PART 2 - PRODUCTS 2.1 SHOP DRAWINGS: SUBMIT SHOP DRAWINGS OF THE FOLLOWING PRODUCTS: A. SWITCHGEAR, PANELBOARDS, OVERCURRENT PROTECTION DEVICES, CIRCUIT BREAKERS, SWITCHES, FUSES. B. WIRING, CABLING, CONDUITS, RACEWAYS, FLOOR AND OUTLET BOXES. C. WIRING DEVICES: RECEPTACLES, OUTLETS, LIGHT SWITCHES, PLATES. D. LIGHTING FIXTURES, LAMPS AND RELATED HARDWARE. E. TIMECLOCKS AND CONTACTORS. F. MISCELLANEOUS SYSTEMS: FIRE ALARM, CONTROLS. 2.2 SWITCHGEAR: PANELBOARDS SHALL BE OF THE CIRCUIT BREAKER TYPE. CIRCUITS BREAKERS SHALL BE MOLDED CASE, BOLT -ON TYPE, OF QUICK -MAKE ACTION, THERMAL MAGNETIC TRIP, FULL SIZE DEVICES. LOAD CENTER TYPE PANELBOARDS SHALL NOT BE USED. UNLESS OTHERWISE NOTED ON PLANS, MINIMUM EQUIPMENT AIC RMS SYM RATING SHALL BE 10,000 AT 1201208`x`, 14,000 AT 277/480V OR TO MATCH EXISTING EQUIPMENT IN WHICH CIRCUIT BREAKER IS BEING INSTALLED, WHICHEVER IS GREATER. PHASES SHALL BE BALANCED WITHIN 10 PER CENT. MANUFACTURER SHALL BE GE, SQUARE -D OR WESTINGHOUSE. PROVIDE LIGHTNING ARRESTOR AT EACH PANELBOARD AND SERVICE DISCONNECTS. 2.3 DISCONNECTS: SWITCHES SHALL BE QUICK -MAKE QUICK -BREAK ACTION, LOCKABLE TYPE. SERVICE DISCONNECT SHALL BE SERVICE RATED, HEAVY -DUTY TYPE. PROVIDE DUAL ELEMENT FUSES FOR MOTOR DRIVEN MECHANICAL EQUIPMENT SIZED PER MANUFACTURER'S RECOMMENDATION. FIELD COORDINATE FUSE SIZE WITH EQUIPMENT NAMEPLATE BEFORE ACTUAL INSTALLATION. MANUFACTURER SHALL BE GE, SQUARE -D OR WESTINGHOUSE. 2.4 RACEWAYS: A. RGS AND IMC: HOT- DIPPED GALVANIZED INCLUDING THE THREADS. PROVIDE FOR EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE AND FOR ELBOWS, ELLS AND RISERS INTO GROUND AND SLAB. INSTALL ELLS AND RISERS STUBBED UP 6 INCHES FROM CONCEALED SLAB RUNS, 48" ABOVE GROUND WHERE EXPOSED ON WALL. PAINT RACEWAYS BELOW SLAB OR FINISHED EXTERIOR GRADE WITH TWO (2) COATS OF BITUMASTIC PAINT UP TO A POINT 2" ABOVE SLAB. B. EMT: MAY BE USED FOR INTERIOR SPACES IN DRY LOCATIONS, WHERE NOT EXPOSED TO PHYSICAL DAMAGE. FITTINGS SHALL BE STEEL. C. PVC SCHEDULE 40 SHALL NOT BE USED. D. FLEXIBLE METALLIC CONDUIT: LIGHTING FIXTURES, MOTORS, TRANSFORMERS AND VIBRATING EQUIPMENT CONNECTIONS IN LENGTHS NOT TO EXCEED 18 ". PVC JACKETED FLEXIBLE METAL CONDUIT FOR LOCATIONS OUTSIDE AND /OR EXPOSED TO MOISTURE. GREENFIELD OR APPROVED EQUAL. E. RUNS BELOW SLAB SHALL BE PROVIDED WITH A YELLOW RIBBON TAPED ALONG TRENCH 6' BELOW GRADE FOR RACEWAY IDENTIFICATION. 2.5 CONDUCTORS: SOFT -DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN CONDUIT. MINIMUM SIZE SHALL BE #12 FOR POWER WIRING, #16 FOR CONTROL CIRCUITS. PROVIDE #10 WIRES FOR 120V POWER CIRCUIT HOMERUNS LONGER THAN 100 FEET. INSULATION SHALL BE 600V THHN /THWN FOR GENERAL USE, THW IN SIZES #6 AND ABOVE, COLOR CODED THROUGHOUT PER NEC AND TRADE STANDARDS. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC 300 -22. 2.6 SPLICES SHALL BE MADE WITH UL LISTED MECHANICAL PRESSURE SOLDERLESS CONNECTORS, BURNDY SERVITS TYPE OR APPROVED EQUAL. FEEDER SPLICES AND TERMINATIONS SHALL BE MADE MECHANICALLY USING COMPRESSION TYPE SLEEVES OR LUGS AND CONNECTION TO PANELS AND SWITCHES AS MANUFACTURED BY BURNDY OR THOMAS & BETTS. 2.7 WIRING DEVICES SHALL BE FLUSH MOUNTED, SPECIFICATION GRADE, BUILDING STANDARD. MANUFACTURER SHALL BE LEVITON. A. SWITCHES: 20A 120/277V, SINGLE POLE, THREE -WAY WHERE NOTED. SWITCHES IN THE SAME AREA SHALL BE GANGED TOGETHER IN THE SAME BOX. B. RECEPTACLES: 20A 120V GROUNDING TYPE DUPLEX. SPECIAL OUTLETS RATED TO MATCH CIRCUIT BREAKERS AS NOTED ON PLANS; QUADRUPLEX OUTLETS AND SWITCH /OUTLET COMBINATIONS SHALL HAVE THE SAME FACE PLATE. ISOLATED GROUND TYPE SHALL BE PROVIDED WITH SEPARATE ISOLATED GROUND WIRE. C. TELEPHONE AND DATA OUTLETS: TELEPHONE /DATA JACKS AND WIRING AS SELECTED BY USER UNLESS OTHERWISE NOTED; OTHERWISE, PULL WIRE WITH 12" SLACK AT EACH END, RUN IN 3/4" EMPTY CONDUIT. WHERE PREVIOUSLY APPROVED BY RULING AUTHORITIES AND ENGINEER, RACEWAYS MAY BE INDIVIDUALLY TERMINATED ABOVE DROP CEILING WITH SMOOTH 90- DEGREE BEND AND PLASTIC BUSHING. D. MOUNTING HEIGHTS: WHERE NOT ESTABLISHED ON PLANS OR LEGEND, MOUNTING HEIGHT SHALL BE AS FOLLOWS OR TO MATCH HEIGHTS ESTABLISHED BY EXISTING DEVICES. MH = 18 "AFF - GENERAL AREA RECEPTACLES, TELEPHONE AND DATA OUTLETS. MH = 42 "AFF - COUNTER RECEPTACLES, TELEPHONES AND DATA OUTLETS. MH = 52 "AFF - WALL MOUNTED PHONES MH = 48 "AFF - SWITCHES MH SHALL BE CONSIDERED TO THE BOTTOM OF EACH OUTLET JUNCTION BOX 2.8 TELEPHONE CABINET /BOARD SHALL BE PROVIDED WITH A 3/4" THICK EXTERIOR GRADE PLYWOOD BACKBOARD PAINTED WITH TWO COATS OF FIRE RETARDANT PAINT ON ALL SIDES AND EDGES. UNLESS OTHERWISE NOTED, BOARD SIZE SHALL BE 4'W X 8'H. PROVIDE DEDICATED 20A DUPLEX AND #6 GROUNDING ELECTRODE. 2.9 LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL NECESSARY LAMPS, BALLASTS, WIRING, LAMP HOLDERS REFLECTORS, GLASSWARE, POLES, BASES AND MOUNTING ACCESSORIES AS REQUIRED TO PROVIDE FOR A COMPLETE INSTALLATION. INTERIOR FIXTURES SHALL HAVE 100% VIRGIN ACRYLIC PRISMATIC DIFFUSERS. LIGHTING FIXTURES SHALL BE SELECTED BY ARCHITECT /TENANT AND LANDLORD, PROVIDED BY CONTRACTOR. REFER TO ARCHITECTURAL DRAWINGS FOR COLOR, FINISH AND EXACT MOUNTING DETAILS. ALL FIXTURES SHALL BE ENERGY SAVING MAGNETIC BALLAST AND LAMPS. 2.10 TIMECLOCKS SHALL BE 24 -HOUR 7 -DAY TYPE WITH BATTERY BACKUP AND OVERRIDE. PHOTOCELL SYSTEM SHALL INCLUDE ALL NECESSARY CONTROLS AS REQUIRED. CIRCUITS CONTROLLED SHALL BE DATA ROOM LIEBERT HVAC UNIT, SIGN LIGHTING, AND AS NOTED. MANUFACTURER SHALL BE TORK, PARAGON OR APPROVED EQUAL. PART 3 - EXECUTION 3.1 TESTS: PROVIDE ALL NECESSARY INSTRUMENTS AND SPECIAL APPARATUS TO CONDUCT ANY TESTS THAT MAY BE REQUIRED TO INSURE SYSTEM IS FREE OF ALL IMPROPER GROUNDS AND SHORT CIRCUITS AND THAT ALL FEEDERS ARE PROPERLY BALANCED. SYSTEM SHALL BE CHECKED FOR QUALITY, CAPACITY AND COMPLETENESS TO CONFORM WITH THE FULL REQUIREMENTS AND INTENT OF THE DRAWINGS AND SPECIFICATIONS. 3.2 CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS AND PARTITIONS; NO RACEWAY SHALL BE EXPOSED WITHIN INTERIOR SPACES. ALL OUTLETS AND WIRING DEVICES SHALL BE FLUSH MOUNTED. 3.3 GROUNDING AND BONDING SHALL COMPLY WITH NEC 250. ALL METALLIC RACEWAYS SHALL BE GROUNDED AND BONDED PER NEC 250. NON- METALLIC RACEWAYS SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER NEC 250 -95. 3.4 ELECTRICAL EQUIPMENT SPACE AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC 110 -16A AND 384 -2. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC 300 -22. 3.5 PANELBOARDS, SWITCHES, CONTROLLERS, CONTROL PANELS, TIMECLOCKS, AND OTHER ELECTRICAL COMPONENTS SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. INDICATE PANELBOARDS CIRCUITS ON UPDATED TYPED DIRECTORY CARD HOLDERS WITH GLASS COVER AND METAL FRAME INSTALLED ON INSIDE OF PANELBOARD DOOR. MARK CONDUCTORS WITH PREPRINTED ADHESIVE MARKERS AS MANUFACTURED BY W.H. BRADY CO. OR THOMAS & BETTS. 3.6 CONTRACTOR SHALL MAKE ALL NECESSARY EXCAVATIONS, CUTTING AND REPATCHING AS REQUIRED FOR THE PROPER EXECUTION OF THIS WORK. 3.7 CONTRACTOR SHALL FIELD SPOT LOCATION OF WIRING DEVICES TO VERIFY AND GET APPROVAL FROM ARCHITECT /TENANT BEFORE INSTALLATION. 3.8 BEFORE COMMENCING WORK CONTRACTOR SHALL COORDINATE WITH LANDLORD EXTENT OF WORK WITHIN AND OUTSIDE TENANT SPACE TO DETERMINE PROVISIONS REQUIRED. 3.9 UNLESS OTHERWISE NOTED AS EXISTING TO REMAIN OR BE RELOCATED, ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR. EXISTING EQUIPMENT TO BE REMOVED NOT CLAIMED BY THE TENANT /LANDLORD SHALL BE REMOVED FROM THE JOB SITE AS DIRECTED. FIELD VERIFY BEFORE REMOVAL. 3.10 WHERE WORK ON EXISTING EQUIPMENT IS REQUIRED, SPECIAL ATTENTION SHALL BE GIVEN TO CONDITIONS OF PANELS AND SWITCHING EQUIPMENT. MODIFY EXISTING PANELS AND EQUIPMENT BY THE ADDITION OF CIRCUIT BREAKERS, WIRING, AND OTHER EQUIPMENT AS REQUIRED IN ORDER TO PROVIDE A COMPLETE AND OPERATING SYSTEM. CIRCUIT BREAKERS AND SWITCHES INSTALLED IN EXISTING PANELBOARDS AND SWITCHING DEVICES SHALL BE OF THE SAME MANUFACTURER AND FULLY COMPATIBLE WITH THE COMPONENTS PROVIDED. EXISTING EQUIPMENT OR DEVICES INADVERTENTLY DE- ENERGIZED OR DISCONNECTED SHALL BE RE- ENERGIZED AND MADE OPERABLE AT NO ADDITIONAL COST. 3.11 HVAC, MOTORS, AND OTHER EQUIPMENT SHALL BE PROVIDED WITH EQUIPMENT WIRING AND PROTECTION AS NOTED ON PLANS. FIELD COORDINATE NAMEPLATE RATINGS AND UPGRADE AS REQUIRED. LANDLORD'S NOTES: REFER TO LANDLORD /TENANT HANDBOOK AND OPERATIONS MANUAL AND TO SPECIFICATIONS ON THESE PLANS FOR ADDITIONAL REQUIREMENTS. WHERE THE WORK "CONTRACTOR" IS USED, IT REFERS TO THE TENANT'S CONTRACTOR UNLESS OTHERWISE NOTED. 1. CABLE TYPES AC AND NM SHALL NOT BE ALLOWED. 2. WHERE PREVIOUSLY APPROVED BY ENGINEER AND LANDLORD'S ENGINEER, CABLE TYPE MC SHALL HAVE BLUE STRIPE. 3. CONDUCTORS SHALL BE COLOR CODED PER LANDLORD /TENANT HANDBOOK AS FOLLOWS: A. 120/208V SYSTEMS: PHASE A- BLACK; PHASE B -RED; PHASE C -BLUE; NEUTRAL- WHITE. B. 277/480V SYSTEMS: PHASE A- BROWN; PHASE B- ORANGE; PHASE C- YELLOW; NEUTRAL -WHITE WITH TRACER OR GRAY. 4. GROUND ON SEPARATELY DERIVED SERVICE SHALL BE BONDED TO COPPER WATER MAIN 0 0 A TYPE MAIN BUS 125A SERVICE 3P, 4W >7 r, NEUTRAL 125A VOLTAGE 120/208 PANEL A MAINS 110A MCB MOUNTING FLUSH MIN 1OK AIC SYM LOCATION TOP KVA POLES TRIP CON DUIT WIRE REMARKS CKT No. 12/27/98 LANDLORD'S REVISION CKT No. REMARKS WIRE CON D TRIP P ES KVA 1.2 1 20 3/4" #12 SIGN LIGHTING VIA T C 1 FCU -1 #10 3 4' 30 2 4._1__ LIGHTING 3 4 1/2 HP, 3KW HTR. PLAN. M PROD. M DESIGN SA 5 6 REFRIGERATOR 2 #12 3/4' 20 1 1.2 7 8 1.2 9 10 UNDER CAB REFRIG. 0.4 11 12 INST. EWH 8 3/4" 40 2 6.2 13 14 0.6 1 16 TV & VCR 12 3/4' 20 1 0.8 1.7 17 18 TV &VCR 0.8 INTERNET COMPUTER 19 20 ALARM 0.4 21 22 RECEPTACLES 0.8 0.2 A/C TEMPER. CONTROL 23 24 RECEPT. COUNTER 1.0 SPARE 25 26 RECEPTACLES 0.8 27 28 CASHIER 0.4 29 30, 0.4 31 32 33 34 35 36 37 38 39 40 11.2 18.1 TOTAL CONNECTED LOAD = 29.3 KVA = 81 AMPS A/C TEMPERATURE CONTROL CIRCUIT SHALL BE LOCKABLE TYPE CB TYPE MAIN BUS 100A SERVICE 3P, 4W „ „ NEUTRAL 100A VOLTAGE 120/208 PANEL B MAINS 50A MCB MOUNTING FLUSH MIN 10K AIC SYM LOCATION TOP KVA POLES TRIP CON WIRE REMARKS CKT CKT REMARKS WIRE CON TRIP POLES KVA DUIT No. No. DUIT 3.3 2 20 3/4 #12 ESPRESSO MACHINE 1 2 COFFEE GRINDER #12 3/4" 20 1 0.9 3 4 COFFEE BREWER 1.7 1.2 1 20 3/4" #12 PASTRY WARMER 5 6 FUTURE EQUIPMENT 1.2 7 8 1.7 BAGEL TOASTER 9 10 SPARE 1.1 FROZEN DRINK MAKER 11 12 SPARE 13 14 15 16 17 18 19 20 21 22 23 24 8.5 5.1 TOTAL CONNECTED LOAD = 13.6 KVA = 38 AMPS L_AIJIIIN\7 LYIINLJL\JI\L/ ..J L,vvvil Tvv/ Z_ i i v vi I .v MDP SERVING TENANT SPACES FOR THIS AREA. PROVIDE CB FOR THIS TENANT SPACE, WITH LABEL IDENTIFYING SPACE AND TENANT X12X PULLBOX 'P 0 q 2) I"- - /--- -3 # 4 -1 „ C -,, -TOTAL CONNECTED = 42.9KVA = 52 AMPS 8X6 W'IREGUTTER \ t " 1.6KJr TENANT SPACE ELECTRICAL AREA DRYTYPE T /F'S, 480- 3P 4W CEILING HUNG DRYTYPE T/F WITH 10% CONTINUOUS OVERLOAD CAPABILITY 30KVA #8 -3/4'C BONDED TO COPPER WATER MAIN \ 4#6-1"C--,,X I I 4 #2- 11/2 "C 3# 10 -3/4" C 3 #6 -1 "C I� PANEL 3 L5480V 60 " B" 360480V PANEL „ A„ POWER RISER POWER RISER NOTES: 1. CONTRACTOR SHALL PROVIDE FOR ALL EQUIPMENT AS REQUIRED TO SERVICE THIS TENANT SPACE AS NOTED ON PLANS, INCLUDING BUT NOT LIMITED TO PANELBOARD, WIRING, TRANSFORMER, DISCONNECTS, CIRCUIT BREAKER AT LANDLORD'S MAIN DISTRIBUTION PANEL, AND ALL OTHER COMPONENTS AS REQUIRED FOR SERVICING THIS TENANT SPACE FROM EXISTING LANDLORD'S ELECTRICAL ROOM. FIELD COORDINATE WITH LANDLORD ELECTRICAL ROOM, MAIN DISTRIBUTION BOARD, AND RELATED LANDLORD'S REQUIREMENTS FOR THIS TENANT SPACE SERVICE. 2. TENANT SPACE SERVICE CIRCUIT BREAKER SHALL BE RATED 65K AIC OR TO MATCH EXISTING LANDLORD'S MDP AIC RATING, WHICHEVER IS GREATER. CIRCUIT BREAKER SHALL BE OF THE SAME MANUFACTURER AND MODEL AS LANDLORD'S, FULLY COMPATIBLE WITH EQUIPMENT. 3. BEFORE COMMENCING WORK CONTRACTOR SHALL FIELD COORDINATE INSTALLATION WITH ARCHITECT, LANDLORD AND FPL REPRESENTATIVE AS REQUIRED, AS WELL AS FEEDER ROUTING TO ELECTRICAL ROOM. PROVIDE PULL BOXES PER NEC 372, MINIMUM 12X4X4, NEMA -3R FOR EXTERIOR AREAS 4. UNLESS OTHERWISE NOTED AS EXISTING, CONTRACTOR SHALL PROVIDE FOR ALL EQUIPMENT AS SHOWN AND AS REQUIRED FOR A COMPLETE INSTALLATION. 5. CONDUCTORS REFER TO THHN /THWN 600V COPPER, RUN IN RACEWAYS. SERVICE FEEDERS SHALL BE RCS WHERE EXPOSED 0 DATE PRE hl j DATE ARCHITECTURAL REVISIONS 0 xq4, 4 DATE REVISIONS N0. 10/29/98 BUILDING DEPT. 1 12/27/98 LANDLORD'S REVISION 2 4/14/99 MISCELLANEOUS REV 7/27/99 TENANT'S REVISION A4 PLAN. M PROD. M DESIGN SA NARANJO + ASSOCIATES p E C 0 N S U L T I N G E N G I N E E R S f' xq4, 4 9300 NW 25TH STREET . #209 MIAMI, FL 33172 TEL: (305)599 -9447 FAX: (305)599 -9427 ORLANDO NARANJO, PE #32646 - ELECTRICAL ID# 65- 0479171 NOTE: WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY, AND BE RESPONSIBLE FOR, ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS. SHOP DETAILS MUST BE SUBMITTED TO THIS OFFICE FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION. Sunset Shops Holding Company NEWSLINK.CO%/f Tenant E -01 A The Shops at Sunset Place Miami. RI zO'j*E R, PANEL WS S-.)tan SCALE NONE DRAWING DATE 10/7/9r JOB NUMBER 1145