14-870-002SCOPE OF WOR4
GM CONSULTING
ENGINEERS
GENERAL NOTES
ABBREVIA11ONS
SYMBOLS AND'LEGE-ND
1,0
GENERAL
AC c
ALTERNATING CURRENT, AIR CONDITIONING
KW
KILOWATTS
AW
AIR CONDMONING CONTRACTOR OF AMERICA
KWH
KILOWATT HOUR
i'l
ALL WORK TO BE PERFORMED UNDER THESE DOCUMENTS SHALL CONFORM WITH THE
ACH
AIR CHANGES PER HOUR
KX
KITCHEN HOOD EXHAUST
FLORIDA BUILDING CODE, AND ALL 0114ER APPUCABLF STATE AND LOCAL REGULATIONS
AFF
ABOVE, FINISHED FLOOR
GATE VALVE
AND ORDINANCES.
AHU
AJR HANDLING UNIT
L
LENGHT
1.2
ALL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED MECHANICAL
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
LAT�
LKrENT
CONTRACTOR, IN A F'IRST CLASS WORKMANUKE MANNER. THE COMPLETE SYSTEM SHALA.
APPROX.
APPROXIMATE
LB&
POUNDS
BE FULLY OPERATIVE AFTER COMPLETION OF WORK,
'niAT
ARCH
ARCHITECT OR ARCHITECTURAL,
LF
LINEAR FOOT
t3
MECHANICAL CONTRACTOR SHALL FURNISH WRITTEN GUARANTEE THE INSTALLED
AS
AIR SEPERATOR
LVG
LEAVING
SYSTEM SHALL BE FREE OF MATERIALS AND WORKMANSHIP DEFECTS FOR A PERIOD OF
ASHRAE
AMERICAN SOCIETY OF HEATING REFRIGERATING AND
LAT
LEAVING AIR TEMPERATURE
ONE YEAR FROM FINAL, ACCEPTANCE UY THE OWNER.
AJR CONDITIONING ENGINEERS INC.
Lwy'
LEAVING WATER TEMPERATURE
t4
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR 08TAJNING HIS OWN PERMIT AND
A.S.M.E.
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
LRA
LOCKED ROTOR AMPS
PAYINO ALL PERMrT AND INSPECTION FEES.
A.SJ.M.
AMERICAN SOCIElY FOR 'TEnNG AND MATERIALS
PRESSURE GAUGE WITH GAUGE VALVE
1.5
suBmrr SHOP DRAWINGS F'OR ACCEPTANCE BY THE ARCHITECT AND/OR ENGINEER
AUTO.
AUTOMATIC
m
MOTOR
BEFORE PROCEEDING WMi PURCHASE OR INSTALLATION OF THE EOUIPMENT AND
AVG.
AVERAGE
MAX
MAXIMUM
MATERIALS
AWS
AMERICAN WELDING SOCIETY
M8H
THOUSAND BRMSH THERMAL UNIT PER HOUR
1.6
THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW
MECH,
MECHANICAL
A.S-BUILT CONDMONS AT THE COMPLErION OF CONSTRUCTION.
BDD
BACK DRAFT DAMPER
MEZZ.
MEZZANINE
13
All BUILDING CONsmuanON AFFECTED BY THE REMOVAL. RELocAnON OR
8HP
BOILER HORSE'POWER, BRAKE HORSEPOWER
mFG.
MANUFACTURING
INSTALLATION Of ANY PIECE OF EQUIPMENT SHALL BE REPAJRED AND nNISHED AS
BLDG.
BUILDING
MFRS.
MANUFACTURERS
REQUIRED TO MATCH EXISnNG CONDMONS. OR AS DIRECTED BY THE
B.O.B.
BOTTOM OF BEAM
misc.
MISCELLANEOUS
ARCHITECTURAL DRAWINGS AND/ OR SPECIFICATIONS.
B.O.C.
BOTTOM OF CURB
Mft
MINIMUM, MINUTE
t8
PLANS AND SCHEMATICS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED.
80D.
BOTTOM OF' DUCT
MOD
MOTORIZED DAMPER
COORDINATE HVAC WORK WITH ALL PLUMBING, FIRE PROTECnON AND ELECTRICAL WORK
Bop�
BOTTOM OF PIPE
MPH
MILES PER HOUR
AT THE SITE SO AS NOT TO CONFLICT IN LOCATION WITH OT14ER WORK PERFORMED
BOT,
BOTTOM
M.U.
MAKE UP WATER
UNDER THIS CONSTRUCTION DOCUMENTS.
Bp
BOILER PUMP
BPD
BY-PkSS DAMPER
(N)
NEW
2,0
FIELD VERIFICATION
Bu
BOILER UNIT
N.
NORTH
NA
NOT AVAILABLE, NOT APPLICABLE
2.1
ALL WORK SHALL BE FIELD VERIFIED BEFORE INSTALLA110N AND COORDINATED WITH ALL
CD
CONDENSATE DRAJN
N.C�
NORMALLY CLOSED, NOISE CRITERIA
OTHER TRADES.
CEN'TRIG,CENT.
CENTRIFUGAL
N.E.
NORTHEAST
12
WHERE INTERFFRENCES OCCUR AND DEPARTURES FROM INDICATED DESIGN WILL. BE
CFM
CUBIC FEET PER MINUTE
NEC
NATIONAL ELECTRICAL CODE
REQUIRED TO DETERMINE CHANGES ON LOCATIONS, SIZES AND ELEVATIONS OF PIPING,
CH
CHILLER
NEMA
NATIONAL ELECTRICAL, MANUFACTURER'S ASSOCIATION
DUCrWORK, ETC., THE C04rRACTOR SHALL SUBMIT A 'WRITTEN REQUEST FOR THE
CHWP
CHILLED WATER PUMP
NFPA
NATIONAL FIRE PROTECTION ASSOCIATION
CHANGE ACCOMPANIED SY A DETAILED DRAWING FOR APPROVAL FROM ARCHITECT/
CHWR
CHILLED WATER RETURN
N.I.C.
NOT IN CONTRACT
ENGINEER PRIOR TO PROCEEDING WITH ANY CHANGE OR DEPARTURES FROM CONTRACT
CHWS
CHILLED WATER SUPPLY
NK
NECK
DOCUMENTS.
CL
CENTERUNE
NO.,
NUMBER
2.3
BEFORE CUTTING OR MAKING OPENINGS IN ANY BUILDING COMPONENT, CONTRACTOR
CLG�
COUNG
N�O�
NORMALLY OPEN
SHALL VERWY USING ANY REQUIRED MEANS 'THAT ITS LOAD BEARING CAPABiLrty IS NOT
CLR"
CLEAR
NOM.
NOMINAL
COMPROMISED IN ANY MATTER AND SHALL REQUEST APPROVAL FROM BUILDING
C.o�
CLEANOUT
N�Pj�
NATIONAL PIPE THREAD
STRUCTURAL ENGINEER,
CO2�S.
CARBON DIOXIDE SENSOR
N.T.S.
NOTTO SCALE
COL.
COLUMN
N�W�
NORTHWEST
3.0
DEMOLITION
CQMPR�
COMPRFSSOR
CONC.
CONCRETE,
O/A
OUTSIDE AIR
3.1
CONTRACTOR SHALL COORDINATE AND PHASE THIS PROJECT TO MINIMIZE BUILDING
CONN.
CONNECTION
OAD
OUTSIDE AIR DAMPER
DOWN TIME. ALL BUILDING SHUT DOWNS SHALL BE COORDINATED WrrH BUILDING
CONSTR.
CONSTRUCTION
OBD
OPPOSED BLADE DAMPER
PERSONNEL AND DONE ON OVERNIGHT HOURS,
CONT.
CONTINUOUS
O.D�
OUTSIDE DIAME.7ER OR DIMENSION
3.2
IT SHALL BE 'THE CONTRACTORS RESPONSIBILITY TO REMOVE ALL DEMOUSHED
CU
CONDENSING UNIT
OSHA
OCCUPATIONAL SAFETY & HEALTH ACT
EQUIPMENT, PIPING, MATERIALS, DEBRIS, ETC, OFF SfTE AND PROPERLY DISPOSE OF�
csj
CONSTRUCTION spEcinCATION INDEX
3.3
ALL EXIS-nNG DEMCES AND EQUIPMENT NOT SHOWN, OR IN AREAS OUTSIDE OF
CT
COOLING TOWER
PAU
PRIMARY AIR UNIT
'THE PROJECT UMITS OF CONSTRUCTION SHALL REMAIN ACTIVE, INSTALL,
CU. FT,
CUBIC FOOT
P�D.
PRESSURE DROP
NECESSARY ITEMS AS REQUIRED TO MAINTAIN THE CONTINUITY OF EXISTING DEACES
cw
CONDENSER WATER
P.E.
PROFFSSIONAL ENGINEER
PRESENTLY ATTACHED TO BUILDING ELEMENTS REMOVED OR AFFECTED SY ANY OF
cwp
CONDENSER WATER PUMP
PH�
PHASE
THE WORK OF TMS PROJECT SHALL BE RELOCATED AS REOUIRED 'TO A13OVE COUNG
CWR
CONDENSER WATER RETURN
PNI...
PANEL
UNE AND SUPPORTED FROM 7HE STRUCTURE ABOVE.
cws
CONDENSER 'WATER SUPPLY
PREFAB.
PREFABRICATED
14
OBSERVE All OF THE ACCEPTED WORK WITH THE OWNER BEFORE COMMENCING
P�S.l.
POUNDS PER SQUARE INCH
DISMANTLING PROCEDURES AND NaTE THEIR CONDMON. AW DAMAGE SUSTAINED BY
DB
DRYBULB
PSIG.
POUNDS PER SQUARE INCH GAUGE
7+4E ACCEPTED WORK FROM THE COMMENCEMENT OF THE DISMANTLING PROCEDURE
DEG. F., *F
DEGREES FAHRENHEIT
Pvc
POLYVINYL. CHLORINE
TO ITS PLACEMENT IN STORAGE SHALL BE THE RESPONSIBIUTY OF THtS
DEPT.
DEPARTMENT
PWR.
POWER
CONTRACTOR. ErrHER REPAJR THE DAMAGE 'TO THE OBSERVED CONDMON PRIOR
DIA., DIAM.
DIAMETER
TO ITS DISMANTLING TO THE SATISFACTION OF' THE OWNER OR REPLACE THE
DIFF.
DIFFUSER
ACCEPTED WORK WITH NEW AS DIRECTED ErY THE OWNER.
DIM.
DIMENSION
QUANTITY
3.5
ISOLATE THE REMAINING ACTIVE, POR'nON OF ALL EXISTING WORK INDICATED FOR
DIR.
DIRECTION, DIRECT
PARnAL REMOVAL SO THAT THE ACTIVE SERVICE CAN REMAIN IN OPERATION. THIS
DIS; DISCH
DISCHARGE
RELOCATED
INCLUDES, BUT IS NOT LlMrrED TO, EXISTING PIPING, EXIS'nNG EOUIPMENT AND OTHER
DIST'RIB�
DISTRIBUTION
RISER
EXISTING WORK INDICATED FOR REMOVAL WHICH CONNECTS TO AN ACTIVE SERVICE 'TO
DOM�
DOMESTIC WATER
R/�
RETURN AIR
REMAIN IN OPERATION, FINISH THE OPEN, ACTIVE END OF THE REMAINING WORK WITH
DN
DOWN
RAD
RETURN AIR DAMPER
MATERiALS AND METHODS MokrCHING THE EXI"ENG WORK,
DR
CLOTH DRYER
RECEP.
RECEPTACLE
16
RESTORE All EXISTING AREAS DAMAGED DUE TO THE PROGRESS OF CONSTRUCTION TO
DAfG.
DRAWING
REF.
REFRIGERATION
ITS INRAL CONDMON AT NO ADDITIONAL COST TO THE OWNER, THIS INCLUDES, BUT IS
DX
DRYER EXHAUST
REQ'D
REQUIRED
NOT UMMED TO, WALLS, COUNGS, PAJNTING, LANDSCAPING, SIDEWALXSI ROOFING,
E
EAST
RM
ROOM
DUCTWORK, PIPING, INSULATION, SUPPORTS, EOUIPMENT AND CONTROLS.
Ek
EACH
RND.
ROUND
3.7
ANY EOUIPMENT OR DEVICES TO REMAIN THAT MIGHT HAVE TO BE DISCONNECTED
'TIED
E/A
EXHAUST AIR
RPM
REVOLUTIONS PER MINUTE
BECAUSE OF THE REMOVAL OF ANY OTHER DEVICE MUST BE RECONNECTED AND
EAT
ENTERING AIR TEMPERATURE
13ACK TO THE EXISTING BUILDING SYSTEMS AND TESTED FOR CORRECT OPERATION.
EDH
ELECTRIC DUCT HEATER
S/A
SUPPLY AIR
4,0
EOUtPMENT
EDP
EER
ELECTRONIC DATA PROCESSING
ENERGY' EFFICIENCY RATING
SAN
SCH, SCHED.
SANfTARY
SCHEDULE
4.1
ALL MECHANICAL EQUIPMENT LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE
EF
EL., ELEV.
EXHAUST FAN
ELEVATION
SD
S(CDT.
SMOKE DETECTOR
SMOKE DAMPER
CONSTRUCTED AND INSTALLED TO WITHSTAND HURRICANE FORCE WINDS FROM AW
ELEC.
ELECTRICAL
s
SECTION
41
DIRECTION AS PER F.B.C.
MECHANICAL EQUIPMENT SHALL BE SUPPORTED PER MANUFACTURER RECOMMENDATIONS
EMER.
ENCL.
EMERGENCY
ENCLOSURE
SEF
SEER
SMOKE EVAC FAN
SEASONAL, ENERGY EFFICIENCY RATING
AND AS REQUIRED FOR APPUCABLE CODES AND STANDARDS, USING SOUND INDUSTRY
ENGR�
ENGINEER
SF
SQUARE FOOT, SUPPLY FAN
STANDARD PRAC"TICES. STRUCTURAL ENGINEER DESIGN AND RECOMMENDATIONS SHALL
ENT.
ENTRANCE, ENTER
SIJT�
SHEEr
BE AS FOLLOWS, SUBMIT SHOP DRAWINGS OF ALL SUPPORTING STRUCTURES THAT
EQ.
EQUAL
SIM.
SIMIIAR
CLEARLY INDICATE SIZES, MATERIAL. DESIGN AND PRODUCT APPROVAL NUMBERS.
EOUIP�
EQUIPMENT
SKZ
SMOKE ZONE
4,3
VIBRATION ISOLATORS SHALL, BE PROVIDED FOR ALL MECHANICAL EQUIPMENT WlTH
EQUIV.
EQUrVALENT
SMACNA
SHEET METAL AND AIR CONDITIONING CONTRACTORS
MOVING AND/OR ROTARY PARTS. SUBM[T SHOP DRAWINGS SHOWING, BUT NOT UMMED.
E.S.P�
EXTERNAL STATIC PRESSURE
NATIONAL ASSOCIATION INC.
ISOLATION PERFORMANCE AND ALLOWABLE SUPPORnNG L,OADS.
ET
EXPANSION TANK
S.P.
STATIC PRESSURE
4.4
FOR ALL OUTDOOR MOUNTED EOUIPMENT, PR0ADE SURFACE AND COIL PROTECnON
EXCAV.
EXCAVATION
SPECS.
SPECIFICATIONS
AGAINST CORROSION DUE TO PROXIMITY TO MARINE AND/OR CORROSIVF EWIRONMENT.
EXH�
EXHAUST
SPF
STAJR PRESSURIZATION FAN
4.5
CONTROL WIRING SRALL BE THE RESPONSIBlUTY OF THE MECHANICAL. CONTRACTOR.
EXIST (E)
EXISTING
SO.
SQUARE
THE CONTRACTOR SHALL FURNISH ALL MOTORS, STARTERS AND RELAYS, ETC., TO
"
EXP�
EXPANSION, EXPOSURE
&s.
STAINLESS STEEL
CONFORM A FULLY OPERATING SYSTEM, COORDINATE WITH THE ELECTRICAL DIVISION
EXPO.
EXPOSED
STA.
STATION
ALL WORK RELATED TO THE MECHANICAL SYSTEMS.
EXT,,
EXTERIOR
STD�
STANDARD
4.6
PROVIDE EQUIPMENT MAINTENANCE AND INSTRUCTION MANUALS, THE MANUAL SHALL
EWT
ENTFRING WATER TEMPERATURE
STL.
STEEL
ESTASUSH ALL REQUIRED SCHEDULED MAINTENANCE THAT SHALL BE PERFORMED
STRL.
STRUCTURAL
DURING THE UFE OF THE BUILDING TO GUARANTEE THE WORKING CONDITION OF THE
F.A,
FIRE ALARM
STRUC
STRUCTURES
INSTALLED SYSTEM, MANUALS SHALL BE SUBMITTED TO THE ENGINEER FOR
FC
FORWARD CURVE
SURF.
SURFACE
ACCEPTANCE.
FCO
FLOOR CLEANOUT
sym�
SYMMETRICAL
43
EQUIPMENT DATA SHOWN IN 'THE EQUIPMENT SCHEDULES IS BASED ON MANUFACTURER
FD
FIRE DAMPER
ACTUAL CATALOG. VERIFY 'THIS INFORMATION W" MANUFACTURERS PRIOR TO
FF.
nNISH FLOOR
T
TON, THERMOSTAT
PURCHASING OR INSTALUNG ANY EQUIPMENT. MANUFACTUREWS NAMES SHAU- BE
FG�
FINISH GRADE
Tclp.
TEMPERATURE CONTROL PANEL
INTERPREJED AS ESTABLISHMENT OF REQUIRED TYPE CLASS AND QUALfTY. ALL
FIG.
FIGURE
tD.
TEMPERATURE DIFFERENCE
SUBSTITUTIONS SHALL BE APPROVED BY THE PROJECT ENGINEER,
FIN.
F'INISH
TEMP.
TEMPERATURE
4.8
PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF 'THE
FIXT�
Fll)(rURE
T�0.8�
'TOP OF BEAM
MECHANICAL SYSTEM,,
Fl.
FLOW UNE
T.O.C.
TOP OF CURB, TOP OF CONCRETE
4�9
SEE EQUIPMENT SCHEDULES ON DRAWINGS FOR INFORMATION ON ALL SPECIFIED
FL.,FLR.
FLOOR
1O.D.
TOP OF DUCT
EQUIPMENT FOR THIS JOB.
FLA
FULL LOAD AMPS, FLORIDA
tO.P�
TOP OF PIPE
FLASH.
FL4SHING
TP
TOTAL PRESSURE
5�O
PIPING
FLEX.
FLEXIBLE
Tx
TOILET EXHAUST
FPM
FEET PER MINUTE
TXV
THERMAL EXPANSION VALVE
5.1
CHILLED WATER PIPING SHALL BE SCHEDUll 40 BLACK IRON PIPE WIT'li WEII)ED
FS
COOUNG TOWER FILTRXnON SYSTEM
Typ.
TYPICAL
5.2
FfMNGS OR GROOVED JOINTS AND \4CTAULIC FITTINGS.
ALL CHIU.ED WATER PIPING SHALL, BE INSULATED WITH 2* THICK CELLULAR GLASS
FSD, F/S
FIRE AND SMOKE DAMPER
Ul.
UNDERWRITERS LABORATORIES
INSULATION WITH ASJ JACKETING. PIPING EXPOSED TO THE EXTERIOR SHALL BE
FT
FEEr
U.N.O�
UNLESS NOTED OTHERWISE
PROVIDED WITH ALUMINUM JACKETING.
FURN.
FURNISH
v
VOLT, SHUT-OFF GATE VALVE, VOLUME, VALVE
5,3
PROVIDE ALL SHUT OFF VALVES, HYDRONIC SPECIALPES, 'THERMOMETERS, PRESSURE
VEL
VELOCrTY
GUAGES, CONTROL DEVICES. ETC. REQUIRED FOR A COMPLETE OPERA'nNG SYSTEM.
Ck
GAUGE
VQ
VOLUME DAMPER
GAL,
GALLON
VERT,
VERTICAL
6.0
TEST AND PALANCING
GALV�
GALVANIZED
VOL.
VOLUME
GEF
GARAGE EXHAUST FAN
VGL
GLOBE VALVE
6.1
aALANCE ALL SYSTEMS TO PROVIDE FLOW OUANTITIES, TFMPERATURES AND CAPACITIES
GPM,GAL./MlN
GALLON PER MINVrE
VFD
VARIABLE FREQUENCY DRIVE
6�2
AS INDICATED ON THE DRAWINGS.
PERFORM A COMPLETE OPERATING AND BALANCING TEST OF THE FINISHED SYSTEM.
GR.
GSF
GRILLE
GARAGE SUPPLY FAN
W.
WEST, WIRE, WATT, WIDE
PROVIDE WRITTEN REPORT OF THE RESULT OF 'THIS TEST STATING T'HE ACCEPTABILITY
'THE
w
U
WtTH
WET BULB
OF SYSTEM AND COMPLIANCE WITH THE DESIGN DOCUMENTS. TEST AND BALANCE
H�
HEIGHT, HUMIDISTAT
AGENCY SHALL BE AN INDEPENDENT, AABC OR NE88 CER-nFlED AGENCY. CONIRACTOR
HOA
HAND-OFF-AUTOMATIC
w.F.
WIDE FLANGE
SHALL COORDINATE WITH OWNER AND TESTING AND COMMISSIONING AGENCY ALL WORK
HP
HORSEPOWER
W�G�
WXrER GAUGE
FOR nNAL CERTIFICArION OF THE HVAC SYSTEM.
HPU
HEAT PUMP UNIT
WLDG.
WELDING
HWP
HOT WATER PUMP
wms
WIRE MESH SCREEN
WITHOUT
HWR
HOT WATER RETURN
Vo
WEIGHT
HWS
HOT WATER SUPPLY
HX
HEAT EXCHANGER
XFMR
TRANSFORMER
HZ�
HERTZ (CYCLES)
LD�
IN.,
INSIDE DIAMETER
INCH&S)
y
YD, YP
WYE
YARD
INCL.
INCLIDONG)
YR
YEAR
INSUL.
INSULARN
tNT�
INTERIOR
SCOPE OF WOR4
GM CONSULTING
ENGINEERS
MECHANICAL
SYMBOLS AND'LEGE-ND
"R EQ"lr"ME* T
EXISTING PIPING C �4
TO BE DEMOLISHED
NE'A' IPJPIN,�
EkSTING Pir-ING TO, RSMA�N
UNION
FLEX CONNECTOR
BUTTERFLY VALVE
GATE VALVE
BALL VALVE
7q
la
SUCTION DIFFUSER
'TRIPLE DUTY VALVE
CIRCUIT SETTER, BAL.ANCING VALVE
TWO-WAY MOTORIZED VALVE
THREE-WAY MCrTORIZED VALVE
DIRECTION OF WATER FLOW
CHECK VALVE
STRAINER
'TEE DOWN
TEE UP
ELBOW U P
ELBOW DOWN
REDUCER
THERMOMETER WITH WELL
-------- W----
'rEST WELL.
PRESSURE GAUGE WITH GAUGE VALVE
CONNECTION TO EXISTING
SCOPE OF WOR4
GM CONSULTING
ENGINEERS