14-482-007O Life Safety Plan
6 SCALE: 3A6" =1' -O'
q
"
a
m
N
Z
0
s
0
d
AM
a
J
J
U
W
a
0
0
2
a
NN
L
An
n
u
\
UNIT
UNOCCUPIED FUTURE
TENANT SPACE
C11 C
'.. ur:....,... �. i+. t' awwwi+ �. w'<«».. �, ..,*.*. .. p;.; r��wia�. .. krn++ iw�• r1; +. ! c:« .. w. www+ lttw\ �• �'!. r.r.a:.i+i.e+»,«»,�.?\wc� �.
I EXISTING UL LABELED #U419 1 HR
FIRE RATED TENANT DEMISING WALL
TO REMAIN. MAINTAIN FIRE RATING.
(V.I.F.)
II NEW UL LABELED #U419 1 HR FIRE
RATED TENANT DEMISING WALL
I
I
FUTURE
I
I C11D
EMERGENCY, EXIT LIGHTING, TENANT SPACE
I AND FIRE EXTINGUISHERS BY
FUTURE TENANT
NEW UL LABELED #U419 1 HR FIRE
- -,� RATED TENANT DEMISING WALL
z
v NEW EXIT CORRIDOR
NEW EMERGENCY LIGHT
W/ BATTERY BACK —UP
�\
'• AAA.
EXISTING UL IABELED #U41'9
1 HR FIRE RATED TENANT
DEMISING WALL TO REMAIN.
MAINTAIN FIRE RATING. (V.I.F.)
sofetq legend:
1 HR = ONE HOUR FIRE RATED SEPARATION
�- - -� TRAVEL DISTANCE
F.E. FIRE EXTINGUISHER ON MOUNTING BRACKET
3' -0" CLEAR EGRESS ACCESS
1. DURING THE PRE - CONSTRUCTION PHASE OF THIS PROJECT, THE
SPRINKLER SYSTEM WILL BE UNIMPAIRED. PERMIT DRAWINGS WILL BE
SUBMITTED BY THE LANDLORD'S SPRINKLER CONTRACTOR FOR FULL
FIRE SPRINKLER PLAN REVIEW OF THE RENOVATED AREA. FUTURE
TENANT WILL MODIFY & SUBMIT DRAWINGS FOR SPECIFIC DESIGN
REQUIREMENTS UNDER A SEPARATE PERMIT /PLAN REVIEW.
2. ALL FIRE EXTINGUISHER CABINETS LOCATED ON FIRE RATED WALLS
SHALL BE CONSTRUCTED TO MAINTAIN THE INTEGRITY OF THE RATED
WALL
3. ALL FIRE E MNGUISERS TO BE INSTALLED NOT GREATER THAN 75' -0"
ALONG THE EGRESS CORRIDOR.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND
SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO
THE AUTHORITY HAVING JURISDICTION.
1.
I
I I
BE NI STALLED I I
PER LANDLORD
SPECIFICATIONS - -
I /
I �
r
I
I
I
NEW EMERGENCY LIGHT—
EXIT SIGN COMBO W/ I
BATTERY BACK -UP
z
z
NEW EMERGENCY LIGHT NEW EXI LCK IGHT
/ BATTERY �
W BATTERY BACK -UP -
F.B.C.) FLORIDA BUILDING CODE 2010 - WITH LATEST SUPPLEMENTS
F.B.C.E. FLORIDA BUILDING CODE 2010 EXISTING - WITH LATEST SUPPLEMENTS
F.F.P.C. FLORIDA FIRE PREVENTION CODE 2010 - WITH LATEST SUPPLEMENTS
N.F.P.A. NFPA LIFE SAFETY CODE - LATEST EDITION
F.A.C.) FLORIDA ACCESSIBILITY CODE FOR BLDG. CONSTRUCTION
N.F.P.A. -10) STANDARD FOR PORTABLE FIRE EXTINGUISHERS
2. CLASSIFICATION OF WORK / ALTERATION LEVEL ANALYSIS : (F.B.C.E. SECTION 202 & 405.1)
GENERAL DEFINITIONS :
ALTERATION - ANY CONSTRUCTION OR RENOVATION TO AN EXISTING STRUCTURE OTHER THAN
A REPAIR OR ADDITION. ALTERATIONS ARE TO BE CLASSIFIED AS LEVEL 1, LEVEL 2, AND
LEVEL 3.
ALTERATION LEVEL 2
SCOPE - LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION
OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY
SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
3. CATEGORY OF REHABILITATION : (F.F.P.0 NFPA 101 SECTION 43.2.2.1.4)
RECONSTRUCTION : THE RECONFIGURATION OF A SPACE THAT AFFECTS AN EXIT OR A
CORRIDOR SHARED BY MORE THAN ONE OCCUPANT SPACE; OR THE RECONFIGURATION OF
A SPACE SUCH THAT THE REHABILITATION WORK AREA IS NOT PERMITTED TO BE OCCUPIED
BECAUSE EXISTING MEANS OF EGRESS AND FIRE PROTECTION SYSTEMS, OR THEIR
EQUIVALENT, ARE NOT IN PLACE OR CONTINUOUSLY MAINTAINED.
4. OCCUPANCY CLASSIFICATION F.B.C. SECTION 309 & 311)
F.F.P.0 NFPA 101 CH. 36 - NEW MERCANTILE OCCUP.)
F.F.P.0 NFPA 101 CH. 6 SECTION 6.1.14.1.3 -
INCIDENTAL OCCUPANCY)
GROUP M - MERCANTILE
5. SUB CLASSIFICATION OF OCCUPANCY (F.F.P.0 NFPA 101 SECTION 36.1.4.2)
MERCANTILE - CLASS "A"
6. REQUIRED SEPARATION OF OCCUPANCIES (F.B.C. TABLE 508.4)
GROUP M - MERCANTILE
(F.F.P.0 NFPA 101 TABLE 6.1.14.4.1(b)
WITH GROUP A ASSEMBLY) = 1 HOUR WITH SPRINKLER SYSTEM
WITH GROUP B BUSINESS) = 1 HOUR WITH SPRINKLER SYSTEM
WITH GROUP M (MERCANTILE) = 1 HOUR WITH SPRINKLER SYSTEM
WITH GROUP S (STORAGE -
LOW & ORDINARY HAZARD) = 1 HOUR (WITH SPRINKLER SYSTEM)
7. REQUIRED FIRE PARTITIONS :
WALLS SEPARATING INDIVIDUAL TENANT SPACES (F.B.C. SECTION 709.1.6 & 709.3)
GROUP M - MERCANTILE = 1 HOUR (WITH SPRINKLER SYSTEM)
8. TEMPORARY SEPARATION WALLS : (F.F.P.C. NFPA 1 CHAPTER 16.4.2)
16.4.2.1: PROTECTION SHALL BE PROVIDED TO SEPARATE AN OCCUPIED PORTION OF THE
STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR DEMOLITION OPERATIONS WHEN
SUCH OPERATIONS ARE CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE
OCCUPIED PORTION OF THE BUILDING.
9. APPROVED AUTOMATIC SPRINKLER SYSTEM : (F.F.P.0 NFPA 101 SECTION 9.7.1)
EXISTING TO BE ADAPTED TO NEW RE- DEMISED SPACES.
10. FIRE ALARM SYSTEM : F.F.P.C. NFPA 101 SECTION 36.4.4.4)
EXISTING TO BE ADAPTED TO NEW RE- DEMISED SPACES
11. OCCUPANT LOAD : F.B.C. TABLE 1004.1.1, F.F.P.C. NFPA 101 TABLE 7.3.1.2)
GROUP M - MERCAN ILE
TOTAL NO.
OF OCCUPANTS
- NEW FUTURE TENANT SPACE C11D 1,380 SF / 30 SF = 46
J
N n
C° ^
12. COMMON PATH OF EGRESS TRAVEL ALLOWED F.B.C. SECTION 1014.3.1)
F.F.P.0 NFPA 101 SECTION 36.2.5.3)
GROUP M = 100 FEET ALLOWED (WITH SPRINKLER SYSTEM)
13. MINIMUM AISLE EGRESS WIDTH ALLOWED F.B.C. SECTION 1017.2)
GROUP M = WINCHES
F.F.P.0 NFPA 101 SECTION 36.2.5.5)
(AS DETERMINED BY F.B.C. TABLE 1005.1 BUT NOT LESS THAN 36" INCHES)
14. EGRESS ACCESS TRAVEL DISTANCE ALLOWED F.B.C. TABLE 1016.1)
F.F.P.0 NFPA 101 SECTION 36.2.6)
GROUP M (WITH SPRINKLER SYSTEM) = 250 FEET ALLOWED
15. FIRE EXTINGUISHER ANALYSIS :
CLASSIFICATION OF HAZARD : (N.F.P.A. 10 SECTION 1 -5)
ORDINARY (MODERATE) HAZARD
(N.F.P.A. 10 SECTION 1 -5.2
MINIMUM RATED SINGLE EXTI 41.11SHER =2A
MAXIMUM FLOOR AREA PER UNIT OF A = 1500 SF
MAXIMUM FLOOR AREA FOR EXTINGUISHER = 11,250 SF
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER = 75 FEET
16. FIRE EXTINGUISHER SPECIFICATION
MANUFACTURER LARSENS
SERIES : MP- SERIES /MULTI PURPOSE DRY CHEMICAL
MODEL NO MP5 (UL RATING 2A- 10B:C)
CABINET : FULL PANEL CLEAR ACRYLICC, FULLY RECESSED, ALUMINUM
INTERIOR MODIFICATIONS ONLY
(ANY EXTERIOR MODIFICATION MAY REQUIRE
A BOARD APPEARANCE)
INIm
LL
F-
Z
O
U
W
H
oZ
zo
0
` 02
zw
ow
fj)}
U~
a
�i
T - Ill
\ I�
O�j
ROBERT ETTE, AIANCARB, LEED AP BD +C, CDP
FLORIDA REGISTERED ARCHITECT # AR 93259
LIFE SAFETY
PLAN &
ZONING CODE
ANALYSIS
E401I11:3
As Shown
March 14th, 2014
Permit Set
dJ
V
M
•
E
�'
>
•L
M
ai
.+-'
t�
M
J
V
+ j
=3
.=
ateJ
Ln
■�
�
Q
r..l
�fCCa
G
N
O
N
CL
cu
O
N
N
�i
T - Ill
\ I�
O�j
ROBERT ETTE, AIANCARB, LEED AP BD +C, CDP
FLORIDA REGISTERED ARCHITECT # AR 93259
LIFE SAFETY
PLAN &
ZONING CODE
ANALYSIS
E401I11:3
As Shown
March 14th, 2014
Permit Set