14-481R-0361.0 GENERAL HY.A.C. GENERAL NOTES 1.1 ALL WORK TO BE PERFORMED UNDER THESE DOCUMENTS SHALL CONFORM WITH THE FLORIDA BUILDING CODE, AND ALL OTHER APPLICABLE STATE AND LOCAL REGULATIONS AND ORDINANCES. 1.2 ALL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED MECHANICAL. CONTRACTOR, IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE AFTER COMPLETION OF WORK. 1.3 MECHANICAL CONTRACTOR SHALL FURNISH WRITTEN GUARANTEE THAT THE INSTALLED SYSTEM SHALL BE FREE OF MATERIALS AND WORKMANSHIP DEFECTS FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE BY THE OWNER. 1.4 MECHANICAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING HIS OWN PERMIT AND PAYING ALL PERMIT AND INSPECTION FEES. 1.5 SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS 1.6 THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO SHOW AS -BUILT CONDITIONS AT THE COMPLETION OF CONSTRUCTION. 1.7 ALL BUILDING CONSTRUCTION AFFECTED BY THE REMOVAL, RELOCATION OR INSTALLATION OF ANY PIECE OF EQUIPMENT SHALL BE REPAIRED AND FINISHED AS REQUIRED TO MATCH EXISTING CONDITIONS, OR AS DIRECTED BY THE ARCHITECTURAL DRAWINGS AND/ OR SPECIFICATIONS. 1.8 ALL MATERIALS EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLES OR SHALL HAVE A FLAME SPREAD INDEX OF NO MORE THAN 25 AND A SMOKE- DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. 1.9 PLANS AND SCHEMATICS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED. COORDINATE HVAC WORK WITH ALL PLUMBING, FIRE PROTECTION AND ELECTRICAL WORK AT THE SITE SO AS NOT TO CONFLICT IN LOCATION WITH OTHER WORK PERFORMED UNDER THIS CONSTRUCTION DOCUMENTS. 1.10 PROVIDE MULTIDISCIPLINE COORDINATION DRAWINGS FOR A/E TEAM REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF WORK. 2.0 FIELD VERIFICATION 2.1 ALL WORK SHALL BE FIELD VERIFIED BEFORE INSTALLATION AND COORDINATED WITH ALL OTHER TRADES. 2.2 WHERE INTERFERENCES OCCUR AND DEPARTURES FROM INDICATED DESIGN WILL BE REQUIRED TO DETERMINE CHANGES ON LOCATIONS, SIZES AND ELEVATIONS OF PIPING, DUCTWORK, ETC. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR THE CHANGE ACCOMPANIED BY A DETAILED DRAWING FOR APPROVAL FROM ARCHITECT / ENGINEER PRIOR TO PROCEEDING WITH ANY CHANGE OR DEPARTURES FROM CONTRACT DOCUMENTS. 2.3 COORDINATE LOCATION OF DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL ELEMENTS. PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED. 2.4 BEFORE CUTTING OR MAKING OPENINGS IN ANY BUILDING COMPONENT, CONTRACTOR SHALL VERIFY USING ANY REQUIRED MEANS THAT ITS LOAD BEARING CAPABILITY IS NOT COMPROMISED IN ANY MATTER. 3.0 EQUIPMENT 3.1 ALL MECHANICAL EQUIPMENT LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND HURRICANE FORCE WINDS FROM ANY DIRECTION AS PER F.B.C. 3.2 MECHANICAL EQUIPMENT SHALL BE SUPPORTED PER MANUFACTURER RECOMMENDATIONS AND AS REQUIRED FOR APPLICABLE CODES AND STANDARDS, USING SOUND INDUSTRY STANDARD PRACTICES. STRUCTURAL ENGINEER DESIGN AND RECOMMENDATIONS SHALL BE AS FOLLOW.S SUBMIT SHOP DRAWINGS OF ALL SUPPORTING STRUCTURES THAT CLEARLY INDICATE SIZES, MATERIAL, DESIGN AND PRODUCT APPROVAL NUMBERS. 3.3 VIBRATION ISOLATORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT WITH MOVING AND /OR ROTARY PARTS. SUBMIT SHOP DRAWINGS SHOWING, BUT NOT LIMITED, ISOLATION PERFORMANCE AND ALLOWABLE SUPPORTING LOADS. 3.4 FOR ALL OUTDOOR, MOUNTED EQUIPMENT, PROVIDE SURFACE AND COIL PROTECTION AGAINST CORROSION DUE TO PROXIMITY TO MARINE AND /OR CORROSIVE ENVIRONMENT. CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. 3.5 THE CONTRACTOR SHALL FURNISH ALL MOTORS, STARTERS AND RELAYS, ETC., TO CONFORM A FULLY OPERATING SYSTEM. COORDINATE WITH THE ELECTRICAL DIVISION ALL WORK RELATED TO THE MECHANICAL SYSTEMS. 3.6 CONDENSATE DRAIN PIPING INSTALLED ON NON -AIR CONDITIONED SPACES SHALL BE PROPERLY INSULATED. 3.7 PROVIDE EQUIPMENT MAINTENANCE AND INSTRUCTION MANUALS. THE MANUAL SHALL ESTABLISH ALL REQUIRED SCHEDULED MAINTENANCE THAT SHALL BE PERFORMED DURING THE LIFE OF THE BUILDING TO GUARANTEE THE WORKING CONDITION OF THE INSTALLED SYSTEM AND THE MAINTENANCE OF A PROPER I.A.Q. IN THE BUILDING. MANUALS SHALL BE SUBMITTED TO THE ENGINEER FOR ACCEPTANCE. 3.8 EQUIPMENT DATA SHOWN IN THE EQUIPMENT SCHEDULES IS BASED ON MANUFACTURER'S ACTUAL CATALOG. VERIFY THIS INFORMATION WITH MANUFACTURERS PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT. MANUFACTURER'S NAMES SHALL BE INTERPRETED AS ESTABLISHMENT OF REQUIRED TYPE CLASS AND QUALITY. ALL SUBSTITUTIONS SHALL BE APPROVED BY THE PROJECT ENGINEER. 3.9 PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF THE MECHANICAL SYSTEM. 3.10 SEE EQUIPMENT SCHEDULES ON DRAWINGS FOR INFORMATION ' ON ALL SPECIFIED EQUIPMENT FOR THIS JOB. 3.11 EXACT LOCATION OF ALL CEILING DIFFUSERS AND GRILLES SHALL BE COORDINATED WITH LIGHTING LAYOUT AND CEILING LAYOUT. 3.12 COORDINATE EXACT LOCATION OF THERMOSTATS WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION. 3.13 CHILLED WATER SUPPLY AND RETURN PIPING TO BE SCH 40 BLACK IRON PIPE INSULATED WITH 2" THICK CELLULAR GLASS INSULATION. 4.0 DUCTWORK 4.1 PROVIDE ALL NECESSARY ACCESS PANELS TO CONTROL VALVES, DAMPERS, SENSORS, AND ANY OTHER DEVICES NON- ACCESSIBLE OTHERWISE. 4.2 ALL SIZES SHOWN FOR LINED AND UNLINED DUCTS ARE CLEAR INSIDE DUCT DIMENSIONS. 4.3 ALL MEDIUM AND LOW VELOCITY AIR CONDITIONED DUCT SHALL BE SHEET METAL DUCTWORK IN ACCORDANCE WITH SMACNA'S SHEET METAL DUCTWORK STANDARDS. IN CONCEALED AREAS PROVIDE EXTERIOR INSULATION HAVING THE REQUIRED DENSITY AND THICKNESS TO PROVIDE A MINIMUM INSULATION VALUE OF R -6. INSULATION SHALL BE INSTALLED NOT TO COMPRESS LESS THAN 75% OF NOMINAL THICKNESS AS PER NAIMA STANDARDS. 4.4 PROVIDE VOLUME DAMPERS, TURNING VANES, ETC., IN DUCTWORK FOR PROPER AIR FLOW AND BALANCE. PROVI17 MULTIPLE VANE EXTRACTORS OR SPUTTERS WITH CONTROL RODS AT ALL OUTLL7S CONNECTED CLOSER HAN TWO DUCT DIAMETERS TO MAIN SUPPLY DUCT AND WHERE SHOWN, 4.5 VENTILATION AND EXHAUST AIR DUCTWORK SHALL BE OF GALVANIZED SHEET METAL CONSTRUCTION PER SMACNA'S STANDARDS, 4.6 EXHAUST VENTS SHALL BE LOCATED 10' MINIMUM DISTANCE FROM ANY OUTSIDE AIR INTAKE. 4.7 SEE SCHEDULES ON PLANS I )R AIR DISTRIBUTION DEVICES SPECIFICATIONS. 4.8 MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 8 FEET. PROVIDE ROUND RIGID DUCT IF LENGTH EXCEEDS 8 FEET. TEST AND BALANCING 5.0 BALANCE ALL SYSTEMS TO PROVIDE FLOW QUANTITIES AND CAPACITIES AS INDICATED ON DRAWINGS. 5.1 PERFORM A COMPLETE OPERATING AND BALANCING TEST OF THE FINISHED SYSTEM. PROVIDE WRITTEN REPORT OF THE RESULT OF THIS TEST STATING THE ACCEPTABILITY 5.2 OF THE SYSTEM AND COMPLIANCE WITH THE DESIGN DOCUMENTS. TEST AND BALANCE AGENCY SHALL BE AN INDEPENDENT, AABC OR NEBB CERTIFIED AGENCY, AND SHALL BE RETAINED BY THE OWNER. CONTRACTOR SHALL COORDINATE WITH OWNER AND TESTING AND COMMISSIONING AGENCY ALL WORK FOR FINAL CERTIFICATION OF THE HVAC SYSTEM. DESIGN CONDITIONS - SUMMER OUTDOOR TEMPERATURES = 91'F DRY BULB / 79'F WET BULB, SUMMER INDOOR TEMPERATURE = 75'F. - WINTER OUTDOOR TEMPERATURE = 44'F. WINTER INDOOR TEMPERATURE = 687. - OUTSIDE AIR FOR VENTILATION 1S PROVIDED TO EACH AREA IN ACCORDANCE WITH PARAGRAPH 403, CHAPTER 4 OF THE FLORIDA BUILDING CODE 2010 - MECHANICAL. - TOILET ROOMS ARE EXHAUSTED AT 50 CFM PER TOILET OR URINAL SYMBOLS AND LEGEND HVAC DESIGN REQUIREMENTS CFM CUBIC FEET PER MINUTE. YES R/A RETURN AIR. DUCT SMOKE DETECTOR (EXISTING) E/A EXHAUST AIR. X S/A SUPPLY AIR X 0/A OUTSIDE AIR SMOKE DAMPER(S) AHU AIR HANDLING UNIT SQUARE PANEL FACE VAV VARIABLE AIR VOLUME BOX X EF EXHAUST FAN FIRE RATED ROOF /FLOOR CEILING ASSEMBLY EXIST. EXISTING NECK: SEE PLANS CHWS(R) CHILLED WATER SUPPLY (RETURN) X VFD VARIABLE FREQUENCY DRIVE SMOKE CONTROL 0 DIAMETER (ALUMINUM) ROOM TEMPERATURE SENSOR /THERMOSTAT O TOTAL HEATING CAPACITY MBH NUMBER NEXT TO SYMBOL DENOTES A/C 1 UNIT TAG. WHITE DIRECTION OF VENTILATION /RETURN AIR FLOW MCA / MOCP AMP 0100 DIFFUSER / GRILLE TAG 34 SUPPLY WITH AIR VOLUME \2./ QX AXB RETURN GRILLE TAG SEE AND SIZE ALUMINUM OPPOSED ®� CEILING SUPPLY DIFFUSER / REGISTER DIFFUSER -�`--� CEILING RETURN GRILLE 3100 -1 ® EXHAUST GRILLE � EXISTING DUCT, DEVICE OR EQUIPMENT 0.125 TO REMAIN 9,107 EXISTING DUCT, DEVICE OR EQUIPMENT 175 TO BE DEMOLISHED. 1,422 FLEXIBLE DUCT ENTERING AIR TEMPERATURE (DB /WB)' F DUCT TURN DOWN 4,450 C PIPE, TUBING OR ROUND DUCT TURN DOWN SURFACE MOUNT O PIPE, TUBING OR ROUND DUCT TURN UP LOUVERED FACE ---�- DUCT REDUCER METALAIRE MANUAL VOLUME DAMPER (MVD) MOTORIZED CONTROL DAMPER. LOW LEAKAGE NECK: 22x22 TYPE, OPPOSED AIR FOIL BLADE WITH a ACTUATOR OUTSIDE AIR FLOW. 0.76. SD SMOKE DETECTOR (ALUMINUM) T -BAR LAY IN DD VII MOTORIZED VALVE FACE: 2424 COOLING ONLY VAV BOX ALUMINUM OPPOSED VAV BOX WITH ELECTRIC HEAT EXHAUST GRILLE FSD COMBINATION FIRE /SMOKE DAMPER HVAC DESIGN REQUIREMENTS MARK YES NO DUCT SMOKE DETECTOR (EXISTING) REMARS/ X FIRE DAMPER(S) X MODEL NO. SMOKE DAMPER(S) X SQUARE PANEL FACE FIRE RATED ENCLOSURE X ALUMINUM OPPOSED FIRE RATED ROOF /FLOOR CEILING ASSEMBLY X NECK: SEE PLANS FIRE STOPPING X AHU -5 SMOKE CONTROL X (ALUMINUM) AIR DISTRIBUTION SCHEDULE MARK DESCRIPTION SIZE MANUFACTURER REMARS/ SERVER ROOM PEOPLE OUTSIDE AIR NOMINAL TONS MODEL NO. ACCESSORIES A SQUARE PANEL FACE FACE: 2424 METALAIRE ALUMINUM OPPOSED I CEILING SUPPLY DIFFUSER NECK: SEE PLANS 5750 -6 AS BLADE DAMPER AHU -5 OFFICE AREA TOTAL COOLING CAPACITY MBH (ALUMINUM) 32 TOTAL HEATING CAPACITY MBH - ELECTRICAL CHARACTERISTICS V /0 /Hz WHITE OFFICE AREA MCA / MOCP AMP 17/20 34 T -BAR LAY IN \2./ ROUND CEILING SUPPLY SEE METALAIRE ALUMINUM OPPOSED TOTAL AIR SUPPLY CFM DIFFUSER PLANS 3100 -1 BLADE DAMPER � EXTERNAL STATIC PRESSURE I.W.G. 0.125 (ALUMINUM) 9,107 0.06 175 5 1,422 BLACK ENTERING AIR TEMPERATURE (DB /WB)' F 75.0 / 62.0 4,450 SPACE PRESSURIZATION; SURFACE MOUNT z = LOUVERED FACE FACE: 2424 METALAIRE WHITE RETURN GRILLE NECK: 22x22 RHE -6 a FAN MOTOR FLA AMP 0.76. AT ALL TIMES THAT THE SPACE IS OCCUPIED. (ALUMINUM) T -BAR LAY IN DD LOUVERED FACE FACE: 2424 METALAIRE ALUMINUM OPPOSED EXHAUST GRILLE NECK: SEE PLANS RHE -6 BLADE DAMPER UNIT MANUFACTURER MITSUBISHI (ALUMINUM) WHITE z MODEL NUMBER MUY- GE24NA T -BAR LAY IN 0 " EXISTING EXISTING EXISTING o AMBIENT TEMPERATURE F DIFFUSER TO z D 0 REMAIN REFRIGERANT R NOTES: 1 REFER TO PLANS FOR QUANTITY, LOCATION AND AIR THROW PATTERN. 2 NECK SIZES FOR CEILING DIFFUSERS SHALL BE EQUAL TO CONNECTING DUCTWORK, REFER TO PLANS FOR SIZES. 2 COORDINATE EXACT LOCATIONS, ELEVATIONS AND FINISHES WITH ARCHITECT. A ► DUCTLESS A/C EQUIPMENT SCHEDULE ► UNIT MANUFACTURER MITSUBISHI NET OCCUPIABLE AREA SERVED AREA SERVED SERVER ROOM PEOPLE OUTSIDE AIR NOMINAL TONS 2 � PROVIDED I SF CFM SF I SYSTEM SEER 19 O E- r�' Co AHU -5 OFFICE AREA TOTAL COOLING CAPACITY MBH 22,5 32 TOTAL HEATING CAPACITY MBH - ELECTRICAL CHARACTERISTICS V /0 /Hz 208- 230/1/60 OFFICE AREA MCA / MOCP AMP 17/20 34 UNIT DESIGNATION AC -1 z"'LL_¢ MODEL NUMBER MSY- GE24NA OFFICE AREA TOTAL AIR SUPPLY CFM 650 f- 5 80 � EXTERNAL STATIC PRESSURE I.W.G. 0.125 0 9,107 0.06 175 5 1,422 o ENTERING AIR TEMPERATURE (DB /WB)' F 75.0 / 62.0 4,450 SPACE PRESSURIZATION; z = LEAVING AIR TEMPERATURE (DB /WB)' F 55.0 / 54.0 1. OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY AS PER 2010 FLORIDA BUILDING - CODE - MECHANICAL TABLE 403.3. a FAN MOTOR FLA AMP 0.76. AT ALL TIMES THAT THE SPACE IS OCCUPIED. WEIGHT Ibs. 37 UNIT DESIGNATION CU -1 L T_ 000 UNIT MANUFACTURER MITSUBISHI Q z MODEL NUMBER MUY- GE24NA Q o AMBIENT TEMPERATURE F 95 z D 0 REFRIGERANT R 410A a N 0 MIN. PIPE SIZE O.D. (UQ. /GAS) INCHES 3/8 / 5/8 N U COMPRESSOR MOTOR RLA AMP 12.9 a CONDENSER FAN MOTOR FLA AMP 0.93 WEIGHT Ibs. 119 NOTES: 1. UNIT AHU -1 SHALL BE WALL MOUNTED COOLING ONLY, MINI -SPLIT TYPE AS INDICATED ON DRAWINGS. 2. SIZE REFRIGERATION PIPING AS PER MANUFACTURER RECOMMENDATIONS, OVERSIZE LINES AS REQUIRED TO COMPENSATE FOR LINE LOSS WITH MINIMUM CAPACITY REDUCTION. SUBMIT SHOP DRAWINGS. 3. AIR HANDLING UNIT SHALL CONTAIN SOLID STATE INTERLOCK BOARD WITH BUILT IN FUSE AND TIME DELAY RELAY. 4. PROVIDE 5 YEAR WARRANTY ON ALL REFRIGERATION COMPONENTS. 5. PROVIDE ALL RELAYS, TRANSFORMERS, ETC. AS REQUIRED FOR COMPLETE OPERATING SYSTEM. 6. UNITS SHALL BE PROVIDED WITH A SYNTHETIC MINIPLEAT FILTER. UNIT CONSTRUCTION AND INSTALLATION SHALL GUARANTEE AN EASY ACCESS TO FILTER SECTION FOR PROPER FILTER INSPECTION AND REPLACEMENT. 7. UNIT INSULATION AND ADHESIVE SHALL COMPLY WITH NFPA 90A REQUIREMENTS FOR FLAME SPREAD AND SMOKE GENERATION. INSULATION SHALL CONTAIN AN EPA REGISTERED IMMOBILIZED ANTI- MICROBIAL AGENT TO EFFECTIVELY RESIST THE GROWTH OF BACTERIA AND FUNGI IN ACCORDANCE WITH ASTM STANDARDS G21 AND G22. 8. FAN MOTOR SHALL BE HIGH EFFICIENCY TYPE, 9. FAN AND MOTORS SHALL BE PROVIDED WITH CIRCUIT PROTECTION. 10. CONDENSATE DRAIN PANS SHALL BE INSULATED AND SLOPED TO OUTLET. PANS SHALL HAVE STAINLESS STEEL LINERS. PROVIDE A OVERFLOW DETECTION SYSTEM CAPABLE OF SHUTDOWN THE UNIT UPON DETECTION OF HIGH LEVELS CONDENSATE DRAIN. 11. SUPPORT UNIT HIGH ENOUGH ABOVE CEILING TO ACCOMMODATE CONDENSATE DRAIN TRAPS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. 12. THE FAN DRIVE SHALL BE SELECTED FOR 125% OF THE MOTOR RATED HORSEPOWER. 13. CONTRACTOR SHALL GUARANTEE ADEQUATE CLEARANCE ALL AROUND THE UNIT FOR MAINTENANCE ACCESS. 14. CONDENSING UNIT SHALL BE INSTALLED TO WITHSTAND WIND PRESSURE FROM ANY DIRECTION AS PER THE "HVHZ" REQUIREMENTS OF THE F.B.C. 15. ALL UNITS SHALL BE PROVIDED WITH INSULATION LINERS TO PREVENT SURFACE CONDENSATION UNDER ALL CONDITIONS. 16. CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD. 17. UNIT SHALL BE PROVIDED WITH A PROGRAMMABLE DIGITAL THERMOSTAT AS RECOMMENDED BY UNITS MANUFACTURER AND SHALL BE CAPABLE OF PROVIDING AFTER HOURS SET BACK FOR ENERGY EFFICIENCY PURPOSES. OUTSIDE AIR CALCULATION SCHEDULE A/C EQUIP. TAG No. AREA SERVED NET OCCUPIABLE AREA SERVED AREA OUTSIDE AIR PEOPLE PEOPLE OUTSIDE AIR TOTAL OUTSIDE AIR CFM REQUIRED PROVIDED ❑ SF CFM SF CFM PERSON O E- r�' Co AHU -5 OFFICE AREA 2,033 0.06 32 5 282 700 AHU -6 OFFICE AREA 2,102 0.06 34 5 297 z"'LL_¢ 450 AHU -7 OFFICE AREA 486 0.06 10 5 80 g 300 AHU -8 OFFICE AREA 9,107 0.06 175 5 1,422 U 3,000 TOTAL 4,450 SPACE PRESSURIZATION; 4,450 CFM 0/A - 3,675 CFM EXH. = 775 CFM POSITIVE �v NOTES 1. OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY AS PER 2010 FLORIDA BUILDING - CODE - MECHANICAL TABLE 403.3. 2. THE FULL VOLUME OF OUTDOOR AIR ESTABLISHED IN THIS SCHEDULE SHALL BE DELIVERED AT ALL TIMES THAT THE SPACE IS OCCUPIED. w 2\ Z z 0 U LLZl ❑ w X w Z) 0 { ❑ w 0 z Q N ❑ z 0 0 N ' c� w z c� 0 0 w 0 w F Q Q ❑ U z 0 U w z 3 0 Z 0 0 J N z 0 z I ❑ w s 0 z Q 0 z U 0 0 0 w U z U a Z Q 0 O 0 ti 0 z z 0 U z 0 U _ c� � z v 0 a 0 z 0 0 z 0 U z Z 0 z w ❑ z a a w > ❑ z a U w z GM CONSULTING U ENGINEERS = N \\ 5001 SW 74th COURT o SUITE #204 myF � '* MIAMI, FLORIDA 33155 3, 11�'` .;,I \ Q PHONE: 305 663 -2944 t_ f i \ FAX: (305) 663 -2970 0 1 \ E -MAIL: office® m- ce.net � w O� C� O z z❑ LL a w �� Li Q � U Z z w :2 Z Q w Z w w I V) 0 0 LL- z 0 U (D � � CV w cy) ,! J ❑ LL EL O _cam w o _ r� 0 L V CHRISTIAN A. VIDAL, AIA LICENSE NO. AR96861 ARCHITECT CONSULTANT scale: as shown ........... ... .................... release date: April 17, 2014 drawn by choked by: M -2 SHEET NO. Z CA N 0000 V) �00N ❑ W - O E- r�' Co Lu -L0'0 Z � Ln .o a M (N z"'LL_¢ ¢ Q g IL w � I U Jo Q IL Wo �v U 00 w - • w m L T_ 000 Uo' cy c� U Q [ J Q D N N 0 � w O� C� O z z❑ LL a w �� Li Q � U Z z w :2 Z Q w Z w w I V) 0 0 LL- z 0 U (D � � CV w cy) ,! J ❑ LL EL O _cam w o _ r� 0 L V CHRISTIAN A. VIDAL, AIA LICENSE NO. AR96861 ARCHITECT CONSULTANT scale: as shown ........... ... .................... release date: April 17, 2014 drawn by choked by: M -2 SHEET NO.