14-481-023STEEL CONCRETE FLOOR 3M FIRE BARRIER CP 25WB+ CAULK STEEL SLEEVE (OPTIONAL) MINERAL WOOL PACKING CONSULT CURRENT UNDERWRITERS LABORATORIES "FIRE RESISTANCE DIRECTORY" FOR DETAILS UL SYSTEMS CA 1044 PENETRATION OF PIPE /CONDUIT - UL SYSTEM #: CAJ 1044 THRU 1,2,3,OR 4 HOUR FLOOR NOT TO SCALE 1 OR 2 HOUR FIDG DATPM GYPSUM WALL ASSEMBLY METAL PIPE WOOL PACKING 1M FIRE BARRIER CP ?5WB+ CAULK STEEL SLEEVE ' ' ' ' ' ' CONSULT CURRENT UNDERWRITERS LABORATORIES, INC. "FIRE RESISTANCE DIRECTORY" FOR DETAILS. UL SYSTEM WL1003 PENETRATION OF PIPE /CONDUIT - UL SYSTEM #: WL1003 THRU 1 OR 2 HR. GYP. BD. WALL NOT TO SCALE O O ch M 00 v 48" 48" 00 v x (A) CLEAR FLOOR SPACE 30" (B) FORWARD APPROACH � 48" x of MI NOTE: X 18" NOTE: X 24" (D) CLEAR FLOOR SPACE IN ALCOVES 30" 6" 48" 12" PARALLEL APPROACH NOTE: IF X > 24" THEN AN ADDITIONAL NOTE: IF X > 15" THEN AN MANUEVERING CLEARANCE OF 6" ADDITIONAL MANUEVERING SHALL BE PROVIDED AS SHOWN CLEARANCE OF 12" SHALL BE PROVIDED AS SHOWN (E) ADDITIONAL MANEUVERING CLEARANCES FOR ALCOVES MIN. CLR. FLOOR SPACE FOR WHEELCHAIRS F. A. C. 2010 MANEUVERING CLEARANCES FOR WHEELCHAIRS NOT TO SCALE Z F�l PULL SI DE 18" MIN X 00 24" PREFERED PULL SIDE ) NOTE: X= 36" MIN. IF Y= 60" X= 42" MIN. IF Y= 54" _x 24" MIN i Z PULL SIDE r� a v ,I NOTE: Y= 54" MIN. IF DOOR HAS A CLOSER z � z 00 X 54" MIN 24" MIN } x �.. v n PUSH SIDE V z PUSH SIDE � rN a PUSH SIDE ' 1 v NOTE: Y= 48" MIN. IF DOOR HAS NOTE: X= 12" IF DOOR HAS BOTH NOTE: Y= 48" MIN. IF DOOR HAS A CLOSER A CLOSER AND A LATCH BOTH A CLOSER AND A LATCH (C) (A) (B) LATCH SIDE APPROACHES - SWINGING DOORS FRONT APPROACHES -SWING DOORS HINGE SIDE APPROACH- SWINGING DOORS NOTE: ALL DOORS IN ALCOVES SHALL COMPLY WITH THE CLEARANCES FOR FRONT APPROACHES MANEUVERING CLEARANCES AT DOORS FLORIDA ACCESSIBILITY CODE 2010 NOT TO SCALE SYMBOLS: ALIGN ALIGN FINISHED SURFACES # INTERIOR ELEVATION ® KEYED NOTE 1/2f- 0 A -0.0 SECTION ROOM NAME ROOM /FLOOR INDICATOR OOM NUMBE (E) DENOTES EXISTING (R) DENOTES RELOCATED FE (T FIRE EXTINGUISHERS FEC FIRE EXTINGUISHER CABINET m B.O. CEILING CEILING HEIGHT EL. +0' -0" A.F.F. 0.00 FLOOR HEIGHT ABBREVIATIONS ADJ ADJACENT AFF ABOVE FINISHED FLOOR ALT ALTERNATE BLDG BUILDING BC BELOW CEILING BRG BEARING BRK BRICK BS BOTH SIDES BTW BETWEEN BW BOTH WAYS CAB CABINET CJ CONSTRUCTION JOINT CL CENTER LINE CLG CEILING CLKG CALKING CLR CLEAR COL COLUMN CONC CONCRETE CONST CONSTRUCTION CONTR CONTRACTOR /CONTRACT CTR CENTER DBL DOUBLE DEMO DEMOLISH /DEMOLITION DF DRINKING FOUNTAIN DIA, DIAMETER DIM DIMENSION DN DOWN DR DOOR DTL DETAIL DWG DRAWING DWR DRAWER (E) EXISTING EA EACH EL ELEVATION EQ EQUAL EQUIP EQUIPMENT E.T.R. EXISTING TO REMAIN (F) FUTURE FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER AND FINISH SAMPLES OF ALL FINISHES & WORK (i.e. CABINETRY, MILLWORK ETC.) FOR CABINET FF FINISHED FLOOR/ FACE FIN FINISH FLR FLOOR /FLOORING FLUOR FLUORESCENT FO FINISH OPENING FOB FACE OF BRICK FOC FACE OF CONCRETE FOM FACE OF MASONRY FOP FACE OF PANEL FOS FACE OF STUD FOW FACE OF WALL FR FRAME FURN FURNITURE GLS GLASS GWB GYPSUM WALL BOARD GYP GYPSUM HDWR HORIZ HT HVAC HW INSUL LT MAT MAX MECH MFR MIN MIR MISC MTD N/A NIC NRC NTS OFCI OFOI OPP PB P LAM PERP RB RCP REC RECEP REFR REV RO SCHED SIM STD SYST TBD TEL TH TM E TS TYP LON VAR V CT VENT V ERT VIF W/ W/O WKSF GENERAL NOTES: 1. ALL WORK TO BE PERFORMED IN ACCORDANCE WITH ALL CODES AND ORDINANCES. REVISIONS 2. INFORMATION CONTAINED IN THESE DRAWINGS IS BASED ON PARTIAL FIELD JUSTICE ON OCTOBER 1991. THE CONTRACTOR AND SUBCONTRACTORS SHALL BE MEASUREMENTS. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, AND NOTIFY G. - - ALVAREZ STUDIO OF ANY DISCREPANCIES. IN ADDITION, CONTRACTOR SHALL NOTIFY HEIGHT G. ALVAREZ STUDIO IMMEDIATELY SHOULD EXISTING CONDITIONS PROHIBIT EXECUTION LEVEL THROUGHOUT, OR SHALL BE CONNECTED BY PEDESTRIAN RAMPS, PASSENGER OF THE DESIGN INTENT OF THE DRAWINGS. ANY ADDITIONAL WORK, DEMOLITION NORTH ARROW AND /OR REMOVAL AS A RESULT OF FAILURE TO DO SO WILL BE AT THE CONTRACTORS HEATING, VENTILATING, EXPENSE. FLOOR TRANSITION 3. CONTRACTOR SHALL FURNISH ALL ITEMS ON THE DRAWINGS UNLESS SPECIFICALLY INSPECTOR OR BUILDING DEPARTMENT INSPECTOR. NOTED OTHERWISE. CONTRACTOR SHALL FURNISH MECHANICAL, ELECTRICAL, PLUMBING AND OTHER HOOKUPS TO BOTH CONTRACTOR FURNISHED AND INSTALLED AND MAINTAIN A DEFLECTION OF L/240 PER THE S.F.B.C. (CURRENT EDITION) SECTION ITEMS, TENANT - FURNISHED CONTRACTOR - INSTALLED ITEMS AND TENANT FURNISHED 2. AND INSTALLED ITEMS UNLESS SPECIFICALLY NOTED OTHERWISE. CONTRACTOR SHALL INSULATION FURNISH ALL REQUIRED MATERIALS AND LABOR NECESSARY TO ENSURE A COMPLETE WHICHEVER GOVERNS. INSTALLATION OF TENANT - FURNISHED CONTRACTOR - INSTALLED ITEMS. 4. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING FLOOR FINISH MATERIALS MATERIAL TO ENSURE THAT THE TRANSITIONS BETWEEN FLOORING MATERIALS WILL BE SMOOTH ACCORDANCE WITH UNDERWRITERS LABORATORY TEST ASSEMBLY UL 1479. AND IN ACCORDANCE WITH THE MAX TOLERANCES PRESCRIBED IN THE DRAWINGS. 15. FAILURE TO COMPLY W/ SUCH TOLERANCES WILL RESULT IN REJECTION OF THE WORK MECHANICAL AT THE CONTRACTORS EXPENSE. 5. ALL CUTTING AND PATCHING SHALL BE PERFORMED IN A NEAT WORKMANLIKE 16. MANNER. ANY EXISTING FINISHES DISTURBED OR DAMAGED BY THE CONTRACTOR MINIMUM DURING THE COURSE OF THE WORK SHALL BE REPAIRED TO MATCH EXISTING IN KIND FLAME SPREAD AND SMOKE GENERATION. OF FINISH. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR RESTRICTING AND CONTAINING DUST AND MISCELLANEOUS DEBRIS GENERATED FROM THE DEMOLITION AND CONSTRUCTION BY MEANS OF SURFACES SHALL MATCH EXISTING ADJACENT SURFACES UNLESS OTHERWISE TEMPORARY PARTITIONS OR BARRIERS AS REQUIRED. 7. THE GENERAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONCEALED FIRE MOUNTED TREATED WOOD BLOCKING WHERE REQUIRED FOR MILLWORK ITEMS (WOOD PANELING AND WALL HUNG CABINETRY. 8. START OF APPLICATION OF ANY PAINT OR WALL COVERING MATERIALS WILL 4. CONSTITUTE ACCEPTANCE OF SURFACES BY EACH SPECIFIC SUBCONTRACTOR AND SPRINKLER CONTRACTOR SHALL PROVIDE SHOP DRAWINGS PRODUCED BY A FLORIDA ASSUMPTION OF RESPONSIBILITY FOR ALL SUBSEQUENT FINISHING AND RESULTS U = THEREOF. 9. REFER TO ENGINEERING DOCUMENTS FOR ALL ELECTRICAL, TELEPHONE, REQUIRED BY THE LOCAL MUNICIPALITY. MECHANICAL, STRUCTURAL, PLUMBING, AND FIRE SPRINKLER REQUIREMENTS. MAY 19. ANY DISCREPANCY BETWEEN THE ARCHITECT AND ENGINEER DOCUMENTS BE NOT TO SCALE ENCOUNTER, GC SHALL CONTACT ARCHITECT FOR CLARIFICATION. 10. CONTRACTOR SHALL PROVIDE G. ALVAREZ STUDIO WITH DETAILED SHOP DRAWINGS AND FINISH SAMPLES OF ALL FINISHES & WORK (i.e. CABINETRY, MILLWORK ETC.) FOR OWNER FURNISHED, APPROVAL. 11. ALL WALL CEILINGS ARE TO BE LEVEL 5 FINISH U.N.O. PLUMB AND STRAIGHT (RIPPLE v v FREE). 12. ALL WORK SHALL BE IN ACCORDANCE WITH A.D.A. ACCESSIBILITY GUIDELINES AS SET CONTRACTORS SHALL MAINTAIN THE INTEGRITY OF THE FIRE ENVELOPE DURING FORTH IN THE "AMERICANS WITH DISABILITIES ACT HANDBOOK ", AS PUBLISHED BY THE HARDWARE DISABLED ACCESS NOTES: --- =- -_ EQUAL EMPLOYMENT OPPORTUNITY COMMISSION AND THE U.S. DEPARTMENT OF 1. PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 2 -A JUSTICE ON OCTOBER 1991. THE CONTRACTOR AND SUBCONTRACTORS SHALL BE HORIZONTAL - - RESPONSIBLE FOR THE IMPLEMENTATION OF SUCH. HEIGHT LEVEL THROUGHOUT, OR SHALL BE CONNECTED BY PEDESTRIAN RAMPS, PASSENGER 13. CONTRACTOR SHALL INSTALL THESE ASSEMBLIES IN ACCORDANCE WITH THE HEATING, VENTILATING, ELEVATORS OR SPECIAL ACCESS LIFTS. - - - MANUFACTURERS SPECIFICATIONS, THE GYPSUM ASSOCIATION STANDARDS. THE AIR CONDITIONING INSPECTOR OR BUILDING DEPARTMENT INSPECTOR. CONTRACTOR SHALL PROVIDE FOR A LIVE LOAD OF 5 POUNDS PER SQUARE FOOT fie LU AND MAINTAIN A DEFLECTION OF L/240 PER THE S.F.B.C. (CURRENT EDITION) SECTION HOT WATER 2. 2305.5 OR THE STANDARD BUILDING CODE (CURRENT EDITION) SECTION 1604, INSULATION 2. WHICHEVER GOVERNS. LIGHT 14. ALL PENETRATION FIRE STOPS FOR METAL PIPE AND INSULATED PIPE SHALL BE IN MATERIAL DRAWINGS, AND ADDITIONAL SIGNS AS REQUIRED BY BUILDING DEPARTMENT ACCORDANCE WITH UNDERWRITERS LABORATORY TEST ASSEMBLY UL 1479. MAXIMUM 15. THERE SHALL BE NO COMMUNICATION OF ELECTRICAL/ DATA BOXES LOCATED BACK MECHANICAL g TO BACK. MANUFACTURER 16. ALL FINISHES SHALL MEET THE REQUIREMENTS OF NFPA 101 (2006) SECTION 10.1 FOR MINIMUM - - - - FLAME SPREAD AND SMOKE GENERATION. MIRROR 17. CONTRACTOR SHALL PATCH AND REPAIR ALL AREAS AFFECTED BY THE WORK. ALL MISCELLANEOUS SURFACES SHALL MATCH EXISTING ADJACENT SURFACES UNLESS OTHERWISE MAINTAIN AISLES AT LEAST 44" WIDE AT PUBLIC AREAS. INDICATED. MOUNTED NOT APPLICABLE 18. ALL SPRINKLER DRAWINGS IF REQUIRED ARE NOT A PART OF THIS CONTRACT. 4. EVERY EXIT DOOR SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY SPRINKLER CONTRACTOR SHALL PROVIDE SHOP DRAWINGS PRODUCED BY A FLORIDA NOT IN CONTRACT U = REGISTERED PROFESSIONAL ENGINEER AND SHALL BE SIGNED AND SEALED AS NOISE REDUCTION 5. REQUIRED BY THE LOCAL MUNICIPALITY. COEFFICIENT 19. CONTRACTOR SHALL PROVIDE (1) 2A -40BC FIRE EXTINGUISHER FOR EVERY 2,500 S.F. NOT TO SCALE A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE LOCATION AS PER DRAWING OR AS DIRECTED BY THE FIELD FIRE INSPECTOR *F.E. - FIRE EXTINGUISHERS AND FULLY - RECESSED FIRE EXTINGUISHER CABINET & FIRE OWNER FURNISHED, M V EXTINGUISHER SS2409 -5R ARCHITECTURAL CABINET; MP -5 5LB. FIRE EXTINGUISHER. CONTRACTOR INSTALLED v v STAINLESS STEEL FINISH OWNER FURNISHED, 20. CONTRACTORS SHALL MAINTAIN THE INTEGRITY OF THE FIRE ENVELOPE DURING OWNER INSTALLED OPENING HARDWARE. MOUNT DOOR OPENING HARDWARE 36" ABOVE FLOOR DEMOLITION AND CONSTRUCTION. OPPOSITE 21. THESE PLANS AND ALL SPECIFICATIONS WITHIN SHALL COMPLY WITH ALL APPLICABLE PANIC BAR CODES. PLASTIC LAMINATE 22. CONTRACTOR SHALL PROVIDE 20 GA. METAL STUDS, 16" O.C. AT ANY WALL HUNG PERPENDICULAR 7. MILLWORK LOCATIONS, WITH WOOD BLOCKING AT REQUIRED FOR LOAD. TYP. 7. MAXIMUM PULL OR PUSH EFFORT TO OPERATE DOORS SHALL NOT EXCEED 8.5 THROUGHOUT 11. ALL NEW AND EXISTING DOORS IN TENANT SPACE SHALL COMPLY RUBBER BASE MORE PERSONS AND IN ANY HAZARDOUS AREA. WITH NFPA 101, SEC. 521.5. REFLECTED CEILING PLAN 0 0 23. SPECIFICATION ARE INTENDED TO DENOTE QUALITY ONLY U.N.O.; THE RECESSED 8. MANUFACTURER, OR PROVIDER OF THE ITEMS, ARE AT THE SOLE DISCRETION OF THE RECEPTACLE FOLDING DOORS. CORRESPONDING DEVICES OR AUTOMATIC DOOR OPERATORS LANDLORD. REFRIGERATOR 24. ANY CHANGES, ADDITIONS, DELETIONS OR SUBSTITUTIONS SHALL BE AT THE SOLE REVISION EXPENSE OF TENANT. NO EXCHANGES OR CREDITS ARE GIVEN FOR QUANTITIES REQUESTED THAT ARE LESS THAN THOSE PROVIDE BY LANDLORD. ROUGH OPENING /ROUGH • CLASS I, FLAME SPREAD 0 -25, SMOKE DENSITY 150, FOR MATERIALS INSTALLED IN 25. ALL ABOVE BUILDING - STANDARD ITEMS PURCHASED BY TENANT SHALL MEET MINIMUM SCHEDULED VERTICAL EXITS. STATE AND LOCAL CODES. SIMILAR 26. ALL FINISH SELECTIONS ( WHETHER BUILDING STANDARD OR ABOVE) SHALL BE STANDARD IDENTIFIED BY TENANT PRIOR THE COMMENCEMENT OF CONSTRUCTION. SYSTEM(S) WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. 27. CONTRACTOR SHALL COORDINATE W/ TENANT'S FURNITURE AND LOW VOLTAGE TO BE DETERMINED CONSULTANTS (ALARM, SECURITY, LOCAL ACCESS, DATA, TELEPHONE, AUDIO VISUAL, TELEPHONE VIDEO CONFERENCING, ETC.) BY TENANT. THICKNESS 28. CONTRACTOR SHALL COORDINATE WITH LANDLORD /TENANT/ TENANT CONSULTANT TO MATCH EXISTING ALL CORE DRILLING. CONTRACTOR TO X -RAY CONCRETE SLAB PRIOR TO CORE INSTALLED IN ANY OTHER LOCATION. DRILLING., (TYP.) TUBE STEEL TYPICAL MILLWORK WIDTH AND NOT LESS THAN 6-8" IN HEIGHT. DOORS SHALL BE CAPABLE OF 9. DECORATIONS (CURTAINS, DRAPES, SHADES, HANGINGS, ETC.) SHALL BE NOTES: UNLESS OTHERWISE NOTED VARIES VINYL COMPOSITION TILE VENTILATOR /VENTILATION VERTICAL VERIFY IN FIELD WITH WITHOUT WORKSURFACE 1. ALL WOOD & CASEWORK, BLOCKING, GROUNDS, ROUGH BUCKS, AND MISCELLANEOUS BLOCKING TO BE FIREPROOF IN ACCORDANCE WITH MUNICIPAL CODE. (INSTALLED BY CABINET CONTRACTOR EXCEPT OTHERWISE NOTED). 2. WHERE ELECTRICAL WORK IS SPECIFIED IN CASEWORK, LAMPS AND LIGHTING FIXTURES ARE TO BE PROVIDED BY THE CABINET CONTRACTOR, CUTOUTS FOR SWITCHES/ RECEPTACLES/ WIRING SHALL BE COORDINATED WITH THE ELECTRICAL CONTRACTOR. 3. PRIOR TO ROUGH -IN IS COMPLETED ALL MEANS OF FASTENING SHALL BE CONCEALED. REFER TO ELEVATIONS FOR ALIGNMENT. ALL WALL MOUNTED COUNTER SURFACES SHALL HAVE CONCEALED FASTENERS/ SUPPORTS 4. ALL DRAWERS TO HAVE FULL EXTENSION SLIDES & SOFT CLOSE HARDWARE BY HAFELE OR APPROVED EQUAL U.O.N. REFER TO DRAWINGS FOR FURTHER SPECIFICATIONS. 5. PROVIDE 2 1/2" DIAMETER GROMMETS PER 5 LIN. FT. OF WORK TOP. LOCATION TO BE DETERMINED ON SHOP DRAWINGS. FINISH TO MATCH MILLWORK HARDWARE. 6. ALL CABINET DOORS SHALL HAVE EURO /CUP CABINET DOOR HINGES BY HAFELE OR APPROVED EQUAL U.O.N. REFER TO DRAWINGS FOR FURTHER SPECIFICATIONS. 7. WHEN WALL CABINETS CONTAIN LIFT OPENING DOORS, ALL DOORS SHALL HAVE STRATO LIFT SYSTEM FOR UPPER CABINETS DOORS BY HAFELE OR APPROVED EQUAL. 8. ALL DRAWERS/ CABINETS DOORS SHALL HAVE SOFT -CLOSE HINGES/ HARDWARE 9. MILLWORK SUB SHALL PROVIDE DETAILED SHOP DRAWINGS W/ FINISHES & HARDWARE. FIRE DEPARMENT NOTES: DISABLED ACCESS NOTES: --- =- -_ _ -- 1. PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 2 -A 1. IN BUILDINGS AND FACILITIES, FLOORS OF A GIVEN STORY SHAL�BE A COMw10h - - WITHIN 75 FOOT TRAVEL DISTANCE TO ALL PORTIONS OF THE BUILDING ON EACH LEVEL THROUGHOUT, OR SHALL BE CONNECTED BY PEDESTRIAN RAMPS, PASSENGER o FLOOR, AND ADDITIONAL EXTINGUISHERS AS REQUIRED BY FIRE DEPARTMENT FIELD ELEVATORS OR SPECIAL ACCESS LIFTS. - - - w-- INSPECTOR OR BUILDING DEPARTMENT INSPECTOR. i-- r\ o fie LU - CV) 2. ALL FLOOR SURFACES SHALL BE SLIP - RESISTANT. 2. PROVIDE EXIT SIGN WITH 6" LETTERS OVER REQUIRED EXITS, WHERE SHOWN ON DRAWINGS, AND ADDITIONAL SIGNS AS REQUIRED BY BUILDING DEPARTMENT 3. EVERY CORRIDOR AND AISLE SERVING AN OCCUPANT LOAD OF 10 OR MORE INSPECTOR OR FIRE DEPARTMENT FIELD INSPECTOR. CONNECT EXIT SIGNS TO g SHALL BE NOT LESS THAN 44" IN WIDTH. -- ----; - -_ EMERGENCY POWER CIRCUITS. COMPLY WITH BUILDING CODES. - - - - - w U 4. ABRUPT CHANGES IN LEVEL ALONG ANY ACCESSIBLE ROUTE SKALL-NO_T EXCEED- 3. MAINTAIN AISLES AT LEAST 44" WIDE AT PUBLIC AREAS. 1/2" IN HEIGHT. LEVEL CHANGES NOT EXCEEDING 1/4" MAY BE VERTICAL. BEVEL OTHERS WITH A SLOPE NO GREATER THAN 1:2 4. EVERY EXIT DOOR SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY M \\ U = m 0 OR ANY SPECIAL KNOWLEDGE OR EFFORT. SPECIAL LOCKING DEVICES SHALL BE OF 5. LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN U AN APPROVED TYPE. ALL NEW DOORS SHALL HAVE APPROVED LEVER HANDLES. A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE - ,- Q. J HARDWARE, PANIC BARS, PUSH -PULL ACTIVATING BARS, OR OTHER HARDWARE M V 5. DOORS OPENING INTO REQUIRED 1 -HOUR, FIRE - RESISTIVE CORRIDORS SHALL BE v v DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE ; PROTECTED WITH A SMOKE OR DRAFT STOP ASSEMBLY HAVING A 20- MINUTE RATING OPENING HARDWARE. MOUNT DOOR OPENING HARDWARE 36" ABOVE FLOOR o 0 AND SHALL BE SELF - CLOSING. FINISH. 6. 20- MINUTE DOOR JAMBS TO BE TIGHT - FITTING, SMOKE AND DRAFT CONTROLLED. 6. CENTER HAND ACTIVATED DOOR OPENING HARDWARE 36" ABOVE THE FLOOR. 7. EXIT DOORS SHALL SWING IN THE DIRECTION OF TRAVEL WHEN SERVING 50 OR 7. MAXIMUM PULL OR PUSH EFFORT TO OPERATE DOORS SHALL NOT EXCEED 8.5 MORE PERSONS AND IN ANY HAZARDOUS AREA. POUNDS FOR EXTERIOR DOORS AND 5 POUNDS FOR INTERIOR DOORS, MEASURED 0 0 AT RIGHT ANGLES TO HINGED DOORS AND AT CENTER PLANE OF SLIDING OR 8. INTERIOR WALL AND CEILING FINISHES FOR EXIT CORRIDOR SHALL NOT EXCEED AN FOLDING DOORS. CORRESPONDING DEVICES OR AUTOMATIC DOOR OPERATORS END POINT FLAME SPREAD RATING: MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. MAXIMUM EFFORT TO OPERATE REQUIRED FIRE DOORS MAY BE INCREASED NOT TO EXCEED 15 POUNDS. • CLASS I, FLAME SPREAD 0 -25, SMOKE DENSITY 150, FOR MATERIALS INSTALLED IN VERTICAL EXITS. 8. THE BOTTOM 10" OF ALL DOORS (EXCEPT SLIDING AND AUTOMATIC) SHALL HAVE A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A • CLASS II, FLAME SPREAD 26 -75, SMOKE DENSITY 300, FOR MATERIALS INSTALLED WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. IN HORIZONTAL EXITS. PROVIDE A 10" HIGH SMOOTH PANEL ON THE PUSH SIDE OF NARROW FRAME DOORS. • CLASS III, FLAME SPREAD 76 -200, SMOKE DENSITY 450, FOR MATERIALS INSTALLED IN ANY OTHER LOCATION. 9. EVERY REQUIRED ENTRANCE OR PASSAGE DOORWAY SHALL BE NOT LESS THAN 3' IN WIDTH AND NOT LESS THAN 6-8" IN HEIGHT. DOORS SHALL BE CAPABLE OF 9. DECORATIONS (CURTAINS, DRAPES, SHADES, HANGINGS, ETC.) SHALL BE OPENING AT LEAST 90 DEGREES AND SHALL BE SO MOUNTED THAT THE CLEAR WIDTH NON - COMBUSTIBLE OR BE FLAMEPROOFED IN AN APPROVED MANNER. OF THE DOORWAY IS NOT LESS THAN 32 ". 10. PROVIDE FIRE DAMPERS OR DOORS WHERE AIR DUCTS PENETRATE FIRE -RATED 10. WHERE A PAIR OF DOORS IS UTILIZED, AT LEAST ONE OF THE DOORS SHALL PROVIDE WALLS OR CEILINGS. A CLEAR, UNOBSTRUCTED OPENING WIDTH OF 32" WITH THE LEAF POSITIONED AT AN w ANGLE OF 90 DEGREES FROM ITS CLOSED POSITION. 11. STORAGE, DISPENSING OR USE OF ANY FLAMMABLE OR COMBUSTIBLE LIQUIDS, FLAMMABLE GAS AND HAZARDOUS SUBSTANCES SHALL COMPLY WITH UNIFORM 11. IDENTIFY ACCESSIBLE ENTRANCES WITH AT LEAST ONE STANDARD SIGN AND WITH FIRE CODE REGULATIONS. ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, VISIBLE FROM APPROACHING PEDESTRIAN WAYS. 12. WOOD BLOCKING SHALL BE FIRE TREATED IN ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS. 12. THE FLOOR OR LANDING ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR SHALL BE LEVEL AND CLEAR. THE LEVEL AND CLEAR AREA SHALL HAVE A LENGTH IN 13. EXTEND OR MODIFY EXISTING FIRE/ LIFE SAFETY SYSTEM AS REQUIRED TO PROVIDE THE DIRECTION OF DOOR SWING OF AT LEAST 60" AND THE LENGTH OPPOSITE THE AN APPROVED FIRE/ LIFE SAFETY SYSTEM. SUBMIT PLANS TO FIRE DEPARTMENT WITH DIRECTION OF DOOR SWING OF 44" AS MEASURED AT RIGHT ANGLES TO THE PLANE COMPLETE DESCRIPTION OF SEQUENCE OF OPERATION, AND OBTAIN APPROVAL OF THE DOOR IN ITS CLOSED POSITION. PRIOR TO INSTALLATION. 13. FLOORS OR LANDINGS SHALL BE NOT MORE THAN 1/2" LOWER THAN THE 14. LOCATE THE CENTER OF FIRE ALARM INITIATING DEVICES 48" ABOVE THE LEVEL OF THRESHOLD OF THE DOORWAY. CHANGE IN LEVEL BETWEEN 1/4" AND 1/2" SHALL BE THE FLOOR, WORKING PLATFORM, GROUND SURFACE OR SIDEWALK. BEVELED WITH A SLOPE NO GREATER THAN 1:2. 15. EMERGENCY WARNING SYSTEMS SHALL ACTIVATE A MEANS OF WARNING THE 14. TO ALERT THE VISUALLY IMPAIRED, MARK THE UPPER APPROACH AND THE LOWER HEARING IMPAIRED. FLASHING VISUAL WARNING SHALL HAVE A FREQUENCY OF TREAD OF EACH INTERIOR STAIR WITH A STRIP OF CLEARLY CONTRASTING COLOR NOT MORE THAN 60 FLASHES PER NNUTE. AT LEAST 2" WIDE, PLACED PARALLEL TO AND NOT MORE THAN 1" FROM THE NOSE OF THE STEP OR LANDING. THE STRIP SHALL BE OF A MATERIAL THAT IS AT LEAST AS 16. EXTEND OR MODIFY EXISTING AUTOMATIC FIRE EXTINGUISHING SYSTEM AS REQUIRED SLIP RESISTANT AS THE OTHER TREADS OF THE STAIR. TO PROVIDE AN APPROVED AUTOMATIC FIRE EXTINGUISHING SYSTEM. SUBMIT PLANS TO FIRE DEPARTMENT AND OBTAIN APPROVAL PRIOR TO INSTALLATION. 15. CENTER ALL ELECTRICAL RECEPTACLE OUTLETS IN WALL LENGTH NOT LESS THAN 15" :. ABOVE THE FLOOR OR WORKING PLATFORM. 17. AUTOMATIC SPRINKLER SYSTEMS SHALL BE SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY OR REMOTE STATION SERVICE OR A LOCAL ALARM WHICH WILL GIVE 16. SANITARY FACILITIES LOCATED ON AN ACCESSIBLE FLOOR OF A BUILDING SHALL BE AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION. ACCESSIBLE TO THE PHYSICALLY HANDICAPPED. 17. ENTRY TO SANITARY FACILITIES: ADDITIONALNOTES: a. 44" CLEAR AISLES OR CORRIDORS WHERE OCCUPANT LOAD IS 10 OR MORE. b. DOORWAYS TO HAVE A 32" CLEAR OPENING. C. ON APPROACH SIDE, PROVIDE A 60" CLEAR LEVEL SPACE WHEN DOOR 1. AUTOCAD BASE PLANS OF BUILDING CONDITIONS ARE FORWARDED TO G. ALVAREZ SWINGS TOWARD APPROACH AND 44" SPACE WHEN DOOR SWINGS AWAY STUDIO BY OWNER OR OWNER'S ARCHITECT, G. ALVAREZ STUDIO MAKES NO CLAIM FROM APPROACH. AS TO THE ACCURACY OF THE BASE BUILDING CORE, PERIMETER AND TENANT DEMISING WALL CONDITIONS REPRESENTED. 18. TOILET ROOM ACCESSORIES: a. MOUNT BOTTOM EDGE OF MIRRORS NO HIGHER THAN 40" FROM THE 2. GC TO VERIFY BASE BUILDING AS BUILT CONDITIONS PRIOR TO PRECEDING WITH FLOOR. WORK AND IMMEDIATELY NOTIFY G. ALVAREZ STUDIO OF ANY CONDITIONS b. MOUNT TOILET TISSUE DISPENSERS WITHIN 12" FROM THE FRONT EDGE OF THE CONTRARY TO THOSE SHOWN OR INFERRED ON THE DRAWINGS. TOILET SEAT. C. MOUNT DISPENSING AND DISPOSAL FIXTURES (TOWEL, SANITARY NAPKINS, 3. WORK TO BE PERFORMED IN ACCORDANCE WITH THE RULES AND REGULATIONS OF WASTE, COIN SLOTS, ETC.) WITH OPERATING PARTS NO HIGHER THAN 40" GOVERNMENTAL AGENCIES HAVING JURISDICTION AND SHALL CONFORM TO ALL FROM THE FLOOR. CITY, COUNTY, STATE AND FEDERAL CONSTRUCTION, SAFETY AND SANITARY LAWS, CODES, STATUES AND ORDINANCES. 19. SINGLE ACCOMMODATION TOILET FACILITY: a. WATER CLOSET TO HAVE A 28" CLEARANCE FROM A FIXTURE AND 32" FROM 4. ALL LUMBER, WOOD GROUNDS, NAILERS AND BLOCKING CONCEALED IN WALLS OR A WALL. LOCATED IN CEILING PLENUMS SHALL BE FIRE - RETARDANT TREATED. b. MINIMUM CLEAR SPACE IN FRONT OF WATER CLOSET TO BE 48 ". C. A SPACE 36' X 48" IS PERMITTED IN FRONT OF EXISTING WATER CLOSET 5. PROVIDE IN -WALL FIRE RETARDANT BLOCKING AT WALL HUNG MILLWORK, WALL ACCESSIBLE TO THE HANDICAPPED. ; MOUNTED FURNISHINGS, WALL MOUNTED SHELVING, WALL MOUNTED LIGHT FIXTURES, AND MARKER BOARDS AS REQUIRED FOR RIGID SUPPORT. 20. THE HEIGHT OF THE WATER CLOSET (TOP OF SEAT) SHALL BE BETWEEN 17" AND 19 ". 6. TYPICAL DOOR ROUGH OPENING ON HINGE SIDE IS TO BE 4" FROM FACE OF 21. MOUNT FLUSH VALVE CONTROL NO MORE THAN 44" ABOVE THE FLOOR, ON THE PERPENDICULAR PARTITION. IF ANY CONFLICTS WITH DEVICES, CLOSER'S SIDE OF THE TOILET WITH THE GREATEST SEPARATION FROM ADJACENT WALL OR CLEARANCES, AMONG OTHER POSSIBLE PROBLEMS, REPORT TO G. ALVAREZ STUDIO. OTHER SURFACE. 7. G.C. TO REFER TO ALL ARCHITECTURAL AND MEP DRAWINGS AS WELL AS ELEVATIONS, 22• PROVIDE GRAB BARS ON EACH SIDE, OR ONE SIDE AND BACK OF WATER CLOSET. DETAILS, ETC. DURING LAYOUT /CHALKING PHASE AND REPORT ANY AND ALL a. GRAB BARS TO BE 33" ABOVE AND PARALLEL TO THE FLOOR. DISCREPANCIES IN SITE CONDITIONS TO G. ALVAREZ STUDIO. b. SIDE BARS TO BE 42" LONG AND PROJECT 24" IN FRONT OF WATER CLOSET STOOL. GRAB BAR AT BACK TO BE 36" LONG. m 8. GC TO INSPECT EXISTING CONCRETE SLAB FOR UNEVEN SURFACES. HIGH AND LOW C. DIAMETER OF GRAB BARS TO BE 1 -1 /4" TO 1 -1/2 ". p o' SPOTS DETERMINED PRIOR TO STONE/ TILE INSTALLATION. STONE/ TILE INSTALLATION d. PROVIDE 1-1/2" CLEARANCE BETWEEN GRAB BARS AND WALL. SHALL BE DONE IN A FLAT CONDITION NOT NECESSARILY LEVEL. RAMPING e. GRAB BARS (INCLUDING CONNECTORS, FASTENERS, SUPPORT BACKING, TOLERANCES OF 1/8" PER 10 FEET RUN SHALL BE MAINTAINED. CONTRACTOR TO ETC.) SHALL SUPPORT A 250 POUND LOAD. <u PROVIDE CONTINGENCY FOR FLOATING OF FLOORS TO ACHIEVE FLUSH TRANSITIONS f• GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS. z BETWEEN FINISHES. g. GRAB BARS AND ANY ADJACENT SURFACE SHALL BE FREE OF SHARP OR E.., z C ABRASIVE ELEMENTS. U < 9. IF ACCESS PANELS ARE REQ. IN DRYWALL CLG., GC SHALL USE STEALTH ACCESS h. EDGES SHALL HAVE A MINIMUM RADIUS OF 1/8 ". PANELS (WHITE) BY INTEXFORM OR APPROVED EQUAL. O o 2 23. PROVIDE A CLEAR FLOOR SPACE 30" X 48" IN FRONT OF LAVATORY TO PERMIT A 10. BUILDING CORRIDORS AND BASE BUILDING PERIMETER WALLS/ PARTITIONS /INSULATED FORWARD APPROACH. a o PARTITIONS NOT UNDER THIS CONTRACT /PERMIT. O < 24. MOUNT LAVATORIES WITH A MINIMUM CLEARANCE OF 29" FROM THE FLOOR TO THE 11. G.C. SHALL USE GREENBOARD OR DUROCK AT ALL WET LOCATIONS SUCH AS BREAK/ BOTTOM OF THE APRON. PROVIDE KNEE CLEARANCE UNDER THE FRONT LIP LOUNGE ROOMS, JANITOR'S CLOSET AND BATHROOMS. EXTENDING A MINIMUM OF 30" IN WIDTH WITH 8" MINIMUM WIDTH, AND SHALL BE A F" Z MINIMUM OF 9" HIGH FROM THE FLOOR A MINIMUM OF 17" DEEP FROM THE FRONT 12. ALL DIMENSIONS IN CONSTRUCTION PLAN ARE TO FINISH FACE OF PARTITION, GC. TO OF THE LAVATORY. BACK OUT ALL THICKNESS OF FINISHES IN LAYING OUT AND FRAMING. 25. FAUCET CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE 13. FLOOR RAMPING: GC SHALL ENSURE THE MOST INCONSPICUOUS MANNER BY HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE SLOPING FROM THE HIGHEST TO THE LOWEST POINT IN ALL DIRECTIONS WITH LATICRETE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN OR OTHER APPROVED METHOD AT A RATE OF 1/8" IN 10' MAX. SLOPE. CONTRACTOR 5 POUNDS. LEVER OPERATED, PUSH TYPE AND ELECTRONICALLY CONTROLLED SHALL NOTIFY G. ALVAREZ STUDIO OF THE INTENDED METHOD BEFORE PROCEEDING MECHANISMS ARE EXAMPLES OF ACCEPTABLE DESIGNS. SELF CLOSING ARE WITH THE WORK. ALLOWED IF THE FAUCET REMAINS OPEN FOR AT LEAST 10 SECONDS. 14. THESE GENERAL NOTES HAVE THE SAME AUTHORITY AS OTHER NOTES AND REFERENCES 26. INSULATE OR OTHERWISE COVER HOT WATER AND DRAIN PIPES UNDER LAVATORIES. " IN THE DRAWINGS OR SPECIFICATIONS AND SHALL NOT BE EXCLUDED IN THE EXECUTION OF THE WORK. THEY MAY REQUIRE COORDINATION BETWEEN VARIOUS 27. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIES. TRADE CONTRACTORS. IN ADDITION TO THESE GENERAL NOTES, REFER TO DEMOLITION AND CONSTRUCTION NOTES SPECIFIC TO EACH DRAWING. WIRE REMOVAL SPECIAL NOTES: (BOAT) .: REMOVE OLD CABLE. AS PER 2008 REVISIONS TO THE NATIONAL 1. BOAT SHALL BE FURNISHED BY TENANT. 2. CONTRACTOR SHALL ITEMIZE BOAT PICK -UP, INSTALLATION, REFURBISHMENT & ADAPTABILITY TO MEETING ROOM. G.C. SHALL INCLUDE BUDGET FOR BOAT TRANSPORTATION TO JOB SITE. 3. G.C. SHALL COORDINATE W/ LL REGARDING INSERTING BOAT INSIDE OF SPACE. G.C. SHALL ITEMIZE ALL COST REGARDING BOAT CONVERSION/ REHABILITATION. NOTE: CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR ALL MILLWORK ITEMS IN THIS JOB, AND SHALL BE APPROVED BY G. ALVAREZ STUDIO, INC. ELECTRICAL CODE, REMOVE CABLE THAT IS NOT BEING USED OR WILL NOT BE USABLE IN THE FUTURE. REMOVE ALL CABLES ALL THE WAY TO THE ELECTRICAL PANEL. FOLLOW SAFETY PRECAUTIONS WHEN REMOVING OLD CABLE. ENSURE THAT WORKERS WEAR PROPER RESPIRATORY PROTECTION, AND SEAL REMOVED CABLE IN PLASTIC BAGS. w w � � U O z 0 D Lu Ee o N ° m N U Z F_ Z W :2 Z N_ W W F_ Z W I..L W T� V) 0 0 13 C 00 U N � N N ' � M u- N v z N M � > J Q� C a ONE N_ wo � � N O Cr W L Cz Q) o CHRISTIAN A. VIDAL, AIA LICENSE NO. AR96861 a ARCHITECT r CONSULTANT scale: as shown release date: April I8, 2014 drawn by: cc cheked by: cv SHEET NO. A -1.0 Z 00 CD N C7 0 00� CN o 00^ w-- 0 O i-- r\ o fie LU - CV) I.- z H�,0 oN z ju_ Q g Q Q CL w U _j -' o wo LLJ o! M M \\ U = m 0 o U N m U - ,- Q. J N M V h O N v v ° o 0 N N m 0 0 w w � � U O z 0 D Lu Ee o N ° m N U Z F_ Z W :2 Z N_ W W F_ Z W I..L W T� V) 0 0 13 C 00 U N � N N ' � M u- N v z N M � > J Q� C a ONE N_ wo � � N O Cr W L Cz Q) o CHRISTIAN A. VIDAL, AIA LICENSE NO. AR96861 a ARCHITECT r CONSULTANT scale: as shown release date: April I8, 2014 drawn by: cc cheked by: cv SHEET NO. A -1.0