Loading...
14-1132-002Sequence of Operations for Access Controlled Doors 'Acces's controlled Door with Electro—Magnetic Locks IN ACCORDANCE WITH NFPA 101-2006-7.2.1.6.2 (1-8) 1 Door . is in the secure position when closed, the door status contact is lined up and the locking mechanism has engaged. 2." To enter the door . the person must present- a valid. card at the card reader, after verification the system will grant access thru the door by releasing the lock for a set period of time. -4 — When someone approaches the door frnrn the onc"rn citAn to ov;+ the mran the Request To Exit (REX) motion detector shall detect. the presence of a person and release the. lock for a set period of time, allowing free egress. 4. Jn, the event of a system failure, the person can exit, the area by pressing the EXIT button located within 5 feet of the door, allowing free egress for a minimum of 30 seconds. DOOR 11 DOOR 12 DOOR 13 DOOR 14 DOOR 15 DOOR 16 5.—In. the event of a Fire Alarm detected by the Fire Alarm System, the system will release the lock, allowing free egress. RISER DIAGRAM THE ACCESS CONTROL SYSTEM PROVIDED ON THIS PROJECT COMPLIES WITH THE FOLLOWING CODE: WI R E LEGE N D TYPICAL. USE TYPE ACCESS CONROL DOOR READER 22 6 STRANDED SHILD. LOCK POWER 18 AWG 2 COND (RED/BLACK) POSITION SWITCH 22 AWG 2 COND (GREEN /WHITE) REQUEST TO EXIT 18 AWG 2 COND (GREEN/WHITE) SENSOR POWER 18 AWG 2 COND (RED/BLACK &.GREEN/WHrrE) 3D g DAME: -Reiision By 14 00 en 4-6 g 00 Z W 04 in 0 NE/5 .0 Z Z Oa MP o SEAL A4 ;,1.67574 it 4- N A\- sV SIGNATURE I U_ E D C/) 4- 0 7" C Z) W ) V Lo Lo 7. 1- 0 < C: 0 LLJ U 11-- C/) '7 1 LU Lij U CX CL CL U_j Nu .� Z.- C/) CL 0 "r U.j Consultant Drawn: D.G. Checked: D.G.-,, -Dote:''. 4 Scale: As—'shown Job No. Sheet NFPA 101 Life Safety Code 2006 Edition SECURITY.- LEGEND. 7.2.1.5 Locks, 'Latches, and Alarm -Devices. -2-15.1� - Doors - sholl, - be - arranged - to - be opened reachly fro the egress side.' 7. . . rn -whenever SYMBOL PART. MANUFACTURER DESCRIPTION the building is occupied. 7.2.1.5.2 Locks, if provided, shall not require the use of 'a key, a tool, or special knowledge or effort for operation from the egress side. CONNECT TO EXISTING ACCESS CONTROL PANEL CONNECT 120V - DEDICATED RECEPTACLE XS REX MOTION SENSOR SENSOR) 7.2.1.6.2*. Access—Controlled Egress Doors. Where permitted in Chapters 11 through 42, ,,equipped (EXIT doors, in the means of egress shall be permitted to be with an approved FC RI entrance and egress access control system, provided that all the following criteria are CARD READER met: FEB] (1) A sensor shall be' provided on the egress side, arranged to detect an occupant EMERGENCY EXIT BUTrON approaching doors that are arranged to unlock in the direction of egress upon' detection NO of an approaching occupant or loss of power to the sensor. 'system MAMOCK (2) Loss of power to the part of the access control that locks the doors shall automatically unlock the doors in the direction� of egress. (3) The doors shall, be arranged to unlock. in the direction of egress from a manual, release device located 40 in. to 48 -in. (1015 mm to 1220 mm) vertically above the floor and within 60 in. (1525 mm') of the secured doors. (4) The. manual 'release device specified in 7.2.1.6.2(3) shall be readily accessible and 'sign clearly identified by a that reads as follows: PUSH TO EXIT, (5) When operated, the manual release device shall result in direct interruption of p6we ' r to the lock independent of the access control system electronics and the doors shall remain unlocked for not less than 30 seconds. (6) Activation of the building fire—protectiv'e' signaling system, if provided, shall automatically unlock the doors in the direction of 'egress, and the doors.shall remain unlocked until the fire—protective signaling system- has been manually reset. (7) The activation of manual fire' a alarm..boxes that activate the building fire protective signaling system specified in 7.2.1.6.2(6) shall not be,-'required to unlock the doors. 0 'detection system, if provided, p (8) Activation of the building automatic sprinkler rinkler or fire m p shall' automatically .-unlock. the doors in, the direction of egress, and the doors shall remain unlocked until :the fire—protective signaling system has been manually reset. 3D g DAME: -Reiision By 14 00 en 4-6 g 00 Z W 04 in 0 NE/5 .0 Z Z Oa MP o SEAL A4 ;,1.67574 it 4- N A\- sV SIGNATURE I U_ E D C/) 4- 0 7" C Z) W ) V Lo Lo 7. 1- 0 < C: 0 LLJ U 11-- C/) '7 1 LU Lij U CX CL CL U_j Nu .� Z.- C/) CL 0 "r U.j Consultant Drawn: D.G. Checked: D.G.-,, -Dote:''. 4 Scale: As—'shown Job No. Sheet