12-900-013I PLUMBING SPECIFICATIONS: 1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH FLORIDA PLUMBING CODE 2010 AND ALL CODES ADOPTED BY IT. 2. PRIOR TO ORDERING, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL MATERIALS AND EQUIPMENT TO ENGINEER OF RECORD FOR APPROVAL 3. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING WORK IS FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP, AND FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE, REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE AT NO EXPENSE TO THE OWNER 4. MATERIALS SHALL BE AS FOLLOWS: A. DOMESTIC WATER PIPING - TYPE Y COPPER WITH LEAD FREE SOLDER B. SANITARY WASTE & VENT PIPING -SCH 40 NO -HUB CAST IRON C. CONDENSATE DRAINAGE PIPING - NOT USED D. VALVES - BRONZE NOBCO OR EQUAL AND RATED AT 125 PSI 5. ALL PLUMBING FIXTURES SHALL BE WATER SAVER PER CODE. FPC TABLE 604.4. TYPE, COLOR AND TRIM TO BE SELECTED BY OWNER. 6. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS BY PPP, INC. OR EQUAL. 7. COMPLETE SYSTEM: FIXTURES AND EQUIPMENT SHALL BE GIVEN AN IN- SERVICE TEST AFTER COMPLETION OF INSTALLATION. 8. REMOVE UNUSED PIPES BACK TO MAIN. 9. ASSE 1010 CERTIFIED WATER HAMMER ARRESTORS SHALL BE ONLY APPROVED MEANS OF CONTROLLING WATER HAMMER. MAY EXTEND AS A WASTE OR VENT WALL PLUGGED TEE WALLCOVER WITH CLEANOUT AND SCREW FLOOR LINE BALANCE OF PIPING SAME UL LISTED FIRE STOP AS CLEANOUT TO GRADE WALL CLEANOUT WALL CLEANOUT NOT TO FIXTURE SCHEDULE MARK DESCRIPTION COLD HOT DRAIN LAV ADA APPROVED, 20x18 ", WALL HUNG, VITREOUS CHINA, 1/2" 1/2" 1 1/4" Location: • ASTM E814 (L'L1479) Standard Test Method accurate. The user of this information must LAVATORY W/ CONCEALED ARM SUPPORTS. 0.5 GPM, ADA �— for Through Penetration Firestopping. determine the suitability of the design to the Q-- PIPE TURNS UP APPROVED, LEVER TYPE FAUCET WITH PERFORATED .° c-:+ - - -••, • •.•••. codes. Tremco shall not be liable for dam - Installer: '•d STRAINER AND NO POP UP ASSEMBLY. PROVIDE TRUE BRO Date: 11 /O1 /00 Drawing: TR -1064 ages, direct or consequential, resulting from LETTER DENOTES SIZE. aA PROTECTIVE SHIELD FOR EXPOSED DRAINAGE AND HOT METER Approved by: J. Pitcole found to be defective. FLOOR CLEAN OUT - WATER PIPING. - -- -- - -- HOT WATER PIPING WC ADA COMPLIANT, FLOOR MOUNTED, FLUSH TANK TYPE, 1/2 —o 3" —a VITREOUS CHINA, ELONGATED BOWL, SIPHON JET ACTION, - - -- P &T - - -- P &T RELIEF PIPE 1.28 GPF ADA APPROVED WATER CLOSET. MOUNTED WITH RIM AT 17" A.F.F. OPEN FRONT SEAT WITHOUT COVER. WCO WALL CLEANOUT. PROVIDE ROUND CHROME ACCESS PLATE IN FINISHED AREAS. SINK SINGLE COMPARTMENT SINK AND 1.5 GPM FAUCET PER 1/2" 1/2" 1 1/2 OWNERS CRITERIA. WM 3.5" WASHING MACHINE OUTLET BOX BY SIOUX CHIEF 1/2" 1/2" 2" MODEL # 696- 2313MF (WITH MINI - RESTER W.H.A.) TM-1 TANKLESS TYPE WATER HEATER 1/2" 1/2" CHRONOMITE MODEL #M40 /277 1108OW 277V 40A 757 TEMP RISE AT 1.0 GPM TWH -2 TANKLESS TYPE WATER HEATER 1/2" 1/2" CHRONOMITE MODEL #M15L /277 415OW 277V 15A 577 TEMP RISE AT 0.5 GPM CONC. SLAB -CONC. INSERT X3/8" ALL THREAD ROD PIPE -\OX --PIPE RING HANGER PIPE HANGER NOT TO SCALE EX.3 /4" 3 and 4 Hour Fire Rated Through Penetration Firestop for Single Metal Pipe through Concrete Floors and Walls using FYRE -SIL and FYRE -SIL S/L. F- Rating = 3 & 4 Hr. T- Rating = 0 Hr. 4F f- ,uf,�7vr /fir G 3735 Green Rd. Beachwood, OH, 44122 QDrawing not to scale C .d ° ° A" a" (D Pre -Rated Concrete Floors or Block Walls: See Table below for min. thickness. (2 ) Metallic Pipe: A) Steel Pipe - 8" diam. (or smaller) Sch. 10 (or heavier) steel pipe. B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or 6" diam.(or smaller) steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. ( Packing Material - See Table below for the mineral wool insulation requirements. ® FYRE -SIL or FYRE -SIL S/L (Floors Only) - Min. 1/2" thickness of sealant applied within annulus flush with top of floor surface or with both sides of wall assembly. Min. Thickness Annular Space Min. Packing Material Min. Packing Material F- Rating of Concrete, in. Range, in. Thickness, in. Density, pcf Hr. 4 -1/2 1/2 to 3 -3/8 3 -1/2 6.0 3 5 -1/2 0 to 1 -7/8 5 4.0 4 d UL /cUL System No. CAJ 1064 9 DESCRIPTION Project: The Tremco products used above have been This information is intended for engineering A - tested in accordance with the following: purposes only and is based on internal and third party testing which we believe to be P &T RELIEF VALVE Location: • ASTM E814 (L'L1479) Standard Test Method accurate. The user of this information must GATE VALVE IN RISER �— for Through Penetration Firestopping. determine the suitability of the design to the Q-- PIPE TURNS UP application and the product to local building .° c-:+ - - -••, • •.•••. codes. Tremco shall not be liable for dam - Installer: '•d WATER HAMMER ARRESTOR Date: 11 /O1 /00 Drawing: TR -1064 ages, direct or consequential, resulting from LETTER DENOTES SIZE. aA FWATER METER Approved by: J. Pitcole found to be defective. FLOOR CLEAN OUT - f- ,uf,�7vr /fir G 3735 Green Rd. Beachwood, OH, 44122 QDrawing not to scale C .d ° ° A" a" (D Pre -Rated Concrete Floors or Block Walls: See Table below for min. thickness. (2 ) Metallic Pipe: A) Steel Pipe - 8" diam. (or smaller) Sch. 10 (or heavier) steel pipe. B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or 6" diam.(or smaller) steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. ( Packing Material - See Table below for the mineral wool insulation requirements. ® FYRE -SIL or FYRE -SIL S/L (Floors Only) - Min. 1/2" thickness of sealant applied within annulus flush with top of floor surface or with both sides of wall assembly. Min. Thickness Annular Space Min. Packing Material Min. Packing Material F- Rating of Concrete, in. Range, in. Thickness, in. Density, pcf Hr. 4 -1/2 1/2 to 3 -3/8 3 -1/2 6.0 3 5 -1/2 0 to 1 -7/8 5 4.0 4 SYMBOL LEGEND T UL /cUL System No. CAJ 1064 SYMBOL DESCRIPTION Project: The Tremco products used above have been This information is intended for engineering GATE VALVE - tested in accordance with the following: purposes only and is based on internal and third party testing which we believe to be P &T RELIEF VALVE Location: • ASTM E814 (L'L1479) Standard Test Method accurate. The user of this information must GATE VALVE IN RISER �— for Through Penetration Firestopping. determine the suitability of the design to the Q-- PIPE TURNS UP application and the product to local building UNION c-:+ - - -••, • •.•••. codes. Tremco shall not be liable for dam - Installer: A� WATER HAMMER ARRESTOR Date: 11 /O1 /00 Drawing: TR -1064 ages, direct or consequential, resulting from LETTER DENOTES SIZE. use of this material or design. Tremco shall Signature: only be respons ible fo r replacing material FWATER METER Approved by: J. Pitcole found to be defective. SYMBOL LEGEND T 7z 7�,/. SYMBOL DESCRIPTION D4 GATE VALVE BALL VALVE P &T RELIEF VALVE C>i - GATE VALVE IN RISER �— PIPE TURNS DOWN Q-- PIPE TURNS UP -+- UNION c-:+ HOSE BIBB A� WATER HAMMER ARRESTOR LETTER DENOTES SIZE. WALL CLEAN OUT FWATER METER ® FLOOR CLEAN OUT - - - COLD WATER PIPING - -- -- - -- HOT WATER PIPING SANITARY WASTE PIPING - - — — — — - VENT PIPING —o —o —� CONDENSATE DRAIN PIPE —a PAN —o PAN DRAIN PIPE - - -- P &T - - -- P &T RELIEF PIPE 3/4" 1 I 1/2" �� �// \` LAY 1 /2w 1/2" '/�'/ \�\ 1/2 "1 /4 IA" / X /2w / 3 /. 3 4 " , ;/ Slb� 1/2 "` II�L2 1/2" t 1/2 w 1/2n I Sl�K t 1/2" I I t TWH -1 1/290 EX.3" VENT r I DOMESTIC WATER ISOMETRICS NOT TO SCALE 2" 2" / 12w � ` / � w LAY _ -.0 2 3/4" CW TO CONNECT TO EXISITNG. CONNECT TO — EXISTING 6" SANITARY AND 3" VENT RISERS. SANITARY ISOMETRICS NOT 70 SCALE PLUMBING PLAN SINK 1 -1/2" DEMOLITION NOTES: 1. REMOVE EXISTING FIXTURES AND FLOOR SINKS. 2. PATCH FLOOR OPENINGS. 3. REMOVE UNUSED PIPES BACK TO MAIN. SCALE: 1/4" = 1$ -0" WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. 0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWIT OMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDIN ODES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS A JSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT TH XPRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. 1, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. �•�`��,,1SCH % �GENSF ••. 5ggg2 '•,* conSULTInG EnGln[�RS Na 240 Commercial Blvd 2A _ * Lauderdale By The Sea, FL 33308 •,' F T 954.523.4933 AUG 2 g 0 �•� Z F 954.523.5052 www.henz.com S 10 IA 'Ito % PROJECT No.: 12059.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. A OM-CW - Mai DM -RAW 126 S. FEDERAL HIGHWAY SUITE f 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX- (954) 922 -7388 EMAIL*#o*roeenateina d*ect com WEB WWWJo8eI18tek18rcHtect.com STATE REG. NO. AR0016674 NATL. REG. NO. 69178 COPYMC*ff ©20M NOIQDERTO ROGET16TEIN ARCHITECT, Ddb. ALL RIGHTS RESERVED. 1146 DOCUMENT OR PARTS I I-E OP, MAY NOT BE REPRODUCED IN ANY FORM UTHOUT PERMi862ON. DESIGNED DAS DRAWN DAS CHpAS I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2012 -37 2/14/2011 5701 SUNSET DR SUITE F06 ISIS WELLNESS NAILBAR SOUTH MIAMI FLORIDA, 33143 PLUMBING PLAN P -1 °� 1 I i i I i I 1i i 1. I I� j�. I' i I i i T 7z 7�,/. DEMOLITION NOTES: 1. REMOVE EXISTING FIXTURES AND FLOOR SINKS. 2. PATCH FLOOR OPENINGS. 3. REMOVE UNUSED PIPES BACK TO MAIN. SCALE: 1/4" = 1$ -0" WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. 0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWIT OMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDIN ODES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS A JSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT TH XPRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. 1, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. �•�`��,,1SCH % �GENSF ••. 5ggg2 '•,* conSULTInG EnGln[�RS Na 240 Commercial Blvd 2A _ * Lauderdale By The Sea, FL 33308 •,' F T 954.523.4933 AUG 2 g 0 �•� Z F 954.523.5052 www.henz.com S 10 IA 'Ito % PROJECT No.: 12059.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. A OM-CW - Mai DM -RAW 126 S. FEDERAL HIGHWAY SUITE f 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX- (954) 922 -7388 EMAIL*#o*roeenateina d*ect com WEB WWWJo8eI18tek18rcHtect.com STATE REG. NO. AR0016674 NATL. REG. NO. 69178 COPYMC*ff ©20M NOIQDERTO ROGET16TEIN ARCHITECT, Ddb. ALL RIGHTS RESERVED. 1146 DOCUMENT OR PARTS I I-E OP, MAY NOT BE REPRODUCED IN ANY FORM UTHOUT PERMi862ON. DESIGNED DAS DRAWN DAS CHpAS I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2012 -37 2/14/2011 5701 SUNSET DR SUITE F06 ISIS WELLNESS NAILBAR SOUTH MIAMI FLORIDA, 33143 PLUMBING PLAN P -1 °� 1 I i i I i I 1i i 1. I I� j�. I' i I i i