12-900-012ELECTRICAL SPECIFICATIONS 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE NEC 2008, FBC 2010, FFPC 2010, NFPA 72 2002, LOCAL CODES, ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C.. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. 2. TO THE BEST OF OUR KNOWLEDGE AND ABILITY THESE DRAWINGS REPRESENT AN ACCURATE PRESENTATION OF EXISTING CONDITIONS BASED UPON CAREFUL EVALUATION OF OBSERVED CONDITIONS Y TO THE EXTENT REASONABLY POSSIBLE. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND IMMEDIATELY NOTIFY ENGINEER WITH ANY DISCREPANCY. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REWIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE. WILL NOT BE ALLOWED. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. 6. CORREC11ON OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS. 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS J10 AND SMALLER MAY BE SOLID. ALL THOSE #8 AND LARGER TO BE STRANDED. 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4", GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC PAINT. COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. 12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE 13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. 14. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT. CARTRIDGE TYPE. FUSES SHALL BE THOSE MANUFACTURED BY EITHER BUSSMAN OR UTTIEFUSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L 15. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER. CATALOG NUMBERS LISTED ARE LUTON: HOWEVER, COMPARABLE DEVICES BY PASS dl: SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND PLATES SHALL BE WHITE UNLESS DICTATED OTHERWISE BY ARCHITECT /OWNER. 16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN PROPER WORKING ORDER. 17. A SEPARATE. GREEN TYPE THM COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. 18. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. 19. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. 20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM C.U.TO A.H.U. ,TERMINATION SHALL BE PERFORMED BY MECHANICAL CONTRACTOR. 21. ALL FLUORESCENT LIGHT FIXTURES SHALL HAVE IN LINE FUSING AND ENERGY SAVING BALLASTS. (ONLY REQUIRED IN MIAMI DADE COUNTY) 22. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE 'D HOWEVER, COMPARABLE EQUIPMENT BY G.E. do SIEMENS ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 23. PROVIDE IDENTIFICATION FOR ALL PANELS, CABINETS, ENCLOSURES, DISCONNECTS do TRANSFORMERS USING ENGRAVED NAMEPLATES, WHITE LETTERING ON A BLACK BACKGROUND. NAMEPLATES SHALL IDENTIFY PANEL DESIGNATION (NAME,) VOLTAGE. PHASE do WIRE CONFIGURATION. PROVIDE TYPEWRITTEN DIRECTORIES UNDER PLASTIC COVER FOR ALL PANEL BRANCH CIRCUITS, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CKT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED. 24. ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME. VOLTAGE AND AMPERAGE. 25. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST - RESISTANT BITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. 26. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME. THE CONTRACTOR SHALL COORDINATE ALL RELATED WORK WITH THE UTILITY COMPANYS RESPONSIBILITIES TO MEET THE OWNER'S SCHED. 27. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM' AND ELECTRICAL NON - METALLIC TUBING USED FOR BRANCH CIRCUITING. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). "MC- TYPE CABLE SHALL NOT BE USED AS HOME RUNS. THE CONTRACTOR SHALL STRICTLY CONFORM M THE N.E.C. REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL, 28. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 208V SYSTEM 240V (HIGH LEG) SYSTEM 480V SYSTEM PHASE SEQUENCE NEUTRAL - WHITE NEUTRAL - WHITE NEUTRAL - WHITE /STRIPE ABC, TOP TO BOTTOM ' PHASE A - BLACK PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT. PHASE B - RED PHASE B - ORANGE PHASE B - PURPLE FRONT TO BACK PHASE C - BLUE PHASE C - BLUE PHASE C - YELLOW GRD.CON - GREEN GRD.CON - GREEN GRD.CON - GREEN 29. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY. 30. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE EM TO INDICATE FIELD CHANGES. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER. 31. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBIUTY TO BRING THIS TO THE ATTENTION OF THE ELECTRICAL ENGINEER IMMEDIATELY. IF ELECTRICAL CONTRACTOR PROCEEDS WITH ARX CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER, . CONTRACTOR WILL NOT BE COMPENSATED. RISER DIAGRAM LEGEND SYMBOL DESCRIPTION LOADCENTERS - QO L.1A PANELBOARD - NQOD 277/480 PANELBOARD - NF ' PNLS SHALL BE MTD 0 +60" A.F.F, U.N.D ® METER MLO 5' -0" TO 6' -0" A.F.G. FEED THRU BUS ID1A 3R FUSED DISCONNECT 5' -0" TO 6' -0" A.F.G. aRMT MAIN CIRCUIT BREAKER 8 DISCONNECT 5' -0" TO 6' -0" A.F.G. GROUND SYSTEM TRANSIENT VOLTAGE SURGE SUPPRESSOR TVSS INTERMATIC SEE PNL SCHEDULE FOR MDL. Q LIGHTING CONTACTOR (MECHANICAL LATCH) O TIME- SWITCH BY INTERMATIC MDL#ET70815CR. EXISTING TO REMAIN I BOLD LINES DENOTE NEW WORK OR EQUIPMENT %UG"Im MMSFMMM NW t TYPICAL 208Y/120 � DRY TYPE TRANSF. PAIL SCIIEDIA88 NOTES 1. BOLD DENOTES AREA OF WORK FOR REFERENCE ONLY. 2. UPON DEMOLITION, CONTRACTOR SHAD_ IDENTIFY AND REUSE CIRCUITS THAT BECOME AVAILABLE, AND PROVIDE ENGINEER WITH COMPLETE AS BUILTS, REFER TO NOTE #31 OF THE ELECTRICAL SPECIFICATIONS. 3. IF AVAILABLE CIRCUITS FOR THIS SUITE ARE INSUFFICIENT, CONTACT ENGINEER IMMEDIATELY. 4. CONTRACTOR SHALL CLEARLY MARK IN PANEL SCHEDULE ALL CIRCUITS. 5. CONTRACTOR SHALL REMOVE ALL WIRING NOT USED AND NOT IN A RACEWAY GOING INTO CUENT SPACE. 6. CONTRACTOR SHALL MARK AS SPARE DEMO CIRCUIT NOT BEEN USED AND LEAVE THEM IN OFF POSITION. PANEL SCHEDULE L Rated Voltage: 120/208V 31PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 200A SPACES: 42 Location: SEE POWER PLAN Type: NEMA 1 Main: 150AMCB Project No: 12059.00 A.I.C: EXSITNG KVA KVA PANEL SCHEDULE H O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LGT /HEAT MOTOR PH RCPT Rated Voltage: 277/480V MAX. DIST.(ft) 31PHAW AWG Manufacture: EXISTING Mounting: SURFACE 1 COMBO WASHER/DRYER Rated Amps: (Cu bus) 225A 87 SPACES: 28 Location: SEE FLOOR PLAN Type: NEMA 1 1.20 Main: 150AMCB 12 2011 SIGN Project No: 12059.00 3 A.I.C: EXISTING 2.50 B 1.70 127 KVA KVA 2511 AHU -1 4 5 TT13 CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LGT /HEAT MOTOR PH RCPT LGT /HEAT MOTOR MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 7 1 SPARE 2013 132 3% 1.00 A A 1.30 101 3% 12 1 20/1 20/3 CU-1 2 3 20/1 12 132 B 1.00 4 5 0.20 658 C 12 20/1 LIGHTS 6 7 IWH 4011 12 110 3% 1.00 11.00 A 1.30 101 3% 12 20/1 LIGHTS (note 7) 8 9 IWH 1511 12 293 3% 1.00 4.15 B 0.20 658 3% 12 20/1 LIGHTS (note 7) 10 11 SPACE 20/1 12 132 3% 1.00 C 1.00 132 3% 12 20/1 DED RECEPT 12 13 SPACE 20/1 12 132 3% 1.00 A 1.00 132 3% 12 20/1 ROOM RECEPT 14 151 SPACE 20/1 12 132 3% 1.00 B 1.50 88 3% 12 20/1 TOWEL WARMER 16 17 SPACE 2011 12 132 3% 1.00 C 1.50 88 3% 1 12 20/1 TOWEL WARMER 18 19 SPACE 20/1 12 132 3% 1.00 A 1.50 88 3% 12 20/1 WARMER 20 21 SPACE 20/1 12 132 3% 1.00 B 20/1 SPARE 22 23 RECEPT 20/1 12 366 3% 6.20 5.50 2.50 C 2011 SPARE 24 29 5.36 3.00 4.20 A 3% 1.10 C 26 25 PANEL'HLB' 175/3 SEE 30 31 RECEPT 6.46 4.10 0.00 B 1.10 A 28 27 (SUBFEED SPACE) SPARE RISER 33 DED RECEPT 20/1 SUBTOTAL CONNECTED LOAD: 132 3% 18.0 12.6 21.9 B 0.0 0.0 0.0 : SUBTOTAL CONNECTED LOAD 20/1 SPARE CONNECTED LOAD PHASE A: 23.6 DED RECEPT 20/1 CONTINUOUS & LARGEST MOTOR @ 25 %: 3.2 note 1 verify max. O.C.P.D. with nameplate CONNECTED LOAD PHASE B: 14.7 CONNECTED MOTOR LOADS @ 100 %: 21.9 note 2 lockable circuit breaker SPARE 36 CONNECTED LOAD PHASE C: 142 20/1 12 120 CONNECTED LIGHTING LOAD @100 %: 12.6 note 3 non - concurrent load A TOTAL CONNECTED LOAD: 52.5 20/1 FUTURE SHOW WIND LOAD note 4 G.F.C.I. type circuit breaker SPARE 30/2 RECEPT. CONNECTED LOAD: 18.0 RECEPEPTACLE COMPUTED LOAD: 14.0 note 5 photo cell controlled 20/1 FUTURE SHOW WIND LOAD 140 TOTAL COMPUTED LOAD: 52 KVA note 6 time switch controlled C 1.30 20/1 62 AMPS note 7 mechanically held lighting contactor SUBTOTAL CONNECTED LOAD: RISER DIAGRAM LEGEND SYMBOL DESCRIPTION LOADCENTERS - QO L.1A PANELBOARD - NQOD 277/480 PANELBOARD - NF ' PNLS SHALL BE MTD 0 +60" A.F.F, U.N.D ® METER MLO 5' -0" TO 6' -0" A.F.G. FEED THRU BUS ID1A 3R FUSED DISCONNECT 5' -0" TO 6' -0" A.F.G. aRMT MAIN CIRCUIT BREAKER 8 DISCONNECT 5' -0" TO 6' -0" A.F.G. GROUND SYSTEM TRANSIENT VOLTAGE SURGE SUPPRESSOR TVSS INTERMATIC SEE PNL SCHEDULE FOR MDL. Q LIGHTING CONTACTOR (MECHANICAL LATCH) O TIME- SWITCH BY INTERMATIC MDL#ET70815CR. EXISTING TO REMAIN I BOLD LINES DENOTE NEW WORK OR EQUIPMENT %UG"Im MMSFMMM NW t TYPICAL 208Y/120 � DRY TYPE TRANSF. PAIL SCIIEDIA88 NOTES 1. BOLD DENOTES AREA OF WORK FOR REFERENCE ONLY. 2. UPON DEMOLITION, CONTRACTOR SHAD_ IDENTIFY AND REUSE CIRCUITS THAT BECOME AVAILABLE, AND PROVIDE ENGINEER WITH COMPLETE AS BUILTS, REFER TO NOTE #31 OF THE ELECTRICAL SPECIFICATIONS. 3. IF AVAILABLE CIRCUITS FOR THIS SUITE ARE INSUFFICIENT, CONTACT ENGINEER IMMEDIATELY. 4. CONTRACTOR SHALL CLEARLY MARK IN PANEL SCHEDULE ALL CIRCUITS. 5. CONTRACTOR SHALL REMOVE ALL WIRING NOT USED AND NOT IN A RACEWAY GOING INTO CUENT SPACE. 6. CONTRACTOR SHALL MARK AS SPARE DEMO CIRCUIT NOT BEEN USED AND LEAVE THEM IN OFF POSITION. PANEL SCHEDULE L Rated Voltage: 120/208V 31PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 200A SPACES: 42 Location: SEE POWER PLAN Type: NEMA 1 Main: 150AMCB Project No: 12059.00 A.I.C: EXSITNG KVA KVA WIRE SIZE CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LGT /HEAT MOTOR PH RCPT LGT /HEAT MOTOR MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 1 COMBO WASHER/DRYER 3012 10 87 3% 2.50 A 1.20 110 3% 12 2011 SIGN 2 3 2.50 B 1.70 127 3% 10 2511 AHU -1 4 5 TT13 20/1 12 366 1 3% 0.36 1 C SPACE 6 7 CONV RECEPT 20/1 12 132 3% 1.00 A 1.30 101 3% 12 1 20/1 SHOW WINDOW RECEPT (note 6) 8 9 CONV RECEPT 20/1 12 132 3% 1.00 B 0.20 658 3% 12 20/1 LIGHTS 10 11 ROOM RECEPT 20/1 12 132 3% 1.00 C 1.30 101 3% 12 20/1 LIGHTS (note 7) 12 13 ROOM RECEPT 20/1 12 132 3% 1.00 A 0.20 658 3% 12 20/1 LIGHTS (note 7) 14 15 ROOM RECEPT 20/1 12 132 3% 1.00 B 1.00 132 3% 12 20/1 DED RECEPT 16 17 ROOM RECEPT 20/1 12 132 3% 1.00 C 1.00 132 3% 12 20/1 ROOM RECEPT 18 19 ROOM RECEPT 20/1 12 132 3% 1.00 A 1.50 88 3% 12 20/1 TOWEL WARMER 20 21 ROOM RECEPT 2011 12 132 3% 1.00 B 1.50 88 3% 1 12 20/1 TOWEL WARMER 22 23 ROOM RECEPT 20/1 12 132 3% 1.00 C 1.50 88 3% 12 20/1 WARMER 24 25 ROOM RECEPT 20/1 12 132 3% 1.00 A 20/1 SPARE 26 27 RECEPT 20/1 12 366 3% 0.36 B 2011 SPARE 28 29 RECEPT 2011 12 120 3% 1.10 C 20/1 SPARE 30 31 RECEPT 2011 12 120 3% 1.10 A 20/1 SPARE 32 33 DED RECEPT 20/1 12 132 3% 1.00 B 20/1 SPARE 34 35 DED RECEPT 20/1 12 132 3% 1.00 C 20/1 SPARE 36 37 RECEPT 20/1 12 120 3% 1.10 A 1.30 20/1 FUTURE SHOW WIND LOAD 38 39 SPARE 30/2 B 1.30 20/1 FUTURE SHOW WIND LOAD 140 41 C 1.30 20/1 FUTURE SHOW WIND LOAD 42 SUBTOTAL CONNECTED LOAD: 16.0 1 0.0 1 5.0 2.0 12.6 1.7 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 142 CONTINUOUS & LARGEST MOTOR @ 25 %: 3.2 note 1 verify max. O.C.P.D. with nameplate CONNECTED LOAD PHASE B: 12.6 CONNECTED MOTOR LOADS @ 100 %: 6.7 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 10.6 CONNECTED LIGHTING LOAD @100 %: 12.6 note 3 non - concurrent load TOTAL CONNECTED LOAD: 37.3 note 4 G F C.I. type circuit breaker RECEPT. CONNECTED LOAD: 18.0 RECEPEPTACLE COMPUTED LOAD: 14.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: 36 KVA note 6 time switch controlled 101 AMPS note 7 via lighting relay panel BRANCH CIRCUIT CONDUIT SIZE WIRE SIZE CONDUIT SIZE 12 1/2 10 1/2 8 3/4- 6 3/4- 4 1" 3 1 1 4' 2 1 1 2' 1 1 1 2" VOLTAGE DROP CALCULATIONS 1. 3% VOLTAGE DROP CALCULATED FOR EVERY BRANCH CIRCUIT SHOWS MAXIMUM DISTANCE ALLOWED FOR THE SPECIFIED WIRE SIZE BASED ON DESIGNED LOAD. 2. ALL CIRCUITS HAVE BEEN VERIFIED ON FLOOR PLANS BASED ON HORIZONTAL STRAIGHT RUNS WITH ADDITIONAL 30 FEET OF VERTICAL RUNS. ACTUAL DISTANCES FOR EVERY CIRCUIT RUN SHALL BE FIELD MEASURED BY THE ELECTRICAL CONTRACTOR. CONTRACTOR SHALL PROVIDE NEXT WIRE SIZE FOR RUNS OVER MAXIMUM DISTANCE SHOWN ON PANEL SCHEDULES. EXISTING PARTIAL ELECTRICAL RISER N.T.S. NOTES: 1. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC.2.1. 2. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC.2.2. OVERRIDE TIME SHALL BE SET AT 30 MINUTES MAX. 5:_0 WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS AN INSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I. THOMAS E. HENZ, P.E. #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING`?HE ENGINEERING SERVICES, 'HENZ ENGINEERING INC% HOLDS AN ACTIVE flt;':AUIFIORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. MAS PROJECT No.: 12059.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. Mf1VfMMTM - n�QNf1 DM - RAM 126 S. FEDERAL HIC*HWAY SUITE # 202 DAM BEACH, FLOFiDA 33004 PH' (954) 922 -6W 1 FAX: ,x.(./954) 922-7388 �7 ■CK069W9i19rCtedCan WEB: WWWl0ser18takwcNteeLcom STATE IREG. NO. AR0016674 NATL. REG. NO. 69178 COPYR[GNT ©2006 NOR8ERT0 ROG"IEAt ARCHMCT 24C. ALL RIGWM REBERvW. TM6 DOGJ'7FNT OR PAM T1EREOP, MAY Nat eE REPRODUCED IN ANY POW IIItTF10Ut PQQhQt36ION. DESIGNED ,4S DRAWN AS CHECKED I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, C13MPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2012 -37 2/14/2011 5701 SUNSET DA SUITE F08 ISIS WELLNESS NAILBAR SOUTH MIAMI FLORIDA, 33143 ELECTRICAL SPECS RISER & SCHD E-2 1 z i i i i I i I 1 f I 1 i i r I 1v I i i