12-900-009AIR CONDITIONING SPECIFICATIONS
L GENERAL:
A. ALL DIMENSIONS AND ACTUAL CONSTRUCTION CONDITIONS MUST BE VERIFIED AT THE
PROJECT SITE PRIOR TO SUBMITTING BID. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY.
B. THESE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE CLOSE COORDINATION WITH EXISTING
STRUCTURE, LIGHTS, CONDUITS, PLUMBING AND CEILING SYSTEM. THE CEILING SPACE IS
EXTREMELY TIGHT AND WILL REQUIRE CAREFUL ADVANCE PLANNING BEFORE DUCT
INSTALLATION. THE CONTRACTORS PRICE FOR THIS PROJECT SHALL INCLUDE A SITE VISIT
TO FIELD VERIFY, ALL COORDINATION, DUCT TRANSITIONS AND FIELD ROUTING AS
REQUIRED FOR A COMPLETE OPERATING AND TESTED SYSTEM.
C. SUBMIT MANUFACTURERS DATA AND SHOP DRAWINGS ON ALL EQUIPMENT, MATERIALS AND
DUCT SYSTEM LAYOUT FOR REVIEW BY THE ENGINEER PRIOR TO ORDERING, FABRICATION
OR INSTALLATION. PRIOR TO ORDERING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO VERIFY THAT EQUIPMENT VOLTAGE SPECIFIED IS AVAILABLE.
D. ALL MOTORS STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR TO BE
WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
E. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE FOLLOWING CODES:
I. THE FLORIDA BUILDING CODE 2010
2. NFPA -90A AIR CONDITIONING AND VENTILATION
3. SMACNA, LOW VELOCITY DUCT CONSTRUCTION
4. NFPA 101, LIFE SAFETY CODE
2. MATERIALS:
A. GALVANIZED STEEL SHEET METAL DUCT WORK INSTALLED IN ACCORDANCE WITH "SMACNA"
STANDARDS WITH R -6 FIBERGLASS DUCT WRAP INSULATION. PROVIDE MANUAL VOLUME
DAMPERS AT ALL BRANCH TAKE -OFFS. PROVIDE TURNING VANES AT ALL ELBOWS.
FLEXIBLE ROUND DUCTS MAY BE USED FOR DIFFUSER DROPS AS SHOWN ON PLANS.
SUBMIT SHOP DRAWINGS.
B. ALL CEILING DIFFUSERS SHALL HAVE OPPOSED BLADE DAMPERS.
C. OUTSIDE AIR AND EXHAUST DUCTS SHALL BE AIR LEAK SEALED GALVANIZED SHEET METAL
3. TEST AND BALANCE:
A. AN AABC OR NEBB CERTIFIED INDEPENDENT TEST AND BALANCE COMPANY SHALL BALANCE
THE SYSTEM TO DESIGN VALUES ON THE DRAWINGS TO WITHIN PLUS 10% OR MINUS 5X
PROVIDE WRITTEN REPORT TO DOCUMENT AIR SYSTEM PERFORMANCE, MOTOR SPEED, AMPS,
SUPPLY AND EXHAUST FAN CFM VALUES AND AIR CONDITIONING PERFORMANCE FOR
ENGINEER REVIEW PRIOR TO PROJECT COMPLETION. IT IS THE RESPONSIBILITY OF THE TEST
AND BALANCE COMPANY TO PERFORM MODIFICATIONS TO THE SPECIFIED EQUIPMENT, BELTS,
PULLEYS ETC. TO ACHIEVE THE DESIGN VALUES LISTED ON THE DRAWINGS.
4. CONTRACTOR'S WARRANTY:
A. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR ALL EQUIPMENT AND SYSTEMS
FROM DATE OF FINAL ACCEPTANCE BY THE OWNER, (CERTIFICATE OF OCCUPANCY).
HVAC SYMBOL LEGEND:
(D
THERMOSTAT
PANEL-
ROOF MTD. EXH. FAN
(D
REMOTE BULB SENSOR
DUCT TURN DOWN
®
DUCT SMOKE DETECTOR
MOUNT
(DUCT OPENING SIZES):
MAXIMUM
PANEL:-
60 "x54"
DUCT TURN UP
®
TEST, RESET &ANNUNCIATOR
"ft-'0
4 "x4"
83 W
VOLTS
115/1 /60
FLEXIBLE DUCT
MANUF.
TRANSITION
ME
MODEL NO.
SP -1380
DBF4XLT
NOTES
EXISTING SUPPLY
3,5
TURNING VANE
FOE
Vot = Voz - QUATION
4-3)
AHU -1 OUTSIDE AIR
RETAIL NET FLOOR AREA = 8CSQFT
EXISTING RETURN
800 X 15/1000 = 12 PEOPLE
45' BRANCH DUCT TAKE -OFF
®R
RELOCATED
VOZ = (186)/(1.0) = 186 CFM
1 -WAY
Vot = 186 CFM
SUPPLY
NOTES: BALANCE AHU -1 TO 19CFM 0 /A.
HORIZONTAL FIRE DAMPER
RELOCATED RETURN
R
R
D.
MANUAL VOLUME DAMPER
FN
NEW SUPPLY
SEE NOTE
RETURN REGISTER
24x24
FILTER BACK RETURN
SUPPLY DIFFUSER
17IN
NEW RETURN
RETURN AIR GRILLE
FIRE DAMPER
COMBINATION FIRE /SMOKE DAMPER
AIR FLOW DIRECTION
NOTES:
1. ALL AIR DISTRIBUTION DEVICES SHALL BE OF ALUMINUM CONSTRUCTION.
2. FINISH FOR ALL AIR DISTRIBUTION DEVICES SHALL BE AS SELECTED BY ARCHITECT /OWNER
3. PROVIDE INSULATING BLANKETS ON
�
MOTORIZED DAMPER
®
EXHAUST FAN
-D4-
VALVE
NOTES:
GYPSUM WA
RETAINING ANGLE
1 1/4x1 1/4 x1/8" al
GYPSUM FILLER
DAMPER S
VERTICAL MOUNT
U.L. SIZE LIMITATIONS
VERTICAL MOUNT
(DUCT OPENING SIZES);
MAXIMUM
PANEL-
60 "x54"
MAXIMUM
ASSEMBLY: 120 "x114"
MINIMUM
PANEL:
4 "x4"
HORIZONTAL
MOUNT
(DUCT OPENING SIZES):
MAXIMUM
PANEL:-
60 "x54"
MAXIMUM
ASSEMBLY. 102 "x54"
MINIMUM
PANEL-
4 "x4"
FAN SCHEDULE
MARK
EF -1
DF -1
USE
TOILET
DRYER
CFM
69
103
S.P. IN WATER
0.250
0.8"
RPM
900
1000
DRIVE
DIRECT
DIRECT
HP/WATTS
54 W
83 W
VOLTS
115/1 /60
115/1 /60
MANUF.
GREENHECK
FANTECH
MODEL NO.
SP -1380
DBF4XLT
NOTES
1,4
3,5
I. PROVIDE BACKDRAFT DAMPER
2. PROVIDE BUG SCREEN
3. PROVIDE WALL CAP
4. CONTROLLED BY WALL SWITCH
5. CONTROLLED BY PRESSURE SWITCH
OUTSIDE AIR CXULATION:
FLORIDA MECHANICAL COD010 TABLE 403.3
OCCUPANCY
Rp
R,,
CFM/ NECK SIZE
OCC. DENSITY
CLASSIFICATION
CFM/PERSON
FM /FT" 2
TMS -AA
# /1000 FT" 2
OFFICE SPACES
5
0.06
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
5
RETAIL SALES
7.5
0.12
C
15
DINING ROOMS
7.5
0.18
70
Vbz = Rp Pz + Ra A - EQUATION
4 -1)
Vbz
Vo` EQUATION
4 -2)
E,
SUPPLY
SINGLE ZONE SYSTEMS
Vot = Voz - QUATION
4-3)
AHU -1 OUTSIDE AIR
RETAIL NET FLOOR AREA = 8CSQFT
250 -AA
800 X 15/1000 = 12 PEOPLE
OBD
Vb, _ (7.5)(12) +(0.12)(800) =86 CFM
VOZ = (186)/(1.0) = 186 CFM
1 -WAY
Vot = 186 CFM
NOTES: BALANCE AHU -1 TO 19CFM 0 /A.
AIR DISTRIBUTION SCHEDULE: � �;'
YES
MARK
MAKE
MODEL
CFM/ NECK SIZE
DAMPER
REMARKS
A
TITUS
TMS -AA
60 -100 CFM 06 "0 NECK
OBD
SEE NOTE
B
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
24x24
105 -200 CFM 08 "0
FIRE STOPPING
C
SMOKE CONTROL
205 -350 CFM 10 "0
D
LAY IN
355 -550 CFM 12 "0
E
SUPPLY
555 -800 CFM 14 "0
F
TITUS
250 -AA
100 CFM 8x8 NECK
OBD
SEE NOTE
1 -WAY
SUPPLY
R
TITUS
350FLF
0 -2000 CFM 20x20 NECK
SEE NOTE
24x24
FILTER BACK RETURN
RETURN
NOTES:
1. ALL AIR DISTRIBUTION DEVICES SHALL BE OF ALUMINUM CONSTRUCTION.
2. FINISH FOR ALL AIR DISTRIBUTION DEVICES SHALL BE AS SELECTED BY ARCHITECT /OWNER
3. PROVIDE INSULATING BLANKETS ON
BACKS OF SUPPLY DIFFUSERS.
4. REFER TO CONTRACT DRAWINGS AND SPECIFICATIONS FOR OTHER ACCESSORIES
AND /OR REQUIREMENTS.
NOTES:
1. UNDERWRITERS LABORATORIES LISTED AND
1-1/2 HOUR STANDARD 555, CLASS 'A
2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL
3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS.
4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS.
NAILOR -HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE"
FUSIBLE LINK TEMPERATURE: 1657
FIRE DAMPER DETAIL:
NOT TO SCALE
SUPPORT FROM STRUCTURE
® /NEOPRENE
VIBRA71ON
TYPE ISOLATORS
AND 3/8" HANGER RODS
FROM CONTROLS
DTR TO CONTROLS MANUAL AIR VENT %LVE
DTS I PIPE 1/4" LINE TO OND. PAN
NOTE 1 AUTOMATIC AIR =NT VALVE
RET. AIR DUCT PIPE 1/4- LINE) COND. PAN
(REFER HVAC PLAN) O
1 Tq COIL
R. A. �!t!`� `; �" -- -T
I 1 i rJ j S.A.
FILTER
FINISHED CEILING
FLEXILE CONNECTION, TYP.
HINGED CABINET DOOR AUX. DRAII PAN WITH FLOAT SWITCH.
TO PROVIDE FULL ACCESS INSULATED TRAPPED SUMMER/WINTER CHANGE FAN
COND.DRAIN(REFER OVER STRAP-ON AQUASTAT INSULATED CONDENSATEPAN
ENLG'D. HVAC PLAN (INSULATE OVER AQUASTAT)
FOR ROUTING) PROVIDE CONDENSATE RMP.
NOTES:
1. AL ED EQUIPMENT SECTION I INSULATION R LHA2. LL VVES LP PINGAN SHWN TO BE LOCATED COIUMT�BI ET
WITH ACCESS FROM BELOW UNIT.
FAN COIL UNIT PIPING SCHEMATIC
(DUCTED INSTALLATION) NOT TO SCALE
MANUAL DAMPER W/
LOCKING ADJUSTMENT
HANDLE
BRANCH
DUCT -
BRANCH
� I
I
I
I
TRUNK DUCT
DIRECTION OF
DIR CTION OF AIR FLOW
AIR FLOW L45' BRANCH DUCT
CONNECTION
TEE
'M MUM^ vA►ure-
3/4" COPPER
CONDENSATE DRAIN WITH
1" K -FLEX INSULATION
TO EXISTING RISER.
FIELD VERIFY EXACT
LOCATION.
EXISTING 1" CHILLED WATE
LINES. EXTEND CHILLED
WATER LINES TO NEW AHL
LOCATION. USE 1" COPPE
WITH 2" K -FLEX
INSULATION. PROVIDE NEW
ISOLATION VALVES AND
2 -WAY VALVE.
RAISE AHU MINIMUM 18"
ABOVE CEILING.
MECHANICAL PLAN
qi,P
Oh,
w
CIRCULAR DUCT FOR
CONNECTION TO FLEX DUCT
PROVIDE CLASS 1 FLEX
DUCT TO DIFFUSERS.
45' FLARED TAP MAIN TRUNK DUCT
INTO TRUNK DUCT
MANUAL VOLUME DAMPER.
FURNISH CABLE OPERATED REMOTE '20y,
CONTROLLED VOLUME DAMPERS IN
BRANCH DUCTS LOCATED IN
INACCESSIBLE CEILINGS.
ROUND NECK CEILING DIFFUSER
SPIN COLLAR DETAIL:
SPUTTER
DAMPER
BLADE
LSPUTTER DAMPER CONTROL
ROD W/ LOCK
HANGING
HANG ALL DUCT PER SMACNA STANDARDS
CHANNEL
STRAP & SADDLE
NOT TO SCALE
ELBOW
coRr...,..
TURI
HVAC DUCT DETAILS
NOT TO SCALE
4 NEW OUTSIDE AIR
�T TO EXISTING MAIN
(SIDE AIR DUCT. FIELD
21FY EXACT LOCATION.
4 NEW TOILET
iAUST TO EXISTING
IN EXHAUST DUCT.
LD VERIFY EXACT
'.ATION.
architect
NORBERTO ROSENSTEIN
ARCHITECT INC.
ARCH16CTH - HrM DPI - FLAW
126 S. FEDERAL HIGHWAY
SURE f 202
DAM BEACH, FLORIDA 33004
PH: (954) 922 -6551
FAX- (954) 922 -7388
E1ML*do9ro9enstekwc Nteckc omm
WEB WWWIO®9I18tekwcI'11teC'LCOII'1
STATE REG. NO. AR0016674
NATL. REG. NO. 69178
COPYMWT Q20e
NOIRMWO ROSENSTEAI ARCHITECT, 24C.
ALL RSGHTS RESERVED. THIS DOCUMENT
OR PARTS I 14 RSOK MAY NOT ft R£PRODUCSD
IN ANY FORM UTHOUT PERI IISSIOK
DESIGNED
DAS
DRAWN
DAS
CHECKED
DAS
I HEREBY CERTIFY THAT THESE PLANS
:R
YLIC WHERE PREPARED BY ME OR UNDER
,R
DT BE MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES,
l
VC>
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
FIRE DAMPER(S)
SMOKE DAMPER(S)
FIRE RATED ENCLOSURE
V,
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
FIRE STOPPING
SMOKE CONTROL
WARNING!
MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG
ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND
LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL
REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE
PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS.
CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING
PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS.
'0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITI
'OMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDIN(
'ODES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS At
NSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE
_XPRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC.
1, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN
THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO
PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN.
I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE
CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE
COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN
ACTIVE CERIfJMTAQF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE.
�% �i
P' "sH•M' �I�f1Z �(1GIfl��RIf1G If1C.
�G� E -
• Na 5ggg2 congflTin miu[as
cc
240 Commercial Blvd 2A
LL
C * Lauderdale By The Sea, FL 33308
OF
1I q• q .�E T954.523.4933
F 954.523.5052
- -ice 0 F L O pk' `*G�.` �.henz,com
''�•,FSS�ONP� �``� PROJECT No.: 12059.00
R E V I S 1 0 N S
COMM. DATE
2012 -37 2/14/2011
5701 SUNSET DR
SUITE FOB
ISIS WELLNESS
NAILBAR
SOUTH MIAMI
FLORIDA, 33143
MECHANICAL
PLAN,
M -1 OF 1